Variable frequency drive · BACnet points list

WEG CFW-11 (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The CFW-11 runs BACnet MS/TP on its RS-485 port and maps drive parameters to fixed objects: AVs for readings, temperatures, hour and energy counters, ramps, PID values, SoftPLC parameters and the network speed reference; BVs for the status word (P0680) and control word (P0682); plus digital and analog I/O. A mailbox (AV 30/31, BV 33/34) reads or writes any parameter by number.

This page lists 116 BACnet objects for the WEG CFW-11 (BACnet MS/TP) — 35 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WEG’s own free documentation, linked below.

Manufacturer
WEG
Model
CFW-11 (BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
116 (35 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
359000 + serial address (P0308) when P0760 and P0761 are 0
Also known as
CFW-11, CFW11, WEG CFW-11, CFW-11 BACnet, 10000831662
Source document
BACnet CFW-11 User's Manual · 10000831662 / 03 · rev. 2014-02
Download CSV 116 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WEG’s current documentation and the live device before use. Not official WEG information. Terms of use.

BMS integration notes: WEG CFW-11 (BACnet MS/TP)

Integration in brief

Set P0312 = 3 (BACnet MS/TP), the address in P0308 and the baud rate in P0310, then set P0220-P0228 so run/stop, direction and reference come from the serial port. Write BV 16 run/stop with BV 17 general enable and the speed reference to AV 29 (8192 = synchronous speed). Read BV 8, AV 3, AV 1 and BV 15, and reset faults with BV 23.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 16Run/StopStart/stop from the BMSCommand
BV 17General EnablingGeneral enable; must be on to runCommand
BV 20LOC/REMRemote mode when P0220 selects serialCommand
AV 29Serial/USB Speed Ref.Speed reference, 8192 = synchronous speedCommand
BV 23Fault resetReset a tripped driveCommand
BV 8Ramp Enabled (RUN)Running statusRead
AV 3Motor FrequencyOutput frequency in HzRead
AV 1Motor CurrentMotor ampsRead
BV 15Fault conditionAny active drive faultRead
AV 19Present FaultActive fault numberRead

Enable & remote start

The drive only obeys the network when P0220-P0228 select the serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enabling and BV 16 Run/Stop; BV 20 LOC/REM switches to remote when P0220 takes local/remote from the serial control word.

Heartbeat & communication loss

P0314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.

Sensors & values from the BMS

AV 26 Keypad PID Setpoint can be written when the drive's PID is used; there is no separate network PID feedback object.

Network setup

Watch out for

WEG CFW-11 (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

116 of 116 shown
Type
Access
Show
WEG CFW-11 (BACnet MS/TP) BACnet Points List
DescriptionStates
AI0AI1 ValueAnalog input 1 level (P0018)%Read
AI1AI2 ValueAnalog input 2 level (P0019)%Read
AI2AI3 ValueAnalog input 3 level (P0020)%Read
AI3AI4 ValueAnalog input 4 level (P0021)%Read
AO0AO1 ValueAnalog output 1 value (P0696)Command
AO1AO2 ValueAnalog output 2 value (P0697)Command
AO2AO3 ValueAnalog output 3 value (P0698)Command
AO3AO4 ValueAnalog output 4 value (P0699)Command
AV0Motor SpeedMotor speed (P0002)rpmRead
AVmin1Motor CurrentMotor current (P0003)ARead
AV2DC Link Voltage (Ud)DC bus voltage (P0004)VRead
AVmin3Motor FrequencyOutput frequency (P0005)HzRead
AV4Motor VoltageOutput voltage (P0007)VRead
AV5Motor TorqueMotor torque (P0009)%Read
AV6Output PowerOutput power (P0010)kWRead
AV7IGBTs Temperature UPhase U IGBT temperature (P0030)°CRead
AV8IGBTs Temperature VPhase V IGBT temperature (P0031)°CRead
AV9IGBTs Temperature WPhase W IGBT temperature (P0032)°CRead
AV10Rectifier TemperatureRectifier temperature (P0033)°CRead
AV11Internal Air TempInternal air temperature (P0034)°CRead
AV12PID Process VariablePID process variable (P0040)%Read
AV13PID Setpoint ValuePID setpoint in use (P0041)%Read
AV14Time PoweredHours powered (P0042)hRead
AV15Time EnabledHours enabled (P0043)hRead
AV16kWh Output EnergyOutput energy counter (P0044); unit printed as HkWhRead
AV17Fan Enabled TimeFan run hours (P0045)hRead
AV18Present AlarmActive alarm number (P0048)Read
AVmin19Present FaultActive fault number (P0049)Read
AV20Last FaultLast fault number (P0050)Read
AV21Acceleration TimeAcceleration ramp time (P0100)sCommand
AV22Deceleration TimeDeceleration ramp time (P0101)sCommand
AV23PID Proportional GainPID proportional gain (P0520)Command
AV24PID Integral GainPID integral gain (P0521)Command
AV25PID Differential GainPID differential gain (P0522)Command
AV26Keypad PID SetpointPID setpoint from keypad (P0525)%Command
AV27Wake Up BandPID wake-up band (P0535)%Command
AV28Speed in 13 bitsMotor speed in 13-bit scale (P0681)%Read
AVmin29Serial/USB Speed Ref.Speed reference from the network, 13-bit (P0683)Command
AV30MBOX parameterMailbox parameter numberWrite
AV31MBOX dataMailbox parameter valueWrite
AV32SoftPLC Parameter 1SoftPLC user parameter 1 (P1010)Command
AV33SoftPLC Parameter 2SoftPLC user parameter 2 (P1011)Command
AV34SoftPLC Parameter 3SoftPLC user parameter 3 (P1012)Command
AV35SoftPLC Parameter 4SoftPLC user parameter 4 (P1013)Command
AV36SoftPLC Parameter 5SoftPLC user parameter 5 (P1014)Command
AV37SoftPLC Parameter 6SoftPLC user parameter 6 (P1015)Command
BI0DI1 StatusDigital input 1 status (P0012 bit 0)Read0=OFF, 1=ON
BI1DI2 StatusDigital input 2 status (P0012 bit 1)Read0=OFF, 1=ON
BI2DI3 StatusDigital input 3 status (P0012 bit 2)Read0=OFF, 1=ON
BI3DI4 StatusDigital input 4 status (P0012 bit 3)Read0=OFF, 1=ON
BI4DI5 StatusDigital input 5 status (P0012 bit 4)Read0=OFF, 1=ON
BI5DI6 StatusDigital input 6 status (P0012 bit 5)Read0=OFF, 1=ON
BI6DI7 StatusDigital input 7 status (P0012 bit 6)Read0=OFF, 1=ON
BI7DI8 StatusDigital input 8 status (P0012 bit 7)Read0=OFF, 1=ON
BI8ReservedReservedRead
BI9ReservedReservedRead
BI10ReservedReservedRead
BI12ReservedReservedRead
BI13ReservedReservedRead
BI14ReservedReservedRead
BI15ReservedReservedRead
BI16DO1 StatusDigital output 1 status (P0013 bit 0)Read0=OFF, 1=ON
BI17DO2 StatusDigital output 2 status (P0013 bit 1)Read0=OFF, 1=ON
BI18DO3 StatusDigital output 3 status (P0013 bit 2)Read0=OFF, 1=ON
BI19DO4 StatusDigital output 4 status (P0013 bit 3)Read0=OFF, 1=ON
BI20DO5 StatusDigital output 5 status (P0013 bit 4)Read0=OFF, 1=ON
BI21ReservedReservedRead
BI22ReservedReservedRead
BI23ReservedReservedRead
BI24ReservedReservedRead
BI25ReservedReservedRead
BI26ReservedReservedRead
BI28ReservedReservedRead
BI29ReservedReservedRead
BI30ReservedReservedRead
BI31ReservedReservedRead
BI32ReservedReservedRead
BO0DO1 ValueDigital output 1 command (P0695 bit 0)Command0=OFF, 1=ON
BO1DO2 ValueDigital output 2 command (P0695 bit 1)Command0=OFF, 1=ON
BO2DO3 ValueDigital output 3 command (P0695 bit 2)Command0=OFF, 1=ON
BO3DO4 ValueDigital output 4 command (P0695 bit 3)Command0=OFF, 1=ON
BO4DO5 ValueDigital output 5 command (P0695 bit 4)Command0=OFF, 1=ON
BV0ReservedReservedRead
BV1ReservedReservedRead
BV2ReservedReservedRead
BV3ReservedReservedRead
BV4ReservedReservedRead
BV52nd Ramp SelectStatus word: 2nd Ramp Select (P0680 bit 5)Read0=OFF, 1=ON
BV6In configuration modeStatus word: In configuration mode (P0680 bit 6)Read0=OFF, 1=ON
BV7Alarm conditionStatus word: Alarm condition (P0680 bit 7)Read0=OFF, 1=ON
BVmin8Ramp Enabled (RUN)Status word: Ramp Enabled (RUN) (P0680 bit 8)Read0=OFF, 1=ON
BV9General Enabling activeStatus word: General Enabling active (P0680 bit 9)Read0=OFF, 1=ON
BV10Speed DirectionStatus word: Speed Direction (P0680 bit 10)Read0=OFF, 1=ON
BV11JOGStatus word: JOG (P0680 bit 11)Read0=OFF, 1=ON
BV12LOC/REMStatus word: LOC/REM (P0680 bit 12)Read0=OFF, 1=ON
BV13UndervoltageStatus word: Undervoltage (P0680 bit 13)Read0=OFF, 1=ON
BV14Manual/AutomaticStatus word: Manual/Automatic (P0680 bit 14)Read0=OFF, 1=ON
BVmin15Fault conditionStatus word: Fault condition (P0680 bit 15)Read0=OFF, 1=ON
BVmin16Run/StopControl word: Run/Stop (P0682 bit 0)Command0=OFF, 1=ON
BVmin17General EnablingControl word: General Enabling (P0682 bit 1)Command0=OFF, 1=ON
BV18Direction of RotationControl word: Direction of Rotation (P0682 bit 2)Command0=OFF, 1=ON
BV19JOGControl word: JOG (P0682 bit 3)Command0=OFF, 1=ON
BVmin20LOC/REMControl word: LOC/REM (P0682 bit 4)Command0=OFF, 1=ON
BV21Second Ramp UseControl word: Second Ramp Use (P0682 bit 5)Command0=OFF, 1=ON
BV22Quick StopControl word: Quick Stop (P0682 bit 6)Command0=OFF, 1=ON
BVmin23Fault resetControl word: Fault reset (P0682 bit 7)Command0=OFF, 1=ON
BV24ReservedReservedRead
BV25ReservedReservedRead
BV26ReservedReservedRead
BV27ReservedReservedRead
BV28ReservedReservedRead
BV29ReservedReservedRead
BV30ReservedReservedRead
BV31ReservedReservedRead
BV33MBOX readMailbox read triggerWrite0=OFF, 1=ON
BV34MBOX writeMailbox write triggerWrite0=OFF, 1=ON
Object ID lookup: WEG CFW-11 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CFW-11 (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WEG CFW-11 (BACnet MS/TP)

How many BACnet points does the WEG CFW-11 (BACnet MS/TP) have?

This list has 116 BACnet objects: 4 analog inputs, 4 analog outputs, 38 analog values, 31 binary inputs, 5 binary outputs, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WEG CFW-11 (BACnet MS/TP) BACnet points are writable?

35 of the 116 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WEG CFW-11 (BACnet MS/TP) BACnet documentation?

The source is BACnet CFW-11 User's Manual (10000831662 / 03), revision 2014-02, published free by WEG at https://static.weg.net/medias/downloadcenter/hbf/h72/WEG-cfw11-bacnet-manual-10000831662-en.pdf.

What are the minimum BACnet points to integrate the WEG CFW-11 (BACnet MS/TP)?

Start with BV 16 Run/Stop (Start/stop from the BMS); BV 17 General Enabling (General enable; must be on to run); BV 20 LOC/REM (Remote mode when P0220 selects serial); AV 29 Serial/USB Speed Ref. (Speed reference, 8192 = synchronous speed); BV 23 Fault reset (Reset a tripped drive); BV 8 Ramp Enabled (RUN) (Running status); AV 3 Motor Frequency (Output frequency in Hz); AV 1 Motor Current (Motor amps); BV 15 Fault condition (Any active drive fault); AV 19 Present Fault (Active fault number).

How do I enable BMS control of the WEG CFW-11 (BACnet MS/TP)?

The drive only obeys the network when P0220-P0228 select the serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enabling and BV 16 Run/Stop; BV 20 LOC/REM switches to remote when P0220 takes local/remote from the serial control word.

Does the WEG CFW-11 (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

P0314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.

Can the BMS supply sensor values to the WEG CFW-11 (BACnet MS/TP)?

AV 26 Keypad PID Setpoint can be written when the drive's PID is used; there is no separate network PID feedback object.

How do I check these points on the real CFW-11 (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WEG BACnet points lists

Source: BACnet CFW-11 User's Manual · 10000831662 / 03 · rev. 2014-02. Object names, instances and units are reproduced as published; descriptions are our own.