- Home
- BACnet instance calculators
- Lennox VRF BACnet gateway V0CTRL95P-3
BACnet instance calculator · VRF BACnet gateway V0CTRL95P-3
Lennox VRF BACnet Gateway Device ID Calculator
Free browser tool · nothing is uploaded · 5 November 2026
The Lennox V0CTRL95P-3 makes every VRF indoor and outdoor unit its own BACnet device, with a 4-digit device ID built from the bus, the unit type and the unit address.
Device ID = bus | type | address: bus (port) 0-3, type 0 for indoor or 1 for outdoor, then the 2-digit unit address. Bus 1, indoor unit 12 is 1012; bus 0, outdoor unit 5 is 105 (written 0105). Inside each device the object instances are fixed.
Lennox calculator
The calculator needs JavaScript. The formula and a worked example are below.
Which unit is this device?
How the numbers are built
device ID = bus x 1000 + type x 100 + address
| Part | Meaning | Range |
|---|---|---|
| bus | RS-485 bus (port) on the gateway | 0-3 |
| type | 0 = indoor unit, 1 = outdoor unit | 0-1 |
| address | Unit address (indoor 00-63, outdoor 00-31) | 00-63 |
Lennox's own examples are 0001 (bus 0, indoor unit 01) and 1105 (bus 1, outdoor unit 05). A leading zero is dropped in the real device instance.
Worked example: bus 1, indoor unit 12
The first objects for bus 1, indoor unit 12 on the V0CTRL95P-3, worked out with the formula above:
| Unit type | Device instance | For |
|---|---|---|
| Indoor unit device | 1012 | Bus (port) 1, Indoor unit address 12 |
| Outdoor unit device | 1105 | Bus (port) 1, Outdoor unit address 5 |
Source
Formula and objects from VRF BACnet Gateway V0CTRL95P-3, Lennox VRF VRB & VPB Systems - User and Application Guide · 507951-02 · rev. 12/2022 (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.
Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.
Questions
How do I work out a Lennox instance number?
Device ID = bus | type | address: bus (port) 0-3, type 0 for indoor or 1 for outdoor, then the 2-digit unit address. Bus 1, indoor unit 12 is 1012; bus 0, outdoor unit 5 is 105 (written 0105). Inside each device the object instances are fixed.
Why do indoor and outdoor Lennox devices have the same object numbers?
Each unit is its own BACnet device, so AI 1 is room temperature inside an indoor unit device and ambient temperature inside an outdoor unit device. The device ID tells you which one you are reading.
Is this Lennox calculator official?
No. It applies the formula printed in Lennox's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.
More instance calculators
- Fujitsu UTY-VBGX VRF gatewayFujitsu's UTY-VBGX gateway puts the refrigerant system and unit address inside every instance number.
instance = point code x 10000 + refrigerant system x 100 + unit address - Mitsubishi Electric BAC-HD150 BM AdapterThe BAC-HD150 BM Adapter numbers every CITY MULTI group's objects as M-NET number, group number and point number.
instance = M-NET number x 10000 + group x 100 + point - Mitsubishi Electric AE-C400 / EW-C50With the BACnet license, the AE-C400 and EW-C50 number objects by class, address and point.
instance = class x 10000 + address x 100 + point - Mitsubishi Electric PAC-YG31CDA (G-50A)The legacy PAC-YG31CDA BACnet interface serves up to ten G-50A controllers and numbers each group's objects by G-50A number, group and point.
instance = G-50A number x 10000 + group x 100 + point - Mitsubishi Electric Procon BAC-IP/50The Procon BAC-IP/50 gives every unit on its G-50 a block of objects numbered 1, the 3-digit unit address and the point number.
instance = 100000 + unit address x 100 + point - Daikin DMS502B71 VRV BACnet interfaceThe Daikin DMS502B71 BACnet interface gives every VRV indoor unit group the same 35-member object template.
instance = unit number x 256 + member number - Toshiba BMS-IFBN1281U BN interfaceToshiba Carrier's BN interface gives every indoor unit the same block of objects, numbered from the unit's central control address and a fixed function code.
instance = central control address x 256 + function code - Gree GMS GW BACnet converterGree's GMS GW 1 and GMS GW 12 converters number every split unit's objects from its line and remote control address.
instance = class x 1048576 + (line - 1) x 131072 + address x 256 + object