Room pressure monitor (room condition monitor) · BACnet points list

Setra SRCM Room Condition Monitor (two-room) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The SRCM monitors pressure, temperature, humidity and a user-defined value for a primary and a secondary room, with alarm limits per isolation mode. Its BACnet object list gives the eight readings as analog inputs, alarm limits per isolation mode and input ranges as analog values, display and alarm options as binary values, and input sources, isolation modes and banner modes as multistate values. This is a larger, two-room object list than the single-room Siemens RPM map already in the library.

This page lists 100 BACnet objects for the Setra SRCM Room Condition Monitor (two-room) — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Setra’s documentation hosted by Kele, not by Setra itself, so treat it as unofficial.

Manufacturer
Setra
Model
SRCM Room Condition Monitor (two-room)
Equipment
Room pressure monitor (room condition monitor)
Equipment type
Thermostats, sensors & meters
BACnet objects
100 (48 writable)
Transport
—
Firmware
Not stated
Also known as
SRCM, Setra SRCM, Room Condition Monitor, Setra Room Condition Monitor
Source document
SRCM BACnet Object List (unofficial copy, hosted by Kele)
Download CSV 100 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.

BMS integration notes: Setra SRCM Room Condition Monitor (two-room)

Integration in brief

Read the room pressures (AI 1 / AI 2) and the alarm summary (MV 8 / MI 1) for monitoring. Set the isolation mode of each room (MV 2 / MV 13) and the alarm limits for that mode from the BMS only if the monitor is not configured locally. Temperature, humidity and user values can be written from BACnet when their input source is set to BACnet.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2Primary Room Pressure ModePrimary isolation mode: 1 pos, 2 neg, 3 neutralWrite
MV 29Room Occupancy StatusOccupancy: 1 = Active, 2 = StandbyWrite
AI 1Primary PressurePrimary room differential pressureRead
AI 2Secondary PressureSecondary room differential pressureRead
AI 3Primary TemperaturePrimary room temperatureRead
AI 5Primary HumidityPrimary room humidityRead
MI 1System Operation StatusRoom state: normal, door, warning, alarm, ACHRead
BI 1Digital Input StatusDoor or valve contactRead
MV 8Pressure Alarm statusWhich room is in pressure alarmRead
BV 1Relay StatusAlarm relay stateRead

Sensors & values from the BMS

Temperature, humidity and user-defined inputs can take their value from BACnet: set the matching input source MV (17, 19, 21, 23, 25, 27) to 3 = BACnet. The document does not say which object the BMS writes the value to.

Network setup

Watch out for

Setra SRCM Room Condition Monitor (two-room) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

100 of 100 shown
Type
Access
Show
Setra SRCM Room Condition Monitor (two-room) BACnet Points List
DescriptionStates
AImin1Primary PressurePrimary room pressureRead
AImin2Secondary PressureSecondary room pressureRead
AImin3Primary TemperaturePrimary room temperatureRead
AI4Secondary TemperatureSecondary room temperatureRead
AImin5Primary HumidityPrimary room humidityRead
AI6Secondary HumiditySecondary room humidityRead
AI7Primary User Defined ParameterPrimary room user-defined inputRead
AI8Secondary User Defined ParameterSecondary room user-defined inputRead
AV1Primary analog outputAnalog output value for the primary room pressureRead
AV46Sensor Full ScaleFull-scale range of the on-board sensorRead
AV2Primary Pressure Low RangeLow range of external primary pressure transducer (ADC)Read
AV53Primary Pressure High RangeHigh range of external primary pressure transducer (ADC)Read
AV15Primary Temperature Low RangeLow range of primary temperature input (ADC)Read
AV16Primary Temperature High RangeHigh range of primary temperature input (ADC)Read
AV29Primary Humidity Low RangeLow range of primary humidity input (ADC)Read
AV30Primary Humidity High RangeHigh range of primary humidity input (ADC)Read
AV27Primary User Defined Parameter Low RangeLow range of primary user-defined input (ADC)Read
AV28Primary User Defined Parameter High RangeHigh range of primary user-defined input (ADC)Read
AV3Primary Alarm Low Limit for Positive PressurePrimary low alarm limit, positive modeWrite
AV4Primary Alarm High Limit for Positive PressurePrimary high alarm limit, positive modeWrite
AV33Primary Alarm Low Limit for Neutral PressurePrimary low alarm limit, neutral modeWrite
AV34Primary Alarm High Limit for Neutral PressurePrimary high alarm limit, neutral modeWrite
AV31Primary Alarm Low Limit for Negative PressurePrimary low alarm limit, negative modeWrite
AV32Primary Alarm High Limit for Negative PressurePrimary high alarm limit, negative modeWrite
AV5Secondary Pressure Low RangeLow range of external secondary pressure transducer (ADC)Read
AV54Secondary Pressure High RangeHigh range of external secondary pressure transducer (ADC)Read
AV40Secondary Temperature Low RangeLow range of secondary temperature input (ADC)Read
AV41Secondary Temperature High RangeHigh range of secondary temperature input (ADC)Read
AV42Secondary Humidity Low RangeLow range of secondary humidity input (ADC)Read
AV43Secondary Humidity High RangeHigh range of secondary humidity input (ADC)Read
AV44Secondary User Defined Parameter Low RangeLow range of secondary user-defined input (ADC)Read
AV45Secondary User Defined Parameter High RangeHigh range of secondary user-defined input (ADC)Read
AV6Secondary Alarm Low Limit for Positive PressureSecondary low alarm limit, positive modeWrite
AV7Secondary Alarm High Limit for Positive PressureSecondary high alarm limit, positive modeWrite
AV38Secondary Alarm Low Limit for Neutral PressureSecondary low alarm limit, neutral modeWrite
AV39Secondary Alarm High Limit for Neutral PressureSecondary high alarm limit, neutral modeWrite
AV36Secondary Alarm Low Limit for Negative PressureSecondary low alarm limit, negative modeWrite
AV37Secondary Alarm High Limit for Negative PressureSecondary high alarm limit, negative modeWrite
AV8Alarm DelayDelay for pressure, valve and ACH alarms (0-9999)Write
AV9Mute Time OutBuzzer mute timeout (0-9999; 99999 = mute forever)Write
AV10Buzzer VolumeBuzzer volume (0-4)Write
AV11Dead BandPressure and ACH alarm dead band (1-10 %)Write
AV12Contrast LevelDisplay contrast (1-4)Write
AV13Pressure ResolutionPressure display resolution (2-4)Write
AV14Display AverageDisplay averaging window (0-40)Write
AV35Window SizeMoving average window size (1-40)Read
AV49ADC Ch1 Input Low voltageADC channel 1 low input voltageRead
AV50ADC Ch1 Input High voltageADC channel 1 high input voltageRead
AV51ADC Ch2 Input Low voltageADC channel 2 low input voltageRead
AV52ADC Ch2 Input High voltageADC channel 2 high input voltageRead
BImin1Digital Input StatusDigital input contactRead0 = Input Closed, 1 = Input Open
BVmin1Relay StatusAlarm relay stateRead0 = Relay Off, 1 = Relay On
BV2Primary Pressure UnitPrimary pressure unitWrite0 = "WC, 1 = Pa
BV3Secondary Pressure UnitSecondary pressure unitWrite0 = "WC, 1 = Pa
BV4Primary Temperature UnitPrimary temperature unitWrite0 = Fahrenheit, 1 = Celsius
BV10Secondary Temperature UnitSecondary temperature unitWrite0 = Fahrenheit, 1 = Celsius
BV6Alarm Latch StatusAlarm latching on/offWrite0 = Disabled, 1 = Enabled
BV8Supervisory Password StatusSupervisor password protectionWrite0 = Disabled, 1 = Enabled
BV9Operator Password StatusOperator password protectionWrite0 = Disabled, 1 = Enabled
BV11User Define Text StatusUser-defined text displayWrite0 = Disabled, 1 = Enabled
BV12Slider StatusDisplay sliderWrite0 = Slider Off, 1 = Slider On
BV14Language supportDisplay languageWrite0 = French, 1 = English
BV15Alarm Condition Blink StatusBlink in alarm conditionWrite0 = Disabled, 1 = Enabled
BV16Normal Condition Blink StatusBlink in normal conditionWrite0 = Disabled, 1 = Enabled
BV17Warning Condition Blink StatusBlink in warning conditionWrite0 = Disabled, 1 = Enabled
BV18Blink In RedBlink for red condition bannerWrite0 = Disabled, 1 = Enabled
BV19Blink In GreenBlink for green condition bannerWrite0 = Disabled, 1 = Enabled
BV20Blink In YellowBlink for yellow condition bannerWrite0 = Disabled, 1 = Enabled
BV26Blink In BlueBlink for blue condition bannerWrite0 = Disabled, 1 = Enabled
BV22Audible Alarm StatusAudible alarm on/offWrite0 = Disabled, 1 = Enabled
BV23Full Screen Condition BannerFull-screen condition banner featureWrite0 = Disabled, 1 = Enabled
MImin1System Operation StatusRoom condition shown by the monitorRead1 = NORMAL, 2 = DOOR, 3 = WARNING, 4 = VALVE, 5 = ALARM, 6 = ACH
MV1Analog Output TypePrimary room analog output typeRead1 = 4-20 mA, 2 = 0-5 V, 3 = 0-10 V
MVmin2Primary Room Pressure ModePrimary room isolation modeWrite1 = Positive, 2 = Negative, 3 = Neutral
MV13Secondary Room Pressure ModeSecondary room isolation modeWrite1 = Positive, 2 = Negative, 3 = Neutral
MV3Color modeCondition banner colourWrite1 = Green, 2 = Red, 3 = Yellow, 4 = Blue
MV14Red Condition Banner ModeMode shown with the red bannerWrite1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied
MV15Green Condition Banner ModeMode shown with the green bannerWrite1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied
MV16Yellow Condition Banner ModeMode shown with the yellow bannerWrite1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied
MV31Blue Condition Banner ModeMode shown with the blue bannerWrite1 = Active, 2 = Standby, 3 = No Action, 4 = Occupied, 5 = Unoccupied
MV5Room to DisplayRoom shown on the home screenWrite1 = Primary Only, 2 = Secondary Only, 3 = Toggle between the two
MV10Primary Room Pressure Input SourcePrimary pressure sourceRead1 = Onboard Sensor, 2 = Analog CH1, 3 = Analog CH2
MV17Primary Room Temperature Input SourcePrimary temperature sourceRead1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None
MV19Primary Room Humidity Input SourcePrimary humidity sourceRead1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None
MV21Primary Room User Defined Parameter Input SourcePrimary user-defined input sourceRead1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None
MV9Secondary Room Pressure Input SourceSecondary pressure sourceRead1 = Analog Ch1, 2 = Analog Ch2, 3 = None
MV23Secondary Room Temperature Input SourceSecondary temperature sourceRead1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None
MV25Secondary Room Humidity Input SourceSecondary humidity sourceRead1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None
MV27Secondary Room User Defined Parameter Input SourceSecondary user-defined input sourceWrite1 = ADC CH-1, 2 = ADC CH-2, 3 = BACnet, 4 = None
MVmin8Pressure Alarm statusPressure alarm summaryRead1 = Primary alarm active, 2 = Secondary alarm active, 3 = Both active, 4 = Both normal
MV11Digital Input ConfigurationDigital input functionRead1 = Door, 2 = Valve, 3 = Disabled, 4 = Door != Alarm
MVmin29Room Occupancy StatusRoom occupancyWrite1 = Active, 2 = Standby
MV6Primary Parameter 1Primary room display parameter 1Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV18Primary Parameter 2Primary room display parameter 2Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV20Primary Parameter 3Primary room display parameter 3Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV22Primary Parameter 4Primary room display parameter 4Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV7Secondary Parameter 1Secondary room display parameter 1Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV24Secondary Parameter 2Secondary room display parameter 2Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV26Secondary Parameter 3Secondary room display parameter 3Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
MV28Secondary Parameter 4Secondary room display parameter 4Read1 = Pressure, 2 = Temperature, 3 = Humidity, 4 = User defined, 5 = None
Object ID lookup: Setra SRCM Room Condition Monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SRCM Room Condition Monitor (two-room) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Setra SRCM Room Condition Monitor (two-room)

How many BACnet points does the Setra SRCM Room Condition Monitor (two-room) have?

This list has 100 BACnet objects: 8 analog inputs, 42 analog values, 1 binary input, 20 binary values, 1 multi-state input, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Setra SRCM Room Condition Monitor (two-room) BACnet points are writable?

48 of the 100 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Setra SRCM Room Condition Monitor (two-room) BACnet documentation?

Setra does not publish it on its own website. This list comes from SRCM BACnet Object List, a copy hosted by Kele at https://assets.kele.com/Catalog/19%20Pressure/PDFs/SRCM%20BACnet%20Objects%20List.pdf. Ask Setra or its representative for the current revision.

What are the minimum BACnet points to integrate the Setra SRCM Room Condition Monitor (two-room)?

Start with MV 2 Primary Room Pressure Mode (Primary isolation mode: 1 pos, 2 neg, 3 neutral); MV 29 Room Occupancy Status (Occupancy: 1 = Active, 2 = Standby); AI 1 Primary Pressure (Primary room differential pressure); AI 2 Secondary Pressure (Secondary room differential pressure); AI 3 Primary Temperature (Primary room temperature); AI 5 Primary Humidity (Primary room humidity); MI 1 System Operation Status (Room state: normal, door, warning, alarm, ACH); BI 1 Digital Input Status (Door or valve contact); MV 8 Pressure Alarm status (Which room is in pressure alarm); BV 1 Relay Status (Alarm relay state).

Can the BMS supply sensor values to the Setra SRCM Room Condition Monitor (two-room)?

Temperature, humidity and user-defined inputs can take their value from BACnet: set the matching input source MV (17, 19, 21, 23, 25, 27) to 3 = BACnet. The document does not say which object the BMS writes the value to.

How do I check these points on the real SRCM Room Condition Monitor (two-room)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Setra BACnet points lists

Source: SRCM BACnet Object List. Object names, instances and units are reproduced as published; descriptions are our own.