Free browser tool · nothing is uploaded · 5 November 2026
The Intesis BACnet server for Hitachi VRF gives each indoor unit a block at its MAPS index x 100 and each outdoor unit a block at address x 25 + 1000.
Indoor unit instance = index x 100 + offset, where the index is the unit's number in Intesis MAPS (not always its H-Link address). Outdoor unit instance = address x 25 + 1000 + offset. Indoor index 23's setpoint command is AO 2300; outdoor address 2's outdoor air temperature is AI 1050.
Intesis calculator
The calculator needs JavaScript. The formula and a worked example are below.
Which unit does this instance belong to?
How the numbers are built
indoor = index x 100 + offset; outdoor = address x 25 + 1000 + offset
| Part | Meaning | Range |
|---|---|---|
| index | Indoor unit index in Intesis MAPS | 1-16 or 1-64 |
| address | Outdoor unit address | 0-63 |
| offset | Object offset in the block | 0-11 / 0-6 |
Use the index Intesis MAPS shows for the unit, which is not necessarily its H-Link address. Objects 0-2 command all units at once.
Worked example: indoor index 23, outdoor address 2
The first objects for indoor index 23, outdoor address 2 on the INBACHIT, worked out with the formula above:
| Object | Name (as printed) | What it is |
|---|---|---|
| BI 2300 | OxxUxxOn/Off_S | On/Off (status) |
| BO 2300 | OxxUxxOn/Off_C | On/Off (command) |
| MI 2300 | OxxUxxMode_S | Mode (status) |
| MO 2300 | OxxUxxMode_C | Mode (command) |
| AI 2300 | OxxUxxSetpoint_S | Setpoint (status) |
| AO 2300 | OxxUxxSetpoint_C | Setpoint (command) |
| AI 1050 | OUxx_Outdoor Air Temp. | Outdoor Air temperature |
| AI 1051 | OUXX_Comp.Top Temp. | CompressorTop temperature |
| AI 1052 | OUXX_Total Real Comp. Freq. | Total Real Compressor Freq. |
| AI 1053 | OUXX_Total Comp. Current | Total Compressor Current |
| AI 1054 | OUXX_Out Exp. Valve 1 Open | Out Exp. Valve 1 Open |
| AI 1055 | OUXX_Discharge Pressure | Discharge Pressure |
Source
- Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) BACnet points list (51 objects)
Formula and objects from Intesis BACnet Server - Hitachi VRF User's Manual · rev. 2022/06 r1.2 (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.
Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.
Questions
How do I work out a Intesis instance number?
Indoor unit instance = index x 100 + offset, where the index is the unit's number in Intesis MAPS (not always its H-Link address). Outdoor unit instance = address x 25 + 1000 + offset. Indoor index 23's setpoint command is AO 2300; outdoor address 2's outdoor air temperature is AI 1050.
Why does one instance match both an indoor and an outdoor unit?
The two formulas overlap above 1000 (indoor index 10 starts at 1000, so does outdoor address 0), and the object type does not always tell them apart. The calculator lists every possible match; check the object name on the device.
Is this Intesis calculator official?
No. It applies the formula printed in Intesis's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.
More instance calculators
- Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic P-Link)The Intesis BACnet server for Panasonic VRF numbers every indoor and outdoor unit from its P-Link line and address.
indoor = unit x 100 + (line-1) x 20000 + offset; outdoor = OU x 25 + (line-1) x 1000 + 10000 + offset - Intesis INBACSAM004O000-064O000 (Samsung NASA)The Intesis BACnet server for Samsung NASA gives every indoor unit a block of objects at its MAPS identifier x 100.
instance = identifier x 100 + offset - Fujitsu UTY-VBGX VRF gatewayFujitsu's UTY-VBGX gateway puts the refrigerant system and unit address inside every instance number.
instance = point code x 10000 + refrigerant system x 100 + unit address - Mitsubishi Electric BAC-HD150 BM AdapterThe BAC-HD150 BM Adapter numbers every CITY MULTI group's objects as M-NET number, group number and point number.
instance = M-NET number x 10000 + group x 100 + point - Mitsubishi Electric AE-C400 / EW-C50With the BACnet license, the AE-C400 and EW-C50 number objects by class, address and point.
instance = class x 10000 + address x 100 + point - Mitsubishi Electric PAC-YG31CDA (G-50A)The legacy PAC-YG31CDA BACnet interface serves up to ten G-50A controllers and numbers each group's objects by G-50A number, group and point.
instance = G-50A number x 10000 + group x 100 + point - Mitsubishi Electric Procon BAC-IP/50The Procon BAC-IP/50 gives every unit on its G-50 a block of objects numbered 1, the 3-digit unit address and the point number.
instance = 100000 + unit address x 100 + point - Daikin DMS502B71 VRV BACnet interfaceThe Daikin DMS502B71 BACnet interface gives every VRV indoor unit group the same 35-member object template.
instance = unit number x 256 + member number