Indoor air quality multi-sensor (CO2 / PM / TVOC / CO / ozone) · BACnet points list
Senva TotalSense air quality sensor (BACnet MS/TP) BACnet points list
Updated 6 November 2026
TotalSense is a Senva indoor air quality monitor with BACnet MS/TP. Analog Inputs give temperature, RH, dew point, CO2, TVOC, PM mass and counts, CO, ozone, light, occupancy, pressure, an air quality index and per-sensor status flags. Analog Values hold offsets, CO2 auto-calibration, relay and analog output setup, a built-in PID loop, air quality thresholds and display options.
This page lists 113 BACnet objects for the Senva TotalSense air quality sensor (BACnet MS/TP) — 69 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Senva’s own free documentation, linked below.
- Manufacturer
- Senva
- Model
- TotalSense air quality sensor (BACnet MS/TP)
- Equipment
- Indoor air quality multi-sensor (CO2 / PM / TVOC / CO / ozone)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 113 (69 writable)
- Transport
- BACnet MS/TP
- Firmware
- VSBHP 14.10, application 1.2.x (PICS 5/13/2021)
- Also known as
- TotalSense, AQ2W, AQ2W-XXXXXX, Senva TotalSense IAQ, Senva TotalSense CO2 PM TVOC
Reference only, provided as-is: verify against Senva’s current documentation and the live device before use. Not official Senva information. Terms of use.
BMS integration notes: Senva TotalSense air quality sensor (BACnet MS/TP)
Set protocol, MAC and baud on the DIP switches, then read temperature, RH, CO2, PM2.5, TVOC and the air quality index. Check the per-sensor status AIs for faults.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Temperature | Space temperature (units per AV 2) | Read |
| AI 2 | Relative humidity | Space RH | Read |
| AI 3 | CO2 | Space CO2, ppm | Read |
| AI 7 | PM 2.5 ug/m3 | PM2.5, µg/m3 | Read |
| AI 4 | TVOC ug/m3 | TVOC, µg/m3 | Read |
| AI 10 | Air quality | 0 Good, 1 Fair, 2 Poor | Read |
| AI 12 | Occupancy | PIR occupancy (PIR models) | Read |
| AI 17 | System status | System fault bit flags | Read |
Network setup
- Protocol, MAC address (0-127), baud (9600-115200) and data/parity/stop come from DIP switches.
- Device instance ships as 655xxx (last 3 digits of the serial number) and is writable; Max_Master is writable.
Watch out for
- AV 31 = 1234 restores factory settings.
- TVOC ppb assumes ethanol's molecular weight; use AV 8 to rescale for another compound.
Senva TotalSense air quality sensor (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Temperature | Space temperature (units per AV 2) | °F / °C | Read | |
| AImin | 2 | Relative humidity | Relative humidity | %RH | Read | |
| AImin | 3 | CO2 | CO2 concentration | ppm | Read | |
| AImin | 4 | TVOC ug/m3 | TVOC, compensated for temperature and pressure | µg/m3 | Read | |
| AI | 5 | TVOC PPB | TVOC as ppb (ethanol-based conversion, scale with AV 8) | ppb | Read | |
| AI | 6 | PM 1.0 ug/m3 | Concentration of particles sized 0.3-1.0 µg/m3 | µg/m3 | Read | |
| AImin | 7 | PM 2.5 ug/m3 | Concentration of particles sized 0.3-2.5 µg/m3 | µg/m3 | Read | |
| AI | 8 | PM 4.0 ug/m3 | Concentration of particles sized 0.3-4.0 µg/m3 | µg/m3 | Read | |
| AI | 9 | PM 10.0 ug/m3 | Concentration of particles sized 0.3-10.0 µg/m3 | µg/m3 | Read | |
| AImin | 10 | Air quality | Air quality status | Read | 0=Good, 1=Fair, 2=Poor | |
| AI | 11 | Slider display | Setpoint slider position | °F / °C | Read | |
| AImin | 12 | Occupancy | Status of PIR occupancy sensor | Read | 0=Unoccupied, 1=Occupied | |
| AI | 13 | Ambient light | Ambient light level | fc | Read | |
| AI | 14 | Relay contacts state | State of setpoint relay | Read | 0=OPEN, 1=CLOSED | |
| AI | 15 | Dewpoint | Dew point temperature | °F / °C | Read | |
| AI | 16 | Pressure | Barometric pressure (pressure models) | inHg | Read | |
| AImin | 17 | System status | System status bit flags | Read | 0x01=EEPROM hardware fault (Consult factory); 0x02=EEPROM data corruption (Consult factory); 0x04=EEPROM write error (Consult factory); 0x08=Device is currently using factory defaults (Consult factory); 0x10=Sensor error (see individual sensor status to more info). Bolded statuses will trigger this error. | |
| AI | 18 | Temp sensor status | Temp sensor status bit flags | Read | 0x01=Sensor hardware fault (Consult factory); 0x02=Sensor Data error (Consult factory) | |
| AI | 19 | RH sensor status | RH sensor status bit flags | Read | 0x01=Sensor hardware fault (Consult factory); 0x02=Sensor Data error (Consult factory) | |
| AI | 20 | CO2 sensor status | CO2 sensor status bit flags | Read | 0x01=Sensor hardware fault (Consult factory); 0x02=Sensor Data error (Consult factory); 0x04=Sensor not ready (Consult factory); 0x40=Temperature compensation not applied (No action necessary. Default value 25oC is used for temp compensation).; 0x80=Pressure compensation not applied (No action necessary. Default value 25oC is used for pressure compensation. | |
| AI | 21 | TVOC sensor status | TVOC sensor status bit flags | Read | 0x01=Sensor hardware (I2C) fault (Consult factory); 0x02=Sensor data error; 0x04=Sensor other hardware error; 0x08=Sensor not ready (training); 0x10=Temperature compensation not applied; 0x20=Humidity compensation not applied | |
| AI | 22 | PM sensor status | PM sensor status bit flags | Read | 0x01=Sensor communication error (Consult factory); 0x02=Sensor Data Error (Consult factory); 0x04=Sensor not ready (Consult factory); 0x08=Sensor fan speed warning (Consult factory); 0x10=Sensor fan failure (Consult factory); 0x20=Sensor laser failure (Consult factory) | |
| AI | 23 | Pressure sensor status | Pressure sensor status bit flags | Read | 0x01=Sensor hardware fault (Consult factory); 0x02=Sensor Data error (Consult factory); 0x04=Sensor not ready (Consult factory) | |
| AI | 24 | PID Output Power | PID analog output level | Read | ||
| AI | 25 | PM0.5 Particle Count | Counts for particles size 0.3 to 0.5 | #/cm3 | Read | |
| AI | 26 | PM1.0 Particle Count | Counts for particles size 0.3 to 1.0 | #/cm3 | Read | |
| AI | 27 | PM2.5 Particle Count | Counts for particles size 0.3 to 2.5 | #/cm3 | Read | |
| AI | 28 | PM4.0 Particle Count | Counts for particles size 0.3 to 4.0 | #/cm3 | Read | |
| AI | 29 | PM10.0 Particle Count | Counts for particles size 0.3 to 10.0 | #/cm3 | Read | |
| AI | 30 | PM Avg Particle Size | Average measured particle size | µm | Read | |
| AI | 31 | CO Reading | CO reading | ppm | Read | |
| AI | 32 | CO Status | CO Status bit flags | Read | 0x01=Sensor communication error (Consult factory); 0x02=Sensor Data Error (Consult factory); 0x04=Sensor Error; 0x08=Sensor not ready (Consult factory); 0x10=Sensor End of Life; 0x20=Calibration Expired; 0x40=Temperature compensation not applied | |
| AI | 33 | O3 Reading | Ozone reading | ppb | Read | |
| AI | 34 | O3 Status | O3 Status bit flags | Read | 0x01=Sensor communication error (Consult factory); 0x02=Sensor Data Error (Consult factory); 0x04=Sensor Error; 0x08=Sensor not ready (Consult factory); 0x10=Temperature compensation not applied; 0x02=Humidity compensation not applied | |
| AI | 35 | User BTN Active State | User button activity | Read | 0=No button press in timeout, 1=Pressed within timeout | |
| AV | 1 | Temp Offset | Temperature offset, ±9 °F (±5 °C) | °F | Write | |
| AV | 2 | Temp Unit | Temperature units for display and BACnet values | Write | 0=°F, 1=°C | |
| AV | 3 | RH Offset | RH offset, ±5 %RH | %RH | Write | |
| AV | 4 | CO2 Offset | CO2 offset, ±250 ppm | ppm | Write | |
| AV | 5 | CO2 autocal enable | CO2 automatic baseline calibration (ABC) enable | Write | 0=disabled, 1=enabled | |
| AV | 6 | CO2 Autocal Baseline | CO2 ABC baseline (default 400) | ppm | Write | |
| AV | 7 | CO2 Autocal Period | CO2 ABC period (default 14) | days | Write | |
| AV | 8 | TVOC scale | TVOC scaling factor (default 1.000 = ethanol) | Write | ||
| AV | 9 | Slider display min | Value shown at slider bottom (display only) | °F / °C | Write | |
| AV | 10 | Slider display max | Value shown at slider top (display only) | °F / °C | Write | |
| AV | 11 | PIR Motion event sensitivity | PIR motion sensitivity (default 80) | Write | ||
| AV | 12 | PIR Occupied delay | Occupied hold time after motion (default 10) | min | Write | |
| AV | 13 | PM clean interval | PM sensor auto-clean interval, 0 = off (default 168) | h | Write | |
| AV | 14 | PM command | PM sensor command | Write | 1=Fan manual clean, 2=PM sensor reset | |
| AV | 15 | Relay source | Which measurement will activate setpoint relay | Write | 0=None, 1=CO2, 2=Humidity, 3=Temp, 4=TVOC µg/m3, 5=PM, 6=Occupancy, 7=Air Quality, 8=CO, 9=Ozone, 10=Ambient Light | |
| AV | 16 | Relay polarity | Relay contact type | Write | 0=N.O., 1=N.C. | |
| AV | 17 | Relay on threshold | Relay on point, % of sensor full scale | % | Write | |
| AV | 18 | Relay off threshold | Relay off point, % of sensor full scale | % | Write | |
| AV | 19 | Relay min on time | Relay minimum on time (default 60) | s | Write | |
| AV | 20 | Relay min off time | Relay minimum off time (default 60) | s | Write | |
| AV | 21 | Display PM size | PM size shown on display | µm | Write | 0=0.3-1.0, 1=0.3-2.5, 2=0.3-4.0, 3=0.3-10.0 |
| AV | 22 | Display center | Value shown in display center | Write | 0=None, 1=Temperature, 2=Humidity, 3=CO2, 4=Air Quality, 5=TVOC µg/m3, 6=TVOC ppb, 7=PM, 8=Temp Setpoint, 9=CO, 10=O3 | |
| AV | 23 | Display upper left | Relay icon on display | Write | 0=None, 1=Relay Icon | |
| AV | 24 | Display upper right | Value shown upper right | Write | 0=None, 1=Temperature, 2=Humidity, 3=CO2, 5=TVOC µg/m3, 6=TVOC ppb, 7=PM, 8=Temp Setpoint, 9=CO, 10=O3 | |
| AV | 25 | Display lower left | Value shown lower left | Write | 0=None, 1=Temperature, 2=Humidity, 3=CO2, 5=TVOC µg/m3, 6=TVOC ppb, 7=PM, 8=Temp Setpoint, 9=CO, 10=O3 | |
| AV | 26 | Display lower right | Value shown lower right | Write | 0=None, 1=Temperature, 2=Humidity, 3=CO2, 5=TVOC µg/m3, 6=TVOC ppb, 7=PM, 8=Temp Setpoint, 9=CO, 10=O3 | |
| AV | 27 | AQ Ring brightness | AQ ring brightness (default 100) | Write | ||
| AV | 28 | Good-Fair | Good/Fair air quality boundary (default 70) | Write | ||
| AV | 29 | Fair-Poor | Fair/Poor air quality boundary (default 40) | Write | ||
| AV | 30 | VOC Mode | VOC sensor mode | Write | 0=Normal operation, 1=Training mode (48 hours) | |
| AV | 31 | Factory reset | Write 1234 to restore factory settings | Write | ||
| AV | 32 | Protocol | Read from the DIP switches | Read | 0=Modbus, 1=BACnet | |
| AV | 33 | MAC address | Read from the DIP switches | Read | ||
| AV | 34 | Baud rate | Read from the DIP switches | Read | 0=9600, 1=19200, 2=38400, 3=57600, 4=76800, 5=115200 | |
| AV | 35 | Data/Parity/Stop | Read from the DIP switches | Read | 0=8N1, 1=8N2, 2=8O1, 3=8E1 | |
| AV | 36 | Analog Source | Analog output source | Write | 0=None, 1=CO2, 2=Humidity, 3=Temperature, 4=VOC, 5=PM, 6=Slider Temp, 7=PID-Temp, 8=PID-CO2, 9=PID-Slider Temp, 10=CO, 11=Ozone, 12=PID-AirQuality, 13=Ambient Light | |
| AV | 37 | Analog V min | Analog output low end, volts | V | Write | |
| AV | 38 | Analog V max | Analog output high end, volts | V | Write | |
| AV | 39 | Analog mA min | Analog output low end, mA | mA | Write | |
| AV | 40 | Analog mA max | Analog output high end, mA | mA | Write | |
| AV | 41 | PID CO2 setpoint | CO2 setpoint for the PID controlled analog output | ppm | Write | |
| AV | 42 | PID Temp Setpoint | Temperature set point for the PID controlled analog output | °F / °C | Write | |
| AV | 43 | PID Kp | Proportional gain PID coefficient | Write | ||
| AV | 44 | PID Ki | Integral gain PID coefficient | Write | ||
| AV | 45 | PID Kd | Derivative gain PID coefficient | Write | ||
| AV | 46 | PID Invert | Reverses the PID error sign | Write | 0=Not Inverted, 1=Inverted | |
| AV | 50 | AQ Enable Temp | Use temperature in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 51 | AQ Enable Humidity | Use humidity in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 52 | AQ Enable CO2 | Use CO2 in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 53 | AQ Enable PM | Use PM in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 54 | AQ Enable VOC | Use VOC in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 55 | Display Lock | Locks the settings menu | Write | 0=Disabled, 1=Enabled | |
| AV | 56 | PIR Display Wake-Up | Wake display on motion | Write | 0=Disabled, 1=Enabled | |
| AV | 57 | Screensaver Timeout | Screensaver delay (default 1) | min | Write | |
| AV | 58 | AQ Enable CO | Use CO in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 59 | AQ Enable Ozone | Use ozone in the air quality index | Write | 0=Disabled, 1=Enabled | |
| AV | 60 | CO Calibration Expiration | Days until CO calibration due | days | Read | |
| AV | 61 | CO Sensor End of Life | Days of CO sensor life left | days | Read | |
| AV | 62 | Ozone Calibration expiration | Days left on ozone calibration | days | Read | |
| AV | 63 | BTN State Hold Time | How long the button state stays active (default 10) | s | Write | |
| AV | 64 | Ozone Sensor end of life | Days of ozone sensor life left | days | Read | |
| AV | 65 | Temp Setpoint | Setpoint used without a slider (default 72) | °F / °C | Read | |
| AV | 66 | AQI PID Setpoint | Air quality index PID setpoint | % | Write | |
| AV | 67 | AQI CO2 Poor quality | Threshold where CO2 quality becomes Poor | ppm | Write | |
| AV | 68 | AQI CO2 Good quality | Threshold where CO2 quality becomes Good | ppm | Write | |
| AV | 69 | AQI VOC Poor quality | Threshold where VOC quality becomes Poor | µg/m3 | Write | |
| AV | 70 | AQI VOC Good quality | Threshold where VOC quality becomes Good | µg/m3 | Write | |
| AV | 71 | AQI PM Poor quality | Threshold where PM quality becomes Poor | µg/m3 | Write | |
| AV | 72 | AQI PM Good quality | Threshold where PM quality becomes Good | µg/m3 | Write | |
| AV | 73 | AQI CO Poor quality | Threshold where CO quality becomes Poor | ppm | Write | |
| AV | 74 | AQI CO Good quality | Threshold where CO quality becomes Good | ppm | Write | |
| AV | 75 | AQI O3 Poor quality | Threshold where Ozone quality becomes Poor | ppb | Write | |
| AV | 76 | AQI O3 Good quality | Threshold where Ozone quality becomes Good | ppb | Write | |
| AV | 77 | AQI Temp Range Low | Low window threshold for good temperature quality | °F / °C | Write | |
| AV | 78 | AQI CO Good quality | High window threshold for good temperature quality | °F / °C | Write | |
| AV | 79 | AQI Temp Range Low | Low window threshold for good humidity quality | %RH | Write | |
| AV | 80 | AQI CO Good quality | High window threshold for good humidity quality | %RH | Write | |
| AV | 81 | Ambient Range | Sets max range for Ambient Light Sensor | fc | Write | 0=300, 1=1000 |
No points match these filters.
Object ID lookup: Senva TotalSense air quality sensor point IDs by name
AI1TemperatureAI2Relative humidityAI3CO2AI4TVOC ug/m3AI5TVOC PPBAI6PM 1.0 ug/m3AI7PM 2.5 ug/m3AI8PM 4.0 ug/m3AI9PM 10.0 ug/m3AI10Air qualityAI11Slider displayAI12OccupancyAI13Ambient lightAI14Relay contacts stateAI15DewpointAI16PressureAI17System statusAI18Temp sensor statusAI19RH sensor statusAI20CO2 sensor statusAI21TVOC sensor statusAI22PM sensor statusAI23Pressure sensor statusAI24PID Output PowerAI25PM0.5 Particle CountAI26PM1.0 Particle CountAI27PM2.5 Particle CountAI28PM4.0 Particle CountAI29PM10.0 Particle CountAI30PM Avg Particle SizeAI31CO ReadingAI32CO StatusAI33O3 ReadingAI34O3 StatusAI35User BTN Active StateAV1Temp OffsetAV2Temp UnitAV3RH OffsetAV4CO2 OffsetAV5CO2 autocal enableAV6CO2 Autocal BaselineAV7CO2 Autocal PeriodAV8TVOC scaleAV9Slider display minAV10Slider display maxAV11PIR Motion event sensitivityAV12PIR Occupied delayAV13PM clean intervalAV14PM commandAV15Relay sourceAV16Relay polarityAV17Relay on thresholdAV18Relay off thresholdAV19Relay min on timeAV20Relay min off timeAV21Display PM sizeAV22Display centerAV23Display upper leftAV24Display upper rightAV25Display lower leftAV26Display lower rightAV27AQ Ring brightnessAV28Good-FairAV29Fair-PoorAV30VOC ModeAV31Factory resetAV32ProtocolAV33MAC addressAV34Baud rateAV35Data/Parity/StopAV36Analog SourceAV37Analog V minAV38Analog V maxAV39Analog mA minAV40Analog mA maxAV41PID CO2 setpointAV42PID Temp SetpointAV43PID KpAV44PID KiAV45PID KdAV46PID InvertAV50AQ Enable TempAV51AQ Enable HumidityAV52AQ Enable CO2AV53AQ Enable PMAV54AQ Enable VOCAV55Display LockAV56PIR Display Wake-UpAV57Screensaver TimeoutAV58AQ Enable COAV59AQ Enable OzoneAV60CO Calibration ExpirationAV61CO Sensor End of LifeAV62Ozone Calibration expirationAV63BTN State Hold TimeAV64Ozone Sensor end of lifeAV65Temp SetpointAV66AQI PID SetpointAV67AQI CO2 Poor qualityAV68AQI CO2 Good qualityAV69AQI VOC Poor qualityAV70AQI VOC Good qualityAV71AQI PM Poor qualityAV72AQI PM Good qualityAV73AQI CO Poor qualityAV74AQI CO Good qualityAV75AQI O3 Poor qualityAV76AQI O3 Good qualityAV77AQI Temp Range LowAV78AQI CO Good qualityAV79AQI Temp Range LowAV80AQI CO Good qualityAV81Ambient Range
Integration notes
- Points from the Readings, Diagnostics and Settings tables of guide 154-0043-0G.
- Objects for sensors a model does not have (CO, ozone, pressure, PIR, light, relay, analog output) are not active on that model.
- The guide reuses names for AV 77-80 ("AQI Temp Range Low", "AQI CO Good quality"); their descriptions say they are the temperature and humidity good-quality window limits. Kept as printed.
- Relay on/off thresholds AV 17/18 are percent of the selected sensor's full scale.
- Protocol, MAC address, baud and parity (AV 32-35) are read from DIP switches and are read-only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TotalSense air quality sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Senva TotalSense air quality sensor (BACnet MS/TP)
How many BACnet points does the Senva TotalSense air quality sensor (BACnet MS/TP) have?
This list has 113 BACnet objects: 35 analog inputs, 78 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Senva TotalSense air quality sensor (BACnet MS/TP) BACnet points are writable?
69 of the 113 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Senva TotalSense air quality sensor (BACnet MS/TP) BACnet documentation?
The source is BACnet Protocol Guide TotalSense Series (154-0043-0G), revision 2025-12-09, published free by Senva at https://www.senvainc.com/catalog/documents/downloadcenter/154-0043-0G%20TotalSense%20BACnet%20Guide.pdf.
What are the minimum BACnet points to integrate the Senva TotalSense air quality sensor (BACnet MS/TP)?
Start with AI 1 Temperature (Space temperature (units per AV 2)); AI 2 Relative humidity (Space RH); AI 3 CO2 (Space CO2, ppm); AI 7 PM 2.5 ug/m3 (PM2.5, µg/m3); AI 4 TVOC ug/m3 (TVOC, µg/m3); AI 10 Air quality (0 Good, 1 Fair, 2 Poor); AI 12 Occupancy (PIR occupancy (PIR models)); AI 17 System status (System fault bit flags).
How do I check these points on the real TotalSense air quality sensor (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Senva BACnet points lists
- Room air quality sensor (temperature / RH / CO2)
Senva AQ Series wall air quality sensor (BACnet MS/TP)
Senva AQ Series (AQW) wall-mount sensors measuring temperature, humidity and/or CO2, with optional set point, push button and relay, using BACnet MS/TP.
Also known as: AQ Series, AQW, AQW-XXXXXXX, Senva AQ CO2 sensor, Senva AQ temperature humidity CO2 - Power and energy meter (submeter)
Senva EMX energy meter (BACnet MS/TP and BACnet IP)
Senva EMX, EMX-L (BACnet MS/TP) and EMX-IP (BACnet IP) three-phase energy meters.
Also known as: EMX, EMX-L, EMX-IP, Senva EMX power meter, Senva EMX submeter - Gas detector / sensor (toxic gas, dual sensor)
Senva TG Series toxic gas detector (BACnet MS/TP)
Senva TG series toxic gas detectors (TGX-BXX-XX) with one or two gas sensors, optional thermistor, fan and alarm relays and buzzer, using BACnet MS/TP.
Also known as: TG, TGX-BXX-XX, Senva TG toxic gas, Senva TG CO NO2 detector - Gas detector / sensor (toxic gas, dual sensor)
Senva TGR Series recessed toxic gas sensor (BACnet MS/TP)
Senva TGR series recessed low-voltage toxic gas sensors (TGR-XXX) with one or two gas sensors, using BACnet MS/TP.
Also known as: TGR, TGR-XXX, Senva TGR toxic gas, Senva TGR recessed gas detector
Source: BACnet Protocol Guide TotalSense Series · 154-0043-0G · rev. 2025-12-09. Object names, instances and units are reproduced as published; descriptions are our own.