Variable frequency drive · BACnet points list

WEG CFW100 (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The CFW100 runs BACnet MS/TP on its RS-485 port and maps drive parameters to fixed objects: AVs for speed, current, voltage, frequency, torque, heatsink temperature, alarm/fault numbers, ramps and the network speed reference; BVs for the status word (P680) and control word (P682); plus digital inputs DI1-DI4. A mailbox (AV 100/101, BV 100/101) reads or writes any parameter by number.

This page lists 45 BACnet objects for the WEG CFW100 (BACnet MS/TP) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WEG’s own free documentation, linked below.

Manufacturer
WEG
Model
CFW100 (BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
45 (15 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
359000 + serial address (P308) when P760 and P761 are 0
Also known as
CFW100, WEG CFW100, CFW100 BACnet, 10007481001
Source document
BACnet CFW100 User's Manual · 10007481001 / 00 · rev. 2020-03
Download CSV 45 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WEG’s current documentation and the live device before use. Not official WEG information. Terms of use.

BMS integration notes: WEG CFW100 (BACnet MS/TP)

Integration in brief

Set P312 = 3 (BACnet MS/TP), the address in P308 and the baud rate in P310, then set P220-P228 so run/stop, direction and reference come from the serial port. Write BV 16 ramp enable (run/stop) with BV 17 general enable and the speed reference to AV 12 (8192 = rated frequency). Read BV 8, AV 3, AV 1 and BV 15, and reset faults with BV 23.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 16Ramp EnableStart/stop from the BMS (1 = run)Command
BV 17General EnableGeneral enable; must be on to runCommand
BV 20RemoteRemote mode when P220 selects serialCommand
AV 12Serial/USB Speed Ref.Speed reference, 8192 = rated frequencyCommand
BV 23Fault ResetReset a tripped driveCommand
BV 8RunningRunning statusRead
AV 3Motor FrequencyOutput frequency in HzRead
AV 1Motor CurrentMotor ampsRead
BV 15FaultAny active drive faultRead
AV 8Present FaultActive fault numberRead

Enable & remote start

The drive only obeys the network when P220-P228 select the serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enable and BV 16 Ramp Enable; BV 20 Remote switches to remote when P220 takes local/remote from the serial control word.

Heartbeat & communication loss

P314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.

Network setup

Watch out for

WEG CFW100 (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

45 of 45 shown
Type
Analog
Access
Show
WEG CFW100 (BACnet MS/TP) BACnet Points List
DescriptionStates
AV0Motor SpeedMotor speed (P002)rpmRead
AVmin1Motor CurrentMotor current (P003)ARead
AV2DC Link Voltage (Ud)DC bus voltage (P004)VRead
AVmin3Motor FrequencyOutput frequency (P005)HzRead
AV4Motor VoltageOutput voltage (P007)VRead
AV5Motor TorqueMotor torque (P009)%Read
AV6Heatsink TemperatureHeatsink temperature (P030)°CRead
AV7Present AlarmActive alarm number (P048)Read
AVmin8Present FaultActive fault number (P049)Read
AV9Acceleration TimeAcceleration ramp time (P100)sCommand
AV10Deceleration TimeDeceleration ramp time (P101)sCommand
AV11Speed in 13 bitsMotor speed in 13-bit scale (P681)Read
AVmin12Serial/USB Speed Ref.Speed reference from the network, 13-bit (P683)Command
AV100Mailbox: param. numberMailbox parameter numberWrite
AV101Mailbox: param. valueMailbox parameter valueWrite
BI0DI1Digital input 1 (P012 bit 0)Read0=Off, 1=On
BI1DI2Digital input 2 (P012 bit 1)Read0=Off, 1=On
BI2DI3Digital input 3 (P012 bit 2)Read0=Off, 1=On
BI3DI4Digital input 4 (P012 bit 3)Read0=Off, 1=On
BV0ReservedReservedRead
BV1Run CommandStatus word: Run Command (P680 bit 1)Read0=Off, 1=On
BV2Fire modeStatus word: Fire mode (P680 bit 2)Read0=Off, 1=On
BV3ReservedReservedRead
BV4ReservedReservedRead
BV52nd RampStatus word: 2nd Ramp (P680 bit 5)Read0=Off, 1=On
BV6Config. ModeStatus word: Config. Mode (P680 bit 6)Read0=Normal, 1=Config
BV7AlarmStatus word: Alarm (P680 bit 7)Read0=No Alarm, 1=Alarm
BVmin8RunningStatus word: Running (P680 bit 8)Read0=Stopped, 1=Running
BV9EnabledStatus word: Enabled (P680 bit 9)Read0=Disabled, 1=Enabled
BV10ForwardStatus word: Forward (P680 bit 10)Read0=Reverse, 1=Forward
BV11JOGStatus word: JOG (P680 bit 11)Read0=Off, 1=On
BV12RemoteStatus word: Remote (P680 bit 12)Read0=Local, 1=Remote
BV13SubvoltageStatus word: Subvoltage (P680 bit 13)Read0=No, 1=Subvoltage
BV14ReservadoReservedRead
BVmin15FaultStatus word: Fault (P680 bit 15)Read0=No Fault, 1=Fault
BVmin16Ramp EnableControl word: Ramp Enable (P682 bit 0)Command0=Stop, 1=Run
BVmin17General EnableControl word: General Enable (P682 bit 1)Command0=Disable, 1=Enable
BV18Run ForwardControl word: Run Forward (P682 bit 2)Command0=Reverse, 1=Forward
BV19JOG EnableControl word: JOG Enable (P682 bit 3)Command0=Off, 1=On
BVmin20RemoteControl word: Remote (P682 bit 4)Command0=Local, 1=Remote
BV212nd RampControl word: 2nd Ramp (P682 bit 5)Command0=Off, 1=On
BV22Quick StopControl word: Quick Stop (P682 bit 6)Command0=Off, 1=On
BVmin23Fault ResetControl word: Fault Reset (P682 bit 7)Command0=Off, 1=Reset
BV100Mailbox: exec. readMailbox read triggerWrite0=Off, 1=On
BV101Mailbox: exec. writeMailbox write triggerWrite0=Off, 1=On
Object ID lookup: WEG CFW100 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CFW100 (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WEG CFW100 (BACnet MS/TP)

How many BACnet points does the WEG CFW100 (BACnet MS/TP) have?

This list has 45 BACnet objects: 15 analog values, 4 binary inputs, 26 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WEG CFW100 (BACnet MS/TP) BACnet points are writable?

15 of the 45 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WEG CFW100 (BACnet MS/TP) BACnet documentation?

The source is BACnet CFW100 User's Manual (10007481001 / 00), revision 2020-03, published free by WEG at https://static.weg.net/medias/downloadcenter/hfc/h9b/WEG-CFW100-bacnet-users-manual-10007481001-en.pdf.

What are the minimum BACnet points to integrate the WEG CFW100 (BACnet MS/TP)?

Start with BV 16 Ramp Enable (Start/stop from the BMS (1 = run)); BV 17 General Enable (General enable; must be on to run); BV 20 Remote (Remote mode when P220 selects serial); AV 12 Serial/USB Speed Ref. (Speed reference, 8192 = rated frequency); BV 23 Fault Reset (Reset a tripped drive); BV 8 Running (Running status); AV 3 Motor Frequency (Output frequency in Hz); AV 1 Motor Current (Motor amps); BV 15 Fault (Any active drive fault); AV 8 Present Fault (Active fault number).

How do I enable BMS control of the WEG CFW100 (BACnet MS/TP)?

The drive only obeys the network when P220-P228 select the serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enable and BV 16 Ramp Enable; BV 20 Remote switches to remote when P220 takes local/remote from the serial control word.

Does the WEG CFW100 (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

P314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.

How do I check these points on the real CFW100 (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WEG BACnet points lists

Source: BACnet CFW100 User's Manual · 10007481001 / 00 · rev. 2020-03. Object names, instances and units are reproduced as published; descriptions are our own.