Rooftop unit controller BACnet module · BACnet points list

Lennox Prodigy M3 BACnet Module BACnet points list

Updated 28 October 2026

Short answer

The M3 BACnet module plugs onto a Lennox Prodigy M3 rooftop unit controller and exposes it as a BACnet MS/TP device (BTL listed, B-ASC). The BAS drives the unit by writing Analog Outputs (mode, occupancy, setpoints, enables) and reads status from Analog Inputs; occupied/unoccupied setpoints live in Analog Values. The device instance defaults to the MS/TP MAC address. The module expects regular writes from the BAS; if they stop, it times out and falls back to its local control mode.

This page lists 83 BACnet objects for the Lennox Prodigy M3 BACnet Module — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lennox’s own free documentation, linked below.

Manufacturer
Lennox
Model
Prodigy M3 BACnet Module
Equipment
Rooftop unit controller BACnet module
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
83 (33 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Same as MS/TP MAC address
Also known as
M3 BACnet Module, BM2, Prodigy M3, Lennox_M3, Prodigy 2.0 BACnet, 1404-L4
Source document
M3 BACnet Module (Unit Information) · Corp 1404-L4 (450402) · rev. 2018-10
Download CSV 83 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lennox Prodigy M3 BACnet Module

Integration in brief

Enable the BACnet module in the M3 setup wizard and set the MAC address, baud and Control Mode. In Room Sensor mode the BMS writes occupancy (AO104) and setpoints (AO109 or AV130-133), and can supply space temperature on AO113. In Network Thermostat mode it sends heat/cool/fan demands on AO101 instead. The M3 does not store commands, so every control point in use must be rewritten on a schedule and after every controller reset.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 104Occupancy Scheduler Control0 = occupied, 1-255 = unoccupied; rewrite every 7 minCommand
AO 101Application Mode ControlMode or direct demand commandCommand
AV 130Heating Occupied SetpointOccupied heating setpoint, 40-95 °FWrite
AV 131Cooling Occupied SetpointOccupied cooling setpoint, 40-95 °FWrite
AV 132Heating Unoccupied SetpointUnoccupied heating setpoint, 40-95 °FWrite
AV 133Cooling Unoccupied SetpointUnoccupied cooling setpoint, 40-95 °FWrite
AI 232Unit StatusHVAC state code: 0 idle, 1 heat, 3 cool, 6 off, 9 fanRead
AI 239Space TemperatureSpace temperature in useRead
AI 253Current ErrorActive alarm codeRead

Enable & remote start

At the M3: SETUP > INSTALL wizard, set Configuration ID 1 position 5 to B to enable the BACnet module. Then SETUP > NETWORK INTEGRATION > BACNET to set the address, baud and CONTROL MODE (Monitor Only, Room Sensor, Network Thermostat, Zone or Remote). In Monitor Only the unit ignores network setpoints and mode demands. No occupancy jumper is needed for Zone/Remote modes.

Heartbeat & communication loss

Network space temperature (AO113) and space RH/CO2 must be rewritten at least every 5 minutes (2-minute interval recommended), or an alarm is raised; some of these alarms only clear with a local reset. AO101 (network thermostat demand), AO109, AV130-133 and AO104 (when not using setpoint control) must be rewritten within 15 minutes (7-minute interval recommended). Without network sensor data for 5 minutes the unit shows Alarm 73. In Room Sensor mode with BACnet setpoints, 15 minutes with no application-level BACnet traffic makes the RTU reset. In Network Thermostat mode, 15 minutes without demands switches it to its backup mode. After losing network data the unit defaults to occupied (Parameter 225 changes this).

Sensors & values from the BMS

Space temperature goes to AO113 (Space Temperature Input) when CONTROL MODE = ROOM SENSOR with network TEMPERATURE = YES. Space RH and CO2 are written to the proprietary space air object properties 536 and 537. Before network sensor data arrives the unit idles up to 5 minutes (Alarm 110), then enters backup sensor mode (Alarm 93). The points list has no network outdoor-air-temperature input.

Network setup

Watch out for

Lennox Prodigy M3 BACnet Module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

83 of 83 shown
Type
Access
Show
Lennox Prodigy M3 BACnet Module BACnet Points List
DescriptionStates
AOmin101Application Mode ControlUnit mode, fan, exhaust and stage command (coded)Command0=Auto; 1=Heat; 3=Cool; 6=Off; 9=Fan only; 208=Fan auto; 209=Fan on; 216-222=Power exhaust commands; 224-236=Direct stage commands; 254=Reset; 255=Null (Auto)
AO102Outdoor Air Min Pos ControlRange 0 to 255%Command
AO103Occupancy Override ControlRange 0 to 255Command0=Occupied; 1=Unoccupied; 2=Refresh occupied override timer
AOmin104Occupancy Scheduler ControlRange 0 to 255Command
AO107Occupancy Sensor InputRange 0 to 255Command0=Sensor sees occupied; 1=Sensor sees unoccupied
AO108Space Dehumidification SetpointRange 0 to 100%Command
AO109Temperature Setpoint (abs)Range 36.25 to 100°FCommand
AO110Temperature Setpoint OffsetRange -32 to 31.75°FCommand
AO113Space Temperature InputRange 36.25 to 100°FCommand
AO114Emergency Override ControlRange 0 to 255Command
AO115Compressor Enable ControlRange 0 to 255Command
AO117Primary Heat Enable ControlRange 0 to 255Command
AO119Auxiliary Heat Enable ControlRange 0 to 255Command
AO123Duct Static SetpointRange 0 to 5in. w.c.Command
AO124Building Static SetpointRange -0.5 to 0.5in. w.c.Command
AO125Discharge Air Cooling SetpointRange -9,40-100°FCommand
AO126Discharge Air Heating SetpointRange -9,60-140°FCommand
AO127Supply Fan Capacity InputRange 33 to 255%Command
AO128Exhaust Fan Capacity InputRange 33 to 255%Command
AO129Set Economizer Outdoor Air SuitableRange 0 to 255Command0=Economizer disable; 1=Economizer enable
AI198Mac AddressRange 0 - 127Read
AI199IMC AddressRange 1-31Read
AI200IMC Version[4]Range 0 - 127; legacy, not for new installsRead
AI201IMC Version[5]Range 0 - 127; legacy, not for new installsRead
AI202IMC Version[6]Range 0 - 127; legacy, not for new installsRead
AI203IMC Version[7]Range 0 - 127; legacy, not for new installsRead
AI204IMC Version[8]Range 0 - 127; legacy, not for new installsRead
AI205IMC Version[9]Range 0 - 127; legacy, not for new installsRead
AI206IMC Version[10]Range 0 - 127; legacy, not for new installsRead
AI207IMC Version[11]Range 0 - 127; legacy, not for new installsRead
AI231Unit IDRange 0 - 127Read
AImin232Unit StatusRange 0 - 255Read
AImin239Space TemperatureRange 63.75 - 100.00°FRead
AI240Discharge Air TemperatureRange -8.7 - 164.4°FRead
AI241Effective OccupancyRange 0 - 2Read0=Occupied; 1=Unoccupied; 2=Occupied (timed override)
AI242Local Outside Air TemperatureRange -30.6 - 131.6°FRead
AI243Local Space TemperatureRange 63.75 - 100.00°FRead
AI244Outside Air DamperRange 0 - 100, 255%Read
AI245Heat PrimaryRange 0 - 100%Read
AI246Heat SecondaryRange 0 - 100%Read
AI247Cool PrimaryRange 0 - 100%Read
AI248Economizer EnabledRange 0, 1, 255%Read0=Disabled; 1=Enabled (OA suitable); 255=No economizer
AI250Supply Fan StatusRange 0 - 100%Read
AI252Space Temperature Set Point (Effective)Range 40.0 - 95.0°FRead
AImin253Current ErrorRange 0 - 255Read
AI254Error PointerRange 0 - 83Read
AI255Most recent Error 1Range 1 - 255Read
AI256Most recent Error 2Range 1 - 255Read
AI257Most recent Error 3Range 1 - 255Read
AI258Most recent Error 4Range 1 - 255Read
AI259Most recent Error 5Range 1 - 255Read
AI260Most recent Error 6Range 1 - 255Read
AI261Most recent Error 7Range 1 - 255Read
AI262Most recent Error 8Range 1 - 255Read
AI263Most recent Error 9Range 1 - 255Read
AI264Most recent Error 10Range 1 - 255Read
AI274Space CO2 Sensor (Effective)Range 0 - 2000ppmRead
AI275Space CO2 Sensor (Local)Range 0 - 2000ppmRead
AI276Space Humidity (Effective)Range 0 - 100%Read
AI277Space Humidity (Local)Range 0 - 100%Read
AI278Dehumidification Set Point (Effective)Range 0 - 100%Read
AI279Dehumidification StatusRange 0 - 2Read0=Not installed; 1=Installed, not running; 2=Installed and running
AI281Return Air TemperatureRange -8.7 - 164.4°FRead
AI282Building Static PressureRange -0.5 - 0.5in. w.c.Read
AI283Duct Static PressureRange 0 - 5.00in. w.c.Read
AI285Exhaust Fan StatusRange 0 - 100%Read0=Off; 1=Stage 1 on; 2=Stage 2 on; 255=No exhaust
AI286Supply airflow statusRange 0 - 480 CFM per ton of unit sizeCFMRead
AI287Blower motor speedRange 0 - 1500RPMRead
AI288Blower motor torqueRange 0 - 100%Read
AI289Outdoor airflowRange 0 - 480 CFM per ton of unit sizeCFMRead
AV1Baud Rate SettingRange 9600, 19200, 38400, 76800Write
AVmin130Heating Occupied SetpointRange 40 to 95°FWrite
AVmin131Cooling Occupied SetpointRange 40 to 95°FWrite
AVmin132Heating Unoccupied SetpointRange 40 to 95°FWrite
AVmin133Cooling Unoccupied SetpointRange 40 to 95°FWrite
AV134Supply airflow Low Speed TargetSmartAirflow units onlyCFMWrite
AV135Supply airflow High Speed TargetSmartAirflow units onlyCFMWrite
AV136Supply airflow Medium Low Speed TargetSmartAirflow units onlyCFMWrite
AV137Supply airflow Medium High Speed TargetSmartAirflow units onlyCFMWrite
AV138Supply airflow Heat Mode TargetSmartAirflow units onlyCFMWrite
AV139Ventilation airflow TargetSmartAirflow units onlyCFMWrite
AV140Smoke airflow TargetSmartAirflow units onlyCFMWrite
AV141Outdoor airflow targetRange 0 to 150 CFM per tonCFMWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Prodigy M3 BACnet Module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lennox Prodigy M3 BACnet Module

How many BACnet points does the Lennox Prodigy M3 BACnet Module have?

This list has 83 BACnet objects: 50 analog inputs, 20 analog outputs, 13 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lennox Prodigy M3 BACnet Module BACnet points are writable?

33 of the 83 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lennox Prodigy M3 BACnet Module BACnet documentation?

The source is M3 BACnet Module (Unit Information) (Corp 1404-L4 (450402)), revision 2018-10, published free by Lennox at https://www.lennox.com/dA/0082a46061/1404e.pdf.

What are the minimum BACnet points to integrate the Lennox Prodigy M3 BACnet Module?

Start with AO 104 Occupancy Scheduler Control (0 = occupied, 1-255 = unoccupied; rewrite every 7 min); AO 101 Application Mode Control (Mode or direct demand command); AV 130 Heating Occupied Setpoint (Occupied heating setpoint, 40-95 °F); AV 131 Cooling Occupied Setpoint (Occupied cooling setpoint, 40-95 °F); AV 132 Heating Unoccupied Setpoint (Unoccupied heating setpoint, 40-95 °F); AV 133 Cooling Unoccupied Setpoint (Unoccupied cooling setpoint, 40-95 °F); AI 232 Unit Status (HVAC state code: 0 idle, 1 heat, 3 cool, 6 off, 9 fan); AI 239 Space Temperature (Space temperature in use); AI 253 Current Error (Active alarm code).

How do I enable BMS control of the Lennox Prodigy M3 BACnet Module?

At the M3: SETUP > INSTALL wizard, set Configuration ID 1 position 5 to B to enable the BACnet module. Then SETUP > NETWORK INTEGRATION > BACNET to set the address, baud and CONTROL MODE (Monitor Only, Room Sensor, Network Thermostat, Zone or Remote). In Monitor Only the unit ignores network setpoints and mode demands. No occupancy jumper is needed for Zone/Remote modes.

Does the Lennox Prodigy M3 BACnet Module need a BACnet heartbeat or have a communication timeout?

Network space temperature (AO113) and space RH/CO2 must be rewritten at least every 5 minutes (2-minute interval recommended), or an alarm is raised; some of these alarms only clear with a local reset. AO101 (network thermostat demand), AO109, AV130-133 and AO104 (when not using setpoint control) must be rewritten within 15 minutes (7-minute interval recommended). Without network sensor data for 5 minutes the unit shows Alarm 73. In Room Sensor mode with BACnet setpoints, 15 minutes with no application-level BACnet traffic makes the RTU reset. In Network Thermostat mode, 15 minutes without demands switches it to its backup mode. After losing network data the unit defaults to occupied (Parameter 225 changes this).

Can the BMS supply sensor values to the Lennox Prodigy M3 BACnet Module?

Space temperature goes to AO113 (Space Temperature Input) when CONTROL MODE = ROOM SENSOR with network TEMPERATURE = YES. Space RH and CO2 are written to the proprietary space air object properties 536 and 537. Before network sensor data arrives the unit idles up to 5 minutes (Alarm 110), then enters backup sensor mode (Alarm 93). The points list has no network outdoor-air-temperature input.

How do I check these points on the real Prodigy M3 BACnet Module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lennox BACnet points lists

Source: M3 BACnet Module (Unit Information) · Corp 1404-L4 (450402) · rev. 2018-10. Object names, instances and units are reproduced as published; descriptions are our own.