Room pressure monitor (room condition monitor) · BACnet points list
Setra SRCM Room Condition Monitor (two-room) BACnet points list
Updated 12 November 2026Unofficial source
The SRCM monitors pressure, temperature, humidity and a user-defined value for a primary and a secondary room, with alarm limits per isolation mode. Its BACnet object list gives the eight readings as analog inputs, alarm limits per isolation mode and input ranges as analog values, display and alarm options as binary values, and input sources, isolation modes and banner modes as multistate values. This is a larger, two-room object list than the single-room Siemens RPM map already in the library.
This page lists 100 BACnet objects for the Setra SRCM Room Condition Monitor (two-room) — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Setra’s documentation hosted by Kele, not by Setra itself, so treat it as unofficial.
- Manufacturer
- Setra
- Model
- SRCM Room Condition Monitor (two-room)
- Equipment
- Room pressure monitor (room condition monitor)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 100 (48 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- SRCM, Setra SRCM, Room Condition Monitor, Setra Room Condition Monitor
- Source document
- SRCM BACnet Object List (unofficial copy, hosted by Kele)
Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.
BMS integration notes: Setra SRCM Room Condition Monitor (two-room)
Read the room pressures (AI 1 / AI 2) and the alarm summary (MV 8 / MI 1) for monitoring. Set the isolation mode of each room (MV 2 / MV 13) and the alarm limits for that mode from the BMS only if the monitor is not configured locally. Temperature, humidity and user values can be written from BACnet when their input source is set to BACnet.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 2 | Primary Room Pressure Mode | Primary isolation mode: 1 pos, 2 neg, 3 neutral | Write |
| MV 29 | Room Occupancy Status | Occupancy: 1 = Active, 2 = Standby | Write |
| AI 1 | Primary Pressure | Primary room differential pressure | Read |
| AI 2 | Secondary Pressure | Secondary room differential pressure | Read |
| AI 3 | Primary Temperature | Primary room temperature | Read |
| AI 5 | Primary Humidity | Primary room humidity | Read |
| MI 1 | System Operation Status | Room state: normal, door, warning, alarm, ACH | Read |
| BI 1 | Digital Input Status | Door or valve contact | Read |
| MV 8 | Pressure Alarm status | Which room is in pressure alarm | Read |
| BV 1 | Relay Status | Alarm relay state | Read |
Sensors & values from the BMS
Temperature, humidity and user-defined inputs can take their value from BACnet: set the matching input source MV (17, 19, 21, 23, 25, 27) to 3 = BACnet. The document does not say which object the BMS writes the value to.
Network setup
- The secondary room uses an external transducer on an analog channel (MV 9); set the channel ranges with AV 5 / AV 54 and AV 49-52.
Watch out for
- Alarm limits exist per isolation mode (positive, neutral, negative) for each room; write the set that matches MV 2 / MV 13.
- The analog values carry no fixed units; check BV 2-4 / BV 10 for the active unit before scaling.
- Most binary values and several multistate values are display settings; avoid cyclic writes.
Setra SRCM Room Condition Monitor (two-room) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Primary Pressure | Primary room pressure | Read | ||
| AImin | 2 | Secondary Pressure | Secondary room pressure | Read | ||
| AImin | 3 | Primary Temperature | Primary room temperature | Read | ||
| AI | 4 | Secondary Temperature | Secondary room temperature | Read | ||
| AImin | 5 | Primary Humidity | Primary room humidity | Read | ||
| AI | 6 | Secondary Humidity | Secondary room humidity | Read | ||
| AI | 7 | Primary User Defined Parameter | Primary room user-defined input | Read | ||
| AI | 8 | Secondary User Defined Parameter | Secondary room user-defined input | Read | ||
| AV | 1 | Primary analog output | Analog output value for the primary room pressure | Read | ||
| AV | 46 | Sensor Full Scale | Full-scale range of the on-board sensor | Read | ||
| AV | 2 | Primary Pressure Low Range | Low range of external primary pressure transducer (ADC) | Read | ||
| AV | 53 | Primary Pressure High Range | High range of external primary pressure transducer (ADC) | Read | ||
| AV | 15 | Primary Temperature Low Range | Low range of primary temperature input (ADC) | Read | ||
| AV | 16 | Primary Temperature High Range | High range of primary temperature input (ADC) | Read | ||
| AV | 29 | Primary Humidity Low Range | Low range of primary humidity input (ADC) | Read | ||
| AV | 30 | Primary Humidity High Range | High range of primary humidity input (ADC) | Read | ||
| AV | 27 | Primary User Defined Parameter Low Range | Low range of primary user-defined input (ADC) | Read | ||
| AV | 28 | Primary User Defined Parameter High Range | High range of primary user-defined input (ADC) | Read | ||
| AV | 3 | Primary Alarm Low Limit for Positive Pressure | Primary low alarm limit, positive mode | Write | ||
| AV | 4 | Primary Alarm High Limit for Positive Pressure | Primary high alarm limit, positive mode | Write | ||
| AV | 33 | Primary Alarm Low Limit for Neutral Pressure | Primary low alarm limit, neutral mode | Write | ||
| AV | 34 | Primary Alarm High Limit for Neutral Pressure | Primary high alarm limit, neutral mode | Write | ||
| AV | 31 | Primary Alarm Low Limit for Negative Pressure | Primary low alarm limit, negative mode | Write | ||
| AV | 32 | Primary Alarm High Limit for Negative Pressure | Primary high alarm limit, negative mode | Write | ||
| AV | 5 | Secondary Pressure Low Range | Low range of external secondary pressure transducer (ADC) | Read | ||
| AV | 54 | Secondary Pressure High Range | High range of external secondary pressure transducer (ADC) | Read | ||
| AV | 40 | Secondary Temperature Low Range | Low range of secondary temperature input (ADC) | Read | ||
| AV | 41 | Secondary Temperature High Range | High range of secondary temperature input (ADC) | Read | ||
| AV | 42 | Secondary Humidity Low Range | Low range of secondary humidity input (ADC) | Read | ||
| AV | 43 | Secondary Humidity High Range | High range of secondary humidity input (ADC) | Read | ||
| AV | 44 | Secondary User Defined Parameter Low Range | Low range of secondary user-defined input (ADC) | Read | ||
| AV | 45 | Secondary User Defined Parameter High Range | High range of secondary user-defined input (ADC) | Read | ||
| AV | 6 | Secondary Alarm Low Limit for Positive Pressure | Secondary low alarm limit, positive mode | Write | ||
| AV | 7 | Secondary Alarm High Limit for Positive Pressure | Secondary high alarm limit, positive mode | Write | ||
| AV | 38 | Secondary Alarm Low Limit for Neutral Pressure | Secondary low alarm limit, neutral mode | Write | ||
| AV | 39 | Secondary Alarm High Limit for Neutral Pressure | Secondary high alarm limit, neutral mode | Write | ||
| AV | 36 | Secondary Alarm Low Limit for Negative Pressure | Secondary low alarm limit, negative mode | Write | ||
| AV | 37 | Secondary Alarm High Limit for Negative Pressure | Secondary high alarm limit, negative mode | Write | ||
| AV | 8 | Alarm Delay | Delay for pressure, valve and ACH alarms (0-9999) | Write | ||
| AV | 9 | Mute Time Out | Buzzer mute timeout (0-9999; 99999 = mute forever) | Write | ||
| AV | 10 | Buzzer Volume | Buzzer volume (0-4) | Write | ||
| AV | 11 | Dead Band | Pressure and ACH alarm dead band (1-10 %) | Write | ||
| AV | 12 | Contrast Level | Display contrast (1-4) | Write | ||
| AV | 13 | Pressure Resolution | Pressure display resolution (2-4) | Write | ||
| AV | 14 | Display Average | Display averaging window (0-40) | Write | ||
| AV | 35 | Window Size | Moving average window size (1-40) | Read | ||
| AV | 49 | ADC Ch1 Input Low voltage | ADC channel 1 low input voltage | Read | ||
| AV | 50 | ADC Ch1 Input High voltage | ADC channel 1 high input voltage | Read | ||
| AV | 51 | ADC Ch2 Input Low voltage | ADC channel 2 low input voltage | Read | ||
| AV | 52 | ADC Ch2 Input High voltage | ADC channel 2 high input voltage | Read | ||
| BImin | 1 | Digital Input Status | Digital input contact | Read | 0 = Input Closed, 1 = Input Open | |
| BVmin | 1 | Relay Status | Alarm relay state | Read | 0 = Relay Off, 1 = Relay On | |
| BV | 2 | Primary Pressure Unit | Primary pressure unit | Write | 0 = "WC, 1 = Pa | |
| BV | 3 | Secondary Pressure Unit | Secondary pressure unit | Write | 0 = "WC, 1 = Pa | |
| BV | 4 | Primary Temperature Unit | Primary temperature unit | Write | 0 = Fahrenheit, 1 = Celsius | |
| BV | 10 | Secondary Temperature Unit | Secondary temperature unit | Write | 0 = Fahrenheit, 1 = Celsius | |
| BV | 6 | Alarm Latch Status | Alarm latching on/off | Write | 0 = Disabled, 1 = Enabled | |
| BV | 8 | Supervisory Password Status | Supervisor password protection | Write | 0 = Disabled, 1 = Enabled | |
| BV | 9 | Operator Password Status | Operator password protection | Write | 0 = Disabled, 1 = Enabled | |
| BV | 11 | User Define Text Status | User-defined text display | Write | 0 = Disabled, 1 = Enabled | |
| BV | 12 | Slider Status | Display slider | Write | 0 = Slider Off, 1 = Slider On | |
| BV | 14 | Language support | Display language | Write | 0 = French, 1 = English | |
| BV | 15 | Alarm Condition Blink Status | Blink in alarm condition | Write | 0 = Disabled, 1 = Enabled | |
| BV | 16 | Normal Condition Blink Status | Blink in normal condition | Write | 0 = Disabled, 1 = Enabled | |
| BV | 17 | Warning Condition Blink Status | Blink in warning condition | Write | 0 = Disabled, 1 = Enabled | |
| BV | 18 | Blink In Red | Blink for red condition banner | Write | 0 = Disabled, 1 = Enabled | |
| BV | 19 | Blink In Green | Blink for green condition banner | Write | 0 = Disabled, 1 = Enabled | |
| BV | 20 | Blink In Yellow | Blink for yellow condition banner | Write | 0 = Disabled, 1 = Enabled | |
| BV | 26 | Blink In Blue | Blink for blue condition banner | Write | 0 = Disabled, 1 = Enabled | |
| BV | 22 | Audible Alarm Status | Audible alarm on/off | Write | 0 = Disabled, 1 = Enabled | |
| BV | 23 | Full Screen Condition Banner | Full-screen condition banner feature | Write | 0 = Disabled, 1 = Enabled | |
| MImin | 1 | System Operation Status | Room condition shown by the monitor | Read | 1 = NORMAL, 2 = DOOR, 3 = WARNING, 4 = VALVE, 5 = ALARM, 6 = ACH | |
| MV | 1 | Analog Output Type | Primary room analog output type | Read | 1 = 4-20 mA, 2 = 0-5 V, 3 = 0-10 V | |
| MVmin | 2 | Primary Room Pressure Mode | Primary room isolation mode | Write | 1 = Positive, 2 = Negative, 3 = Neutral | |
| MV | 13 | Secondary Room Pressure Mode | Secondary room isolation mode | Write | 1 = Positive, 2 = Negative, 3 = Neutral | |
| MV | 3 | Color mode | Condition banner colour | Write | 1 = Green, 2 = Red, 3 = Yellow, 4 = Blue | |
| MV | 14 | Red Condition Banner Mode | Mode shown with the red banner | Write | 1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied | |
| MV | 15 | Green Condition Banner Mode | Mode shown with the green banner | Write | 1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied | |
| MV | 16 | Yellow Condition Banner Mode | Mode shown with the yellow banner | Write | 1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied | |
| MV | 31 | Blue Condition Banner Mode | Mode shown with the blue banner | Write | 1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied | |
| MV | 5 | Room to Display | Room shown on the home screen | Write | 1 = Primary Only, 2 = Secondary Only, 3 = Toggle between the two | |
| MV | 10 | Primary Room Pressure Input Source | Primary pressure source | Read | 1 = Onboard Sensor, 2 = Analog CH1, 3 = Analog CH2 | |
| MV | 17 | Primary Room Temperature Input Source | Primary temperature source | Read | 1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None | |
| MV | 19 | Primary Room Humidity Input Source | Primary humidity source | Read | 1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None | |
| MV | 21 | Primary Room User Defined Parameter Input Source | Primary user-defined input source | Read | 1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None | |
| MV | 9 | Secondary Room Pressure Input Source | Secondary pressure source | Read | 1 = Analog Ch1, 2 = Analog Ch2, 3 = None | |
| MV | 23 | Secondary Room Temperature Input Source | Secondary temperature source | Read | 1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None | |
| MV | 25 | Secondary Room Humidity Input Source | Secondary humidity source | Read | 1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None | |
| MV | 27 | Secondary Room User Defined Parameter Input Source | Secondary user-defined input source | Write | 1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None | |
| MVmin | 8 | Pressure Alarm status | Pressure alarm summary | Read | 1 = Primary alarm active, 2 = Secondary alarm active, 3 = Both active, 4 = Both normal | |
| MV | 11 | Digital Input Configuration | Digital input function | Read | 1 = Door, 2 = Valve, 3 = Disabled, 4 = Door != Alarm | |
| MVmin | 29 | Room Occupancy Status | Room occupancy | Write | 1 = Active, 2 = Standby | |
| MV | 6 | Primary Parameter 1 | Primary room display parameter 1 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 18 | Primary Parameter 2 | Primary room display parameter 2 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 20 | Primary Parameter 3 | Primary room display parameter 3 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 22 | Primary Parameter 4 | Primary room display parameter 4 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 7 | Secondary Parameter 1 | Secondary room display parameter 1 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 24 | Secondary Parameter 2 | Secondary room display parameter 2 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 26 | Secondary Parameter 3 | Secondary room display parameter 3 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None | |
| MV | 28 | Secondary Parameter 4 | Secondary room display parameter 4 | Read | 1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None |
No points match these filters.
Object ID lookup: Setra SRCM Room Condition Monitor point IDs by name
AI1Primary PressureAI2Secondary PressureAI3Primary TemperatureAI4Secondary TemperatureAI5Primary HumidityAI6Secondary HumidityAI7Primary User Defined ParameterAI8Secondary User Defined ParameterAV1Primary analog outputAV46Sensor Full ScaleAV2Primary Pressure Low RangeAV53Primary Pressure High RangeAV15Primary Temperature Low RangeAV16Primary Temperature High RangeAV29Primary Humidity Low RangeAV30Primary Humidity High RangeAV27Primary User Defined Parameter Low RangeAV28Primary User Defined Parameter High RangeAV3Primary Alarm Low Limit for Positive PressureAV4Primary Alarm High Limit for Positive PressureAV33Primary Alarm Low Limit for Neutral PressureAV34Primary Alarm High Limit for Neutral PressureAV31Primary Alarm Low Limit for Negative PressureAV32Primary Alarm High Limit for Negative PressureAV5Secondary Pressure Low RangeAV54Secondary Pressure High RangeAV40Secondary Temperature Low RangeAV41Secondary Temperature High RangeAV42Secondary Humidity Low RangeAV43Secondary Humidity High RangeAV44Secondary User Defined Parameter Low RangeAV45Secondary User Defined Parameter High RangeAV6Secondary Alarm Low Limit for Positive PressureAV7Secondary Alarm High Limit for Positive PressureAV38Secondary Alarm Low Limit for Neutral PressureAV39Secondary Alarm High Limit for Neutral PressureAV36Secondary Alarm Low Limit for Negative PressureAV37Secondary Alarm High Limit for Negative PressureAV8Alarm DelayAV9Mute Time OutAV10Buzzer VolumeAV11Dead BandAV12Contrast LevelAV13Pressure ResolutionAV14Display AverageAV35Window SizeAV49ADC Ch1 Input Low voltageAV50ADC Ch1 Input High voltageAV51ADC Ch2 Input Low voltageAV52ADC Ch2 Input High voltageBI1Digital Input StatusBV1Relay StatusBV2Primary Pressure UnitBV3Secondary Pressure UnitBV4Primary Temperature UnitBV10Secondary Temperature UnitBV6Alarm Latch StatusBV8Supervisory Password StatusBV9Operator Password StatusBV11User Define Text StatusBV12Slider StatusBV14Language supportBV15Alarm Condition Blink StatusBV16Normal Condition Blink StatusBV17Warning Condition Blink StatusBV18Blink In RedBV19Blink In GreenBV20Blink In YellowBV26Blink In BlueBV22Audible Alarm StatusBV23Full Screen Condition BannerMI1System Operation StatusMV1Analog Output TypeMV2Primary Room Pressure ModeMV13Secondary Room Pressure ModeMV3Color modeMV14Red Condition Banner ModeMV15Green Condition Banner ModeMV16Yellow Condition Banner ModeMV31Blue Condition Banner ModeMV5Room to DisplayMV10Primary Room Pressure Input SourceMV17Primary Room Temperature Input SourceMV19Primary Room Humidity Input SourceMV21Primary Room User Defined Parameter Input SourceMV9Secondary Room Pressure Input SourceMV23Secondary Room Temperature Input SourceMV25Secondary Room Humidity Input SourceMV27Secondary Room User Defined Parameter Input SourceMV8Pressure Alarm statusMV11Digital Input ConfigurationMV29Room Occupancy StatusMV6Primary Parameter 1MV18Primary Parameter 2MV20Primary Parameter 3MV22Primary Parameter 4MV7Secondary Parameter 1MV24Secondary Parameter 2MV26Secondary Parameter 3MV28Secondary Parameter 4
Integration notes
- Object names come from the summary table (pp1-5); read/write comes from the Present_Value row of each object's property table (pp6-35). The property pages print some names differently (e.g. 'Primary Room Isolation Mode' for MV 2).
- Twenty Character String Value objects (PCV 1-20: room labels, user-defined names and units, audit trail strings, technical support ID and banner texts) are typed as proprietary objects in the property tables and are left out here.
- The list also has notification classes NC 1-4 and event enrollments EE 1-4 for primary and secondary room pressure warning and alarm.
- Pressure units follow BV 2 / BV 3 and temperature units BV 4 / BV 10; the analog objects carry no fixed units in the document.
- The summary table describes AV 7 as the negative-mode limit; its name and the property page say positive pressure.
- The document does not state the data link (BACnet IP or BACnet MS/TP).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SRCM Room Condition Monitor (two-room) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Setra SRCM Room Condition Monitor (two-room)
How many BACnet points does the Setra SRCM Room Condition Monitor (two-room) have?
This list has 100 BACnet objects: 8 analog inputs, 42 analog values, 1 binary input, 20 binary values, 1 multi-state input, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Setra SRCM Room Condition Monitor (two-room) BACnet points are writable?
48 of the 100 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Setra SRCM Room Condition Monitor (two-room) BACnet documentation?
Setra does not publish it on its own website. This list comes from SRCM BACnet Object List, a copy hosted by Kele at https://assets.kele.com/Catalog/19%20Pressure/PDFs/SRCM%20BACnet%20Objects%20List.pdf. Ask Setra or its representative for the current revision.
What are the minimum BACnet points to integrate the Setra SRCM Room Condition Monitor (two-room)?
Start with MV 2 Primary Room Pressure Mode (Primary isolation mode: 1 pos, 2 neg, 3 neutral); MV 29 Room Occupancy Status (Occupancy: 1 = Active, 2 = Standby); AI 1 Primary Pressure (Primary room differential pressure); AI 2 Secondary Pressure (Secondary room differential pressure); AI 3 Primary Temperature (Primary room temperature); AI 5 Primary Humidity (Primary room humidity); MI 1 System Operation Status (Room state: normal, door, warning, alarm, ACH); BI 1 Digital Input Status (Door or valve contact); MV 8 Pressure Alarm status (Which room is in pressure alarm); BV 1 Relay Status (Alarm relay state).
Can the BMS supply sensor values to the Setra SRCM Room Condition Monitor (two-room)?
Temperature, humidity and user-defined inputs can take their value from BACnet: set the matching input source MV (17, 19, 21, 23, 25, 27) to 3 = BACnet. The document does not say which object the BMS writes the value to.
How do I check these points on the real SRCM Room Condition Monitor (two-room)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Setra BACnet points lists
- Room pressure monitor and controller
Setra FLEX Room Pressure Monitor
Setra FLEX wall-mounted room pressure and environmental monitors (FLEX-RM monitor-only and FLEX-RC room control) covering up to three rooms.
Also known as: SetraFLEX, Setra FLEX, FLEX-RM, FLEX-RC, Setra FLEX Environmental Monitor - Multi-load power meter
Setra Power Meter (SPM) - load device
Setra Power Meter (SPM) multi-load electrical meters; this entry covers each virtual load device (one per configured load).
Also known as: SPM, Setra SPM, Setra Power Meter, SPM load - Multi-load power meter
Setra Power Meter (SPM) - root device
Setra Power Meter (SPM) multi-load electrical meters; this entry covers the root device that carries the voltage inputs.
Also known as: SPM, Setra SPM, Setra Power Meter, Setra multi-load power meter - Humidity / temperature sensor