Variable frequency drive · BACnet points list
WEG CFW-11 (BACnet MS/TP) BACnet points list
Updated 4 November 2026
The CFW-11 runs BACnet MS/TP on its RS-485 port and maps drive parameters to fixed objects: AVs for readings, temperatures, hour and energy counters, ramps, PID values, SoftPLC parameters and the network speed reference; BVs for the status word (P0680) and control word (P0682); plus digital and analog I/O. A mailbox (AV 30/31, BV 33/34) reads or writes any parameter by number.
This page lists 116 BACnet objects for the WEG CFW-11 (BACnet MS/TP) — 35 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WEG’s own free documentation, linked below.
- Manufacturer
- WEG
- Model
- CFW-11 (BACnet MS/TP)
- Equipment
- Variable frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 116 (35 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 359000 + serial address (P0308) when P0760 and P0761 are 0
- Also known as
- CFW-11, CFW11, WEG CFW-11, CFW-11 BACnet, 10000831662
Reference only, provided as-is: verify against WEG’s current documentation and the live device before use. Not official WEG information. Terms of use.
BMS integration notes: WEG CFW-11 (BACnet MS/TP)
Set P0312 = 3 (BACnet MS/TP), the address in P0308 and the baud rate in P0310, then set P0220-P0228 so run/stop, direction and reference come from the serial port. Write BV 16 run/stop with BV 17 general enable and the speed reference to AV 29 (8192 = synchronous speed). Read BV 8, AV 3, AV 1 and BV 15, and reset faults with BV 23.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 16 | Run/Stop | Start/stop from the BMS | Command |
| BV 17 | General Enabling | General enable; must be on to run | Command |
| BV 20 | LOC/REM | Remote mode when P0220 selects serial | Command |
| AV 29 | Serial/USB Speed Ref. | Speed reference, 8192 = synchronous speed | Command |
| BV 23 | Fault reset | Reset a tripped drive | Command |
| BV 8 | Ramp Enabled (RUN) | Running status | Read |
| AV 3 | Motor Frequency | Output frequency in Hz | Read |
| AV 1 | Motor Current | Motor amps | Read |
| BV 15 | Fault condition | Any active drive fault | Read |
| AV 19 | Present Fault | Active fault number | Read |
Enable & remote start
The drive only obeys the network when P0220-P0228 select the serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enabling and BV 16 Run/Stop; BV 20 LOC/REM switches to remote when P0220 takes local/remote from the serial control word.
Heartbeat & communication loss
P0314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.
Sensors & values from the BMS
AV 26 Keypad PID Setpoint can be written when the drive's PID is used; there is no separate network PID feedback object.
Network setup
- P0312 = 3 (BACnet MS/TP); P0308 MS/TP address 0-254 (factory 1).
- P0310 baud 9600, 19200 (factory), 38400 or 57600; P0311 must be 0 (8 bits, no parity, 1 stop).
- Device instance: P0760 x 10000 + P0761; with both at 0 the drive uses 359000 + P0308 (WEG vendor ID 359).
- P0762 max master (factory 127), P0763 max info frames, P0764 I-Am at power-up (factory) or continuously.
Watch out for
- Speed reference AV 29 is a 13-bit value, not Hz or %: 8192 = motor synchronous speed; negative values reverse.
- Ramp times, PID gains and the mailbox write change drive parameters; don't write them cyclically.
- P0313 = 0 keeps the drive running at the last command after a comm loss.
- P0311 is printed with default 1 (even parity), although its note calls option 0 the default; BACnet needs 0.
WEG CFW-11 (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | AI1 Value | Analog input 1 level (P0018) | % | Read | |
| AI | 1 | AI2 Value | Analog input 2 level (P0019) | % | Read | |
| AI | 2 | AI3 Value | Analog input 3 level (P0020) | % | Read | |
| AI | 3 | AI4 Value | Analog input 4 level (P0021) | % | Read | |
| AO | 0 | AO1 Value | Analog output 1 value (P0696) | Command | ||
| AO | 1 | AO2 Value | Analog output 2 value (P0697) | Command | ||
| AO | 2 | AO3 Value | Analog output 3 value (P0698) | Command | ||
| AO | 3 | AO4 Value | Analog output 4 value (P0699) | Command | ||
| AV | 0 | Motor Speed | Motor speed (P0002) | rpm | Read | |
| AVmin | 1 | Motor Current | Motor current (P0003) | A | Read | |
| AV | 2 | DC Link Voltage (Ud) | DC bus voltage (P0004) | V | Read | |
| AVmin | 3 | Motor Frequency | Output frequency (P0005) | Hz | Read | |
| AV | 4 | Motor Voltage | Output voltage (P0007) | V | Read | |
| AV | 5 | Motor Torque | Motor torque (P0009) | % | Read | |
| AV | 6 | Output Power | Output power (P0010) | kW | Read | |
| AV | 7 | IGBTs Temperature U | Phase U IGBT temperature (P0030) | °C | Read | |
| AV | 8 | IGBTs Temperature V | Phase V IGBT temperature (P0031) | °C | Read | |
| AV | 9 | IGBTs Temperature W | Phase W IGBT temperature (P0032) | °C | Read | |
| AV | 10 | Rectifier Temperature | Rectifier temperature (P0033) | °C | Read | |
| AV | 11 | Internal Air Temp | Internal air temperature (P0034) | °C | Read | |
| AV | 12 | PID Process Variable | PID process variable (P0040) | % | Read | |
| AV | 13 | PID Setpoint Value | PID setpoint in use (P0041) | % | Read | |
| AV | 14 | Time Powered | Hours powered (P0042) | h | Read | |
| AV | 15 | Time Enabled | Hours enabled (P0043) | h | Read | |
| AV | 16 | kWh Output Energy | Output energy counter (P0044); unit printed as H | kWh | Read | |
| AV | 17 | Fan Enabled Time | Fan run hours (P0045) | h | Read | |
| AV | 18 | Present Alarm | Active alarm number (P0048) | Read | ||
| AVmin | 19 | Present Fault | Active fault number (P0049) | Read | ||
| AV | 20 | Last Fault | Last fault number (P0050) | Read | ||
| AV | 21 | Acceleration Time | Acceleration ramp time (P0100) | s | Command | |
| AV | 22 | Deceleration Time | Deceleration ramp time (P0101) | s | Command | |
| AV | 23 | PID Proportional Gain | PID proportional gain (P0520) | Command | ||
| AV | 24 | PID Integral Gain | PID integral gain (P0521) | Command | ||
| AV | 25 | PID Differential Gain | PID differential gain (P0522) | Command | ||
| AV | 26 | Keypad PID Setpoint | PID setpoint from keypad (P0525) | % | Command | |
| AV | 27 | Wake Up Band | PID wake-up band (P0535) | % | Command | |
| AV | 28 | Speed in 13 bits | Motor speed in 13-bit scale (P0681) | % | Read | |
| AVmin | 29 | Serial/USB Speed Ref. | Speed reference from the network, 13-bit (P0683) | Command | ||
| AV | 30 | MBOX parameter | Mailbox parameter number | Write | ||
| AV | 31 | MBOX data | Mailbox parameter value | Write | ||
| AV | 32 | SoftPLC Parameter 1 | SoftPLC user parameter 1 (P1010) | Command | ||
| AV | 33 | SoftPLC Parameter 2 | SoftPLC user parameter 2 (P1011) | Command | ||
| AV | 34 | SoftPLC Parameter 3 | SoftPLC user parameter 3 (P1012) | Command | ||
| AV | 35 | SoftPLC Parameter 4 | SoftPLC user parameter 4 (P1013) | Command | ||
| AV | 36 | SoftPLC Parameter 5 | SoftPLC user parameter 5 (P1014) | Command | ||
| AV | 37 | SoftPLC Parameter 6 | SoftPLC user parameter 6 (P1015) | Command | ||
| BI | 0 | DI1 Status | Digital input 1 status (P0012 bit 0) | Read | 0=OFF, 1=ON | |
| BI | 1 | DI2 Status | Digital input 2 status (P0012 bit 1) | Read | 0=OFF, 1=ON | |
| BI | 2 | DI3 Status | Digital input 3 status (P0012 bit 2) | Read | 0=OFF, 1=ON | |
| BI | 3 | DI4 Status | Digital input 4 status (P0012 bit 3) | Read | 0=OFF, 1=ON | |
| BI | 4 | DI5 Status | Digital input 5 status (P0012 bit 4) | Read | 0=OFF, 1=ON | |
| BI | 5 | DI6 Status | Digital input 6 status (P0012 bit 5) | Read | 0=OFF, 1=ON | |
| BI | 6 | DI7 Status | Digital input 7 status (P0012 bit 6) | Read | 0=OFF, 1=ON | |
| BI | 7 | DI8 Status | Digital input 8 status (P0012 bit 7) | Read | 0=OFF, 1=ON | |
| BI | 8 | Reserved | Reserved | Read | ||
| BI | 9 | Reserved | Reserved | Read | ||
| BI | 10 | Reserved | Reserved | Read | ||
| BI | 12 | Reserved | Reserved | Read | ||
| BI | 13 | Reserved | Reserved | Read | ||
| BI | 14 | Reserved | Reserved | Read | ||
| BI | 15 | Reserved | Reserved | Read | ||
| BI | 16 | DO1 Status | Digital output 1 status (P0013 bit 0) | Read | 0=OFF, 1=ON | |
| BI | 17 | DO2 Status | Digital output 2 status (P0013 bit 1) | Read | 0=OFF, 1=ON | |
| BI | 18 | DO3 Status | Digital output 3 status (P0013 bit 2) | Read | 0=OFF, 1=ON | |
| BI | 19 | DO4 Status | Digital output 4 status (P0013 bit 3) | Read | 0=OFF, 1=ON | |
| BI | 20 | DO5 Status | Digital output 5 status (P0013 bit 4) | Read | 0=OFF, 1=ON | |
| BI | 21 | Reserved | Reserved | Read | ||
| BI | 22 | Reserved | Reserved | Read | ||
| BI | 23 | Reserved | Reserved | Read | ||
| BI | 24 | Reserved | Reserved | Read | ||
| BI | 25 | Reserved | Reserved | Read | ||
| BI | 26 | Reserved | Reserved | Read | ||
| BI | 28 | Reserved | Reserved | Read | ||
| BI | 29 | Reserved | Reserved | Read | ||
| BI | 30 | Reserved | Reserved | Read | ||
| BI | 31 | Reserved | Reserved | Read | ||
| BI | 32 | Reserved | Reserved | Read | ||
| BO | 0 | DO1 Value | Digital output 1 command (P0695 bit 0) | Command | 0=OFF, 1=ON | |
| BO | 1 | DO2 Value | Digital output 2 command (P0695 bit 1) | Command | 0=OFF, 1=ON | |
| BO | 2 | DO3 Value | Digital output 3 command (P0695 bit 2) | Command | 0=OFF, 1=ON | |
| BO | 3 | DO4 Value | Digital output 4 command (P0695 bit 3) | Command | 0=OFF, 1=ON | |
| BO | 4 | DO5 Value | Digital output 5 command (P0695 bit 4) | Command | 0=OFF, 1=ON | |
| BV | 0 | Reserved | Reserved | Read | ||
| BV | 1 | Reserved | Reserved | Read | ||
| BV | 2 | Reserved | Reserved | Read | ||
| BV | 3 | Reserved | Reserved | Read | ||
| BV | 4 | Reserved | Reserved | Read | ||
| BV | 5 | 2nd Ramp Select | Status word: 2nd Ramp Select (P0680 bit 5) | Read | 0=OFF, 1=ON | |
| BV | 6 | In configuration mode | Status word: In configuration mode (P0680 bit 6) | Read | 0=OFF, 1=ON | |
| BV | 7 | Alarm condition | Status word: Alarm condition (P0680 bit 7) | Read | 0=OFF, 1=ON | |
| BVmin | 8 | Ramp Enabled (RUN) | Status word: Ramp Enabled (RUN) (P0680 bit 8) | Read | 0=OFF, 1=ON | |
| BV | 9 | General Enabling active | Status word: General Enabling active (P0680 bit 9) | Read | 0=OFF, 1=ON | |
| BV | 10 | Speed Direction | Status word: Speed Direction (P0680 bit 10) | Read | 0=OFF, 1=ON | |
| BV | 11 | JOG | Status word: JOG (P0680 bit 11) | Read | 0=OFF, 1=ON | |
| BV | 12 | LOC/REM | Status word: LOC/REM (P0680 bit 12) | Read | 0=OFF, 1=ON | |
| BV | 13 | Undervoltage | Status word: Undervoltage (P0680 bit 13) | Read | 0=OFF, 1=ON | |
| BV | 14 | Manual/Automatic | Status word: Manual/Automatic (P0680 bit 14) | Read | 0=OFF, 1=ON | |
| BVmin | 15 | Fault condition | Status word: Fault condition (P0680 bit 15) | Read | 0=OFF, 1=ON | |
| BVmin | 16 | Run/Stop | Control word: Run/Stop (P0682 bit 0) | Command | 0=OFF, 1=ON | |
| BVmin | 17 | General Enabling | Control word: General Enabling (P0682 bit 1) | Command | 0=OFF, 1=ON | |
| BV | 18 | Direction of Rotation | Control word: Direction of Rotation (P0682 bit 2) | Command | 0=OFF, 1=ON | |
| BV | 19 | JOG | Control word: JOG (P0682 bit 3) | Command | 0=OFF, 1=ON | |
| BVmin | 20 | LOC/REM | Control word: LOC/REM (P0682 bit 4) | Command | 0=OFF, 1=ON | |
| BV | 21 | Second Ramp Use | Control word: Second Ramp Use (P0682 bit 5) | Command | 0=OFF, 1=ON | |
| BV | 22 | Quick Stop | Control word: Quick Stop (P0682 bit 6) | Command | 0=OFF, 1=ON | |
| BVmin | 23 | Fault reset | Control word: Fault reset (P0682 bit 7) | Command | 0=OFF, 1=ON | |
| BV | 24 | Reserved | Reserved | Read | ||
| BV | 25 | Reserved | Reserved | Read | ||
| BV | 26 | Reserved | Reserved | Read | ||
| BV | 27 | Reserved | Reserved | Read | ||
| BV | 28 | Reserved | Reserved | Read | ||
| BV | 29 | Reserved | Reserved | Read | ||
| BV | 30 | Reserved | Reserved | Read | ||
| BV | 31 | Reserved | Reserved | Read | ||
| BV | 33 | MBOX read | Mailbox read trigger | Write | 0=OFF, 1=ON | |
| BV | 34 | MBOX write | Mailbox write trigger | Write | 0=OFF, 1=ON |
No points match these filters.
Object ID lookup: WEG CFW-11 point IDs by name
AI0AI1 ValueAI1AI2 ValueAI2AI3 ValueAI3AI4 ValueAO0AO1 ValueAO1AO2 ValueAO2AO3 ValueAO3AO4 ValueAV0Motor SpeedAV1Motor CurrentAV2DC Link Voltage (Ud)AV3Motor FrequencyAV4Motor VoltageAV5Motor TorqueAV6Output PowerAV7IGBTs Temperature UAV8IGBTs Temperature VAV9IGBTs Temperature WAV10Rectifier TemperatureAV11Internal Air TempAV12PID Process VariableAV13PID Setpoint ValueAV14Time PoweredAV15Time EnabledAV16kWh Output EnergyAV17Fan Enabled TimeAV18Present AlarmAV19Present FaultAV20Last FaultAV21Acceleration TimeAV22Deceleration TimeAV23PID Proportional GainAV24PID Integral GainAV25PID Differential GainAV26Keypad PID SetpointAV27Wake Up BandAV28Speed in 13 bitsAV29Serial/USB Speed Ref.AV30MBOX parameterAV31MBOX dataAV32SoftPLC Parameter 1AV33SoftPLC Parameter 2AV34SoftPLC Parameter 3AV35SoftPLC Parameter 4AV36SoftPLC Parameter 5AV37SoftPLC Parameter 6BI0DI1 StatusBI1DI2 StatusBI2DI3 StatusBI3DI4 StatusBI4DI5 StatusBI5DI6 StatusBI6DI7 StatusBI7DI8 StatusBI8ReservedBI9ReservedBI10ReservedBI12ReservedBI13ReservedBI14ReservedBI15ReservedBI16DO1 StatusBI17DO2 StatusBI18DO3 StatusBI19DO4 StatusBI20DO5 StatusBI21ReservedBI22ReservedBI23ReservedBI24ReservedBI25ReservedBI26ReservedBI28ReservedBI29ReservedBI30ReservedBI31ReservedBI32ReservedBO0DO1 ValueBO1DO2 ValueBO2DO3 ValueBO3DO4 ValueBO4DO5 ValueBV0ReservedBV1ReservedBV2ReservedBV3ReservedBV4ReservedBV52nd Ramp SelectBV6In configuration modeBV7Alarm conditionBV8Ramp Enabled (RUN)BV9General Enabling activeBV10Speed DirectionBV11JOGBV12LOC/REMBV13UndervoltageBV14Manual/AutomaticBV15Fault conditionBV16Run/StopBV17General EnablingBV18Direction of RotationBV19JOGBV20LOC/REMBV21Second Ramp UseBV22Quick StopBV23Fault resetBV24ReservedBV25ReservedBV26ReservedBV27ReservedBV28ReservedBV29ReservedBV30ReservedBV31ReservedBV33MBOX readBV34MBOX write
Integration notes
- The manual calls the object types ANI, ANO, ANV, BIN and BOUT; they are standard AI, AO, AV, BI and BO objects.
- Reserved objects are listed as printed; BI 11 and BI 27 are not in the binary input tables.
- AV 16 kWh Output Energy is printed with unit 'H'; it is an energy counter.
- Mailbox: write the parameter number to AV 30, then 1 to BV 33 to read it into AV 31, or set AV 31 and write 1 to BV 34.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CFW-11 (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WEG CFW-11 (BACnet MS/TP)
How many BACnet points does the WEG CFW-11 (BACnet MS/TP) have?
This list has 116 BACnet objects: 4 analog inputs, 4 analog outputs, 38 analog values, 31 binary inputs, 5 binary outputs, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WEG CFW-11 (BACnet MS/TP) BACnet points are writable?
35 of the 116 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WEG CFW-11 (BACnet MS/TP) BACnet documentation?
The source is BACnet CFW-11 User's Manual (10000831662 / 03), revision 2014-02, published free by WEG at https://static.weg.net/medias/downloadcenter/hbf/h72/WEG-cfw11-bacnet-manual-10000831662-en.pdf.
What are the minimum BACnet points to integrate the WEG CFW-11 (BACnet MS/TP)?
Start with BV 16 Run/Stop (Start/stop from the BMS); BV 17 General Enabling (General enable; must be on to run); BV 20 LOC/REM (Remote mode when P0220 selects serial); AV 29 Serial/USB Speed Ref. (Speed reference, 8192 = synchronous speed); BV 23 Fault reset (Reset a tripped drive); BV 8 Ramp Enabled (RUN) (Running status); AV 3 Motor Frequency (Output frequency in Hz); AV 1 Motor Current (Motor amps); BV 15 Fault condition (Any active drive fault); AV 19 Present Fault (Active fault number).
How do I enable BMS control of the WEG CFW-11 (BACnet MS/TP)?
The drive only obeys the network when P0220-P0228 select the serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enabling and BV 16 Run/Stop; BV 20 LOC/REM switches to remote when P0220 takes local/remote from the serial control word.
Does the WEG CFW-11 (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
P0314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.
Can the BMS supply sensor values to the WEG CFW-11 (BACnet MS/TP)?
AV 26 Keypad PID Setpoint can be written when the drive's PID is used; there is no separate network PID feedback object.
How do I check these points on the real CFW-11 (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WEG BACnet points lists
- Variable frequency drive
WEG CFW100 (BACnet MS/TP)
WEG CFW100 mini frequency inverters using BACnet MS/TP on the RS-485 port (plug-in communication module).
Also known as: CFW100, WEG CFW100, CFW100 BACnet, 10007481001 - Variable frequency drive
WEG CFW300 (BACnet MS/TP)
WEG CFW300 micro frequency inverters using BACnet MS/TP on the RS-485 port (plug-in communication module).
Also known as: CFW300, WEG CFW300, CFW300 BACnet, 10006901889, CFW320 - Variable frequency drive
WEG CFW503 (BACnet MS/TP)
WEG CFW503 frequency inverters using BACnet MS/TP on the standard or plug-in RS-485 port.
Also known as: CFW503, WEG CFW503, CFW503 BACnet, 10012735607, CFW500 - Variable frequency drive (HVAC)
WEG CFW701 HVAC drive (BACnet MS/TP)
WEG CFW701 HVAC-R frequency inverters using BACnet MS/TP on the RS-485 port.
Also known as: CFW701, WEG CFW701, CFW701 HVAC-R, CFW701 BACnet, 10001538519
Source: BACnet CFW-11 User's Manual · 10000831662 / 03 · rev. 2014-02. Object names, instances and units are reproduced as published; descriptions are our own.