VRF BACnet IP gateway · BACnet points list

Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet points list

Updated 28 October 2026

Short answer

The V0CTRL95P-3 connects Lennox VRF systems to a BMS over BACnet IP, with four RS-485 buses to the VRF units and an Ethernet port. Each indoor and outdoor unit appears as its own BACnet device whose device ID encodes the bus, unit type and unit address; inside each device the object instances are fixed, so one indoor template and one outdoor template cover the site. Indoor units take on/off, mode, fan speed and setpoint commands; outdoor units are mostly monitoring plus an emergency stop.

This page lists 42 BACnet objects for the Lennox VRF BACnet Gateway V0CTRL95P-3 — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lennox’s own free documentation, linked below.

Manufacturer
Lennox
Model
VRF BACnet Gateway V0CTRL95P-3
Equipment
VRF BACnet IP gateway
Equipment type
VRF & split air conditioners
BACnet objects
42 (13 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
V0CTRL95P-3, V0CTRL95P, Lennox VRF BACnet gateway, VRB BACnet gateway, VPB BACnet gateway, 507951
Source document
VRF BACnet Gateway V0CTRL95P-3, Lennox VRF VRB & VPB Systems - User and Application Guide · 507951-02 · rev. 12/2022
Download CSV 42 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lennox VRF BACnet Gateway V0CTRL95P-3

Integration in brief

Connect the VRF buses to the gateway's four RS-485 ports, set the gateway's IP settings from a web browser, then discover the per-unit BACnet devices. Map each indoor unit's on/off, mode, fan speed and setpoint commands plus room temperature and alarm; outdoor unit devices are for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1On/Off SettingStart/stop indoor unitWrite
MV 1Mode SettingMode command (3 = cool, 4 = heat, 5 = auto)Write
AV 1Temperature SettingSetpoint commandWrite
MV 2Fan Speed SettingFan speed command (8 = auto)Write
AI 1Room TemperatureIndoor unit room temperatureRead
BI 2Alarm IndicationIndoor unit has an error codeRead

Enable & remote start

No enable point is documented. Wired and wireless controller locks (BV 5, BV 4) and mode/fan locks (MV 3, MV 5) restrict local changes.

Network setup

Watch out for

Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

42 of 42 shown
Type
Access
Show
Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet Points List
DescriptionStates
BVmin1On/Off Setting[Indoor unit] On/off commandWrite0=Off; 1=On
MVmin1Mode Setting[Indoor unit] Mode commandWrite1=Off; 2=Fan; 3=Cooling; 4=Heating; 5=Auto; 6=Dry
MVmin2Fan Speed Setting[Indoor unit] Fan speed commandWrite1-2=Low; 3-4=Medium; 5-7=High; 8=Auto; 9=Off
AVmin1Temperature Setting[Indoor unit] Setpoint for cool, heat and dry, 62-86 °F°F/°CWrite
AV2Dual Point (Cooling) Setting[Indoor unit] Auto mode cooling setpoint°F/°CWrite
AV3Dual Point (Heating) Setting[Indoor unit] Auto mode heating setpoint°F/°CWrite
AV4Cool Temperature Limit Setting[Indoor unit] Lowest allowed cooling/auto/dry setpoint°F/°CWrite
AV5Heat Temperature Limit Setting[Indoor unit] Highest allowed heating/auto heating setpoint°F/°CWrite
MV3Mode Limit Setting[Indoor unit] Mode lockWrite0=Unlocked; 1=Locked in cooling; 2=Locked in heating
MV5Fan Lock/Unlock Setting[Indoor unit] Fan speed lockWrite1-2=Locked low; 3-4=Locked medium; 5-7=Locked high; 8=Unlocked
BV4Remote Control Lock Setting[Indoor unit] Wireless remote lockWrite0=Unlocked; 1=Wireless control locked
BV5Controller Lock Setting[Indoor unit] Wired controller lockWrite0=Unlocked; 1=Wired control locked
AImin1Room Temperature[Indoor unit] Room temperature sensor value°F/°CRead
BImin2Alarm Indication[Indoor unit] Error code presentRead0=No malfunction code; 1=Malfunction code
AI9EXV Opening[Indoor unit] Electronic expansion valve openingRead
AI10Software Version[Indoor unit] Software versionRead
AI11Indoor type[Indoor unit] Indoor unit seriesRead1=V33B four-way cassette; 2=VWMB wall mounted; 3=VMDB medium static duct; 5=VVCB vertical air handler; 6=VHIB high static duct; 7=V22B compact four-way cassette; 8=VCFB ceiling/floor; 11=VOSB outside air duct; 14=VOWA one-way cassette; 21=AHU control kit
AI12Indoor Capacity[Indoor unit] Indoor unit capacity codeRead8=7k; 10=9k; 12=12k; 17=15k; 20=18k; 25=24k; 32=30k; 40=36k; 50=48k; 60=54k; 65=60k; 80=72k; 100=96k Btu/h
MI1Mode Status[Outdoor unit] Operating modeRead1=Off; 2=Reserved; 3=Cooling; 4=Heating; 5=Cooling test; 6=Mix cooling; 7=Mix heating; 8=Heating test
BI1On/Off Status[Outdoor unit] Run statusRead0=Off; 1=On
AI1Ambient Temperature[Outdoor unit] Outdoor ambient temperature°F/°CRead
AI2Compressor 1 Freq.[Outdoor unit] Main compressor frequencyHzRead
AI3Compressor 2 Freq.[Outdoor unit] Sub compressor frequencyHzRead
AI4Compressor 1 Discharge Temp.[Outdoor unit] Main compressor discharge temperature°F/°CRead
AI5Compressor 2 Discharge Temp.[Outdoor unit] Sub compressor discharge temperature°F/°CRead
AI6High Pressure[Outdoor unit] Discharge pressurepsiRead
AI7Low Pressure[Outdoor unit] Suction pressurepsiRead
AI9Fan 1 Speed[Outdoor unit] Fan 1 speed step (not rpm)Read
AI10Fan 2 Speed[Outdoor unit] Fan 2 speed step (not rpm)Read
BI2Alarm Indication[Outdoor unit] Error code presentRead0=No malfunction code; 1=Malfunction code
AI11T3[Outdoor unit] Left condenser temperature°F/°CRead
AI12T3B[Outdoor unit] Right condenser temperature°F/°CRead
BI4SV2[Outdoor unit] Solenoid valve SV2 statusRead0=Off; 1=On
BI6SV4[Outdoor unit] Solenoid valve SV4 statusRead0=Off; 1=On
BI11ST1[Outdoor unit] Reversing valve ST1 statusRead0=Not energized; 1=Energized
BI12ST2[Outdoor unit] Reversing valve ST2 statusRead0=Not energized; 1=Energized
AI13Version[Outdoor unit] Main PCB software versionRead
AI14Outdoor type[Outdoor unit] Outdoor unit typeRead0=Mini VRF; 1=VRF
AI15Outdoor horses[Outdoor unit] Outdoor unit capacitytonRead
AI16Exv1 opening[Outdoor unit] EEV A openingpulseRead
AI17Exv2 opening[Outdoor unit] EEV B openingpulseRead
BV1Emergency Stop[Outdoor unit] Emergency stop commandWrite0=None; 1=Emergency stop

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VRF BACnet Gateway V0CTRL95P-3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lennox VRF BACnet Gateway V0CTRL95P-3

How many BACnet points does the Lennox VRF BACnet Gateway V0CTRL95P-3 have?

This list has 42 BACnet objects: 21 analog inputs, 5 analog values, 7 binary inputs, 4 binary values, 1 multi-state input, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet points are writable?

13 of the 42 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet documentation?

The source is VRF BACnet Gateway V0CTRL95P-3, Lennox VRF VRB & VPB Systems - User and Application Guide (507951-02), revision 12/2022, published free by Lennox at https://www.lennox.com/dA/020b57558a/507951-02.pdf.

What are the minimum BACnet points to integrate the Lennox VRF BACnet Gateway V0CTRL95P-3?

Start with BV 1 On/Off Setting (Start/stop indoor unit); MV 1 Mode Setting (Mode command (3 = cool, 4 = heat, 5 = auto)); AV 1 Temperature Setting (Setpoint command); MV 2 Fan Speed Setting (Fan speed command (8 = auto)); AI 1 Room Temperature (Indoor unit room temperature); BI 2 Alarm Indication (Indoor unit has an error code).

How do I enable BMS control of the Lennox VRF BACnet Gateway V0CTRL95P-3?

No enable point is documented. Wired and wireless controller locks (BV 5, BV 4) and mode/fan locks (MV 3, MV 5) restrict local changes.

How do I check these points on the real VRF BACnet Gateway V0CTRL95P-3?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lennox BACnet points lists

Source: VRF BACnet Gateway V0CTRL95P-3, Lennox VRF VRB & VPB Systems - User and Application Guide · 507951-02 · rev. 12/2022. Object names, instances and units are reproduced as published; descriptions are our own.