Variable frequency drive (HVAC) · BACnet points list

WEG CFW701 HVAC drive (BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The CFW701 is WEG's HVAC-R drive with BACnet MS/TP on its RS-485 port. Drive parameters map to fixed objects: AVs for readings, ramps, three PID loops and the network speed reference, BVs for the status word (P0680) and control word (P0682), plus digital and analog I/O. A mailbox (AV 100/101, BV 100/101) reads or writes any parameter by number.

This page lists 94 BACnet objects for the WEG CFW701 HVAC drive (BACnet MS/TP) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WEG’s own free documentation, linked below.

Manufacturer
WEG
Model
CFW701 HVAC drive (BACnet MS/TP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
94 (34 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
359000 + serial address (P0308) when P0760 and P0761 are 0
Also known as
CFW701, WEG CFW701, CFW701 HVAC-R, CFW701 BACnet, 10001538519
Source document
CFW701 Manual del Usuario BACnet · 10001538519 / 01 · rev. 2016-09
Download CSV 94 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WEG CFW701 HVAC drive (BACnet MS/TP)

Integration in brief

Set P0312 = 3 (BACnet MS/TP), the address in P0308 and the baud rate in P0310, then set P0220-P0228 so run/stop, direction and reference come from the serial port. Write BV 16 start/stop with BV 17 general enable and the speed reference to AV 17 (8192 = synchronous speed). Read BV 8, AV 3, AV 1 and BV 15, and reset faults with BV 23.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 16Start/StopStart/stop from the BMSCommand
BV 17General EnablingGeneral enable; must be on to runCommand
BV 20LOC/REMRemote mode when P0220 selects serialCommand
AV 17Serial/USB Speed Ref.Speed reference, 8192 = synchronous speedCommand
BV 23Fault resetReset a tripped driveCommand
BV 8Ramp Enabled (RUN)Running statusRead
AV 3Motor FrequencyOutput frequency in HzRead
AV 1Motor CurrentMotor ampsRead
BV 15Fault conditionAny active drive faultRead
AV 13Present FaultActive fault numberRead

Enable & remote start

The drive only obeys the network when P0220-P0228 select a serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enabling and BV 16 Start/Stop; BV 20 LOC/REM switches to remote when P0220 takes local/remote from the serial control word.

Heartbeat & communication loss

P0314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.

Sensors & values from the BMS

The BMS can write the main PID automatic setpoint (AV 21) and the external PID 1 and 2 setpoints (AV 25, AV 29) when the drive's PID loops are used; their units follow the drive's PID setup.

Network setup

Watch out for

WEG CFW701 HVAC drive (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

94 of 94 shown
Type
Access
Show
WEG CFW701 HVAC drive (BACnet MS/TP) BACnet Points List
DescriptionStates
AI0AI1 ValueAnalog input 1 level (P0018)%Read
AI1AI2 ValueAnalog input 2 level (P0019)%Read
AI2AI3 ValueAnalog input 3 level (P0020)%Read
AO0AO1 ValueNetwork value for an analog output (P0696)Command
AO1AO2 ValueNetwork value for an analog output (P0697)Command
AV0Motor SpeedMotor speed (P0002)rpmRead
AVmin1Motor CurrentMotor current (P0003)ARead
AV2DC Link Voltage (Ud)DC bus voltage (P0004)VRead
AVmin3Motor FrequencyOutput frequency (P0005)HzRead
AV4Motor VoltageOutput voltage (P0007)VRead
AV5Motor TorqueMotor torque (P0009)%Read
AV6Output PowerOutput power (P0010)kWRead
AV7IGBTs Temperature UIGBT temperature, phase U (P0030)°CRead
AV8Internal Air TempInternal air temperature (P0034)°CRead
AV9Time PoweredPowered hours (P0042)hRead
AV10Time EnabledEnabled hours (P0043)hRead
AV11kWh Output EnergyEnergy counter (P0044); unit printed as HkWhRead
AV12Present AlarmActive alarm number (P0048)Read
AVmin13Present FaultActive fault number (P0049)Read
AV14Acceleration TimeAcceleration ramp time (P0100)sCommand
AV15Deceleration TimeDeceleration ramp time (P0101)sCommand
AV16Speed in 13 bitsMotor speed, 13-bit scale (P0681)%Read
AVmin17Serial/USB Speed Ref.Speed reference, 13-bit scale (P0683)Command
AV18SoftPLC Parameter 1012SoftPLC user parameterCommand
AV19SoftPLC Parameter 1013SoftPLC user parameterCommand
AV20SoftPLC Parameter 1025SoftPLC user parameterCommand
AV21Automatic Setpoint main PIDMain PID automatic setpoint (P1011); user unitCommand
AV22Manual Setpoint main PIDMain PID manual setpoint (P1014)%Command
AV23Feedback main PIDMain PID feedback (P1015); user unitRead
AV24Main PID outputMain PID output (P1016)%Read
AV25Automatic Setpoint external PID 1External PID 1 automatic setpoint (P1060); user unitCommand
AV26Manual Setpoint external PID 1External PID 1 manual setpoint (P1061)%Command
AV27Feedback external PID 1External PID 1 feedback (P1062); user unitRead
AV28External PID 1 outputExternal PID 1 output (P1063)%Read
AV29Automatic Setpoint external PID 2External PID 2 automatic setpoint (P1080); user unitCommand
AV30Manual Setpoint external PID 2External PID 2 manual setpoint (P1081)%Command
AV31Feedback external PID 2External PID 2 feedback (P1082); user unitRead
AV32External PID 2 outputExternal PID 2 output (P1083)%Read
AV100MBOX parameterParameter number for mailbox accessWrite
AV101MBOX dataValue read from or to write to the parameterWrite
BI0DI1 StatusDigital input 1 (P0012 bit 0)Read0=OFF, 1=ON
BI1DI2 StatusDigital input 2 (P0012 bit 1)Read0=OFF, 1=ON
BI2DI3 StatusDigital input 3 (P0012 bit 2)Read0=OFF, 1=ON
BI3DI4 StatusDigital input 4 (P0012 bit 3)Read0=OFF, 1=ON
BI4DI5 StatusDigital input 5 (P0012 bit 4)Read0=OFF, 1=ON
BI5DI6 StatusDigital input 6 (P0012 bit 5)Read0=OFF, 1=ON
BI6DI7 StatusDigital input 7 (P0012 bit 6)Read0=OFF, 1=ON
BI7DI8 StatusDigital input 8 (P0012 bit 7)Read0=OFF, 1=ON
BI8ReservadoReservedRead
BI9ReservadoReservedRead
BI10ReservadoReservedRead
BI12ReservadoReservedRead
BI13ReservadoReservedRead
BI14ReservadoReservedRead
BI15ReservadoReservedRead
BO0DO1 ValueDigital output 1 (P0695 bit 0)Command0=OFF, 1=ON
BO1DO2 ValueDigital output 2 (P0695 bit 1)Command0=OFF, 1=ON
BO2DO3 ValueDigital output 3 (P0695 bit 2)Command0=OFF, 1=ON
BO3DO4 ValueDigital output 4 (P0695 bit 3)Command0=OFF, 1=ON
BO4DO5 ValueDigital output 5 (P0695 bit 4)Command0=OFF, 1=ON
BV0ReservadoReservedRead
BV1ReservadoReservedRead
BV2Fire ModeStatus: fire modeRead0=OFF, 1=ON
BV3BypassStatus: bypassRead0=OFF, 1=ON
BV4Active Quick StopStatus: quick stop activeRead0=OFF, 1=ON
BV52nd Ramp SelectStatus: second rampRead0=OFF, 1=ON
BV6In configuration modeStatus: configuration modeRead0=OFF, 1=ON
BV7Alarm conditionStatus: alarm activeRead0=OFF, 1=ON
BVmin8Ramp Enabled (RUN)Status: ramp enabled (running)Read0=OFF, 1=ON
BV9General Enabling activeStatus: general enableRead0=OFF, 1=ON
BV10Speed DirectionStatus: directionRead0=OFF, 1=ON
BV11JOGStatus: JOGRead0=OFF, 1=ON
BV12LOC/REMStatus: local/remoteRead0=OFF, 1=ON
BV13UndervoltageStatus: undervoltageRead0=OFF, 1=ON
BV14ReservadoReservedRead
BVmin15Fault conditionStatus: fault activeRead0=OFF, 1=ON
BVmin16Start/StopCommand: start/stopCommand0=OFF, 1=ON
BVmin17General EnablingCommand: general enableCommand0=OFF, 1=ON
BV18Direction of RotationCommand: directionCommand0=OFF, 1=ON
BV19JOGCommand: JOGCommand0=OFF, 1=ON
BVmin20LOC/REMCommand: local/remote selectCommand0=OFF, 1=ON
BV21Second Ramp UseCommand: second rampCommand0=OFF, 1=ON
BV22Quick StopCommand: quick stopCommand0=OFF, 1=ON
BVmin23Fault resetCommand: fault resetCommand0=OFF, 1=ON
BV24ReservadoReservedRead
BV25ReservadoReservedRead
BV26ReservadoReservedRead
BV27ReservadoReservedRead
BV28ReservadoReservedRead
BV29Manual/Auto Internal PIDCommand: internal PID manual/autoCommand0=OFF, 1=ON
BV30Manual/Auto external PID 1Command: external PID 1 manual/autoCommand0=OFF, 1=ON
BV31Manual/Auto external PID 2Command: external PID 2 manual/autoCommand0=OFF, 1=ON
BV100MBOX readMailbox read triggerWrite0=OFF, 1=ON
BV101MBOX writeMailbox write triggerWrite0=OFF, 1=ON

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CFW701 HVAC drive (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WEG CFW701 HVAC drive (BACnet MS/TP)

How many BACnet points does the WEG CFW701 HVAC drive (BACnet MS/TP) have?

This list has 94 BACnet objects: 3 analog inputs, 2 analog outputs, 35 analog values, 15 binary inputs, 5 binary outputs, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WEG CFW701 HVAC drive (BACnet MS/TP) BACnet points are writable?

34 of the 94 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WEG CFW701 HVAC drive (BACnet MS/TP) BACnet documentation?

The source is CFW701 Manual del Usuario BACnet (10001538519 / 01), revision 2016-09, published free by WEG at https://static.weg.net/medias/downloadcenter/h65/h01/WEG-cfw701-manual-bacnet-10001538519-es.pdf.

What are the minimum BACnet points to integrate the WEG CFW701 HVAC drive (BACnet MS/TP)?

Start with BV 16 Start/Stop (Start/stop from the BMS); BV 17 General Enabling (General enable; must be on to run); BV 20 LOC/REM (Remote mode when P0220 selects serial); AV 17 Serial/USB Speed Ref. (Speed reference, 8192 = synchronous speed); BV 23 Fault reset (Reset a tripped drive); BV 8 Ramp Enabled (RUN) (Running status); AV 3 Motor Frequency (Output frequency in Hz); AV 1 Motor Current (Motor amps); BV 15 Fault condition (Any active drive fault); AV 13 Present Fault (Active fault number).

How do I enable BMS control of the WEG CFW701 HVAC drive (BACnet MS/TP)?

The drive only obeys the network when P0220-P0228 select a serial option for local/remote, reference, direction and run/stop. It needs both BV 17 General Enabling and BV 16 Start/Stop; BV 20 LOC/REM switches to remote when P0220 takes local/remote from the serial control word.

Does the WEG CFW701 HVAC drive (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

P0314 Serial Watchdog (0.0-999.0 s, 0 = off, factory 0.0): if no valid telegram arrives within that time the drive shows alarm A128 (or fault F228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.

Can the BMS supply sensor values to the WEG CFW701 HVAC drive (BACnet MS/TP)?

The BMS can write the main PID automatic setpoint (AV 21) and the external PID 1 and 2 setpoints (AV 25, AV 29) when the drive's PID loops are used; their units follow the drive's PID setup.

How do I check these points on the real CFW701 HVAC drive (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WEG BACnet points lists

Source: CFW701 Manual del Usuario BACnet · 10001538519 / 01 · rev. 2016-09. Object names, instances and units are reproduced as published; descriptions are our own.