Gas detector / sensor (toxic gas, dual sensor) · BACnet points list

Senva TG Series toxic gas detector (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The TG is a Senva toxic gas detector with BACnet MS/TP. Each measurement (temperature, gas sensor 1 and 2, supply voltage) has a primary Analog Input plus Smoothed, Minimum, Maximum and Average objects. Analog Values hold the warning and alarm setpoints, hysteresis, sensor life and RS-485 settings; commandable Binary Outputs drive the fan relay, alarm relay and buzzer, and MSV 170 reports the Normal / Warning / Alarm / Extended Alarm state.

This page lists 61 BACnet objects for the Senva TG Series toxic gas detector (BACnet MS/TP) — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Senva’s own free documentation, linked below.

Manufacturer
Senva
Model
TG Series toxic gas detector (BACnet MS/TP)
Equipment
Gas detector / sensor (toxic gas, dual sensor)
Equipment type
Thermostats, sensors & meters
BACnet objects
61 (50 writable)
Transport
BACnet MS/TP
Firmware
2.0.0 (PICS 2/7/2020)
Also known as
TG, TGX-BXX-XX, Senva TG toxic gas, Senva TG CO NO2 detector
Source document
BACnet Protocol Guide TG · 154-0035-0B · rev. 2021-03-12
Download CSV 61 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Senva’s current documentation and the live device before use. Not official Senva information. Terms of use.

BMS integration notes: Senva TG Series toxic gas detector (BACnet MS/TP)

Integration in brief

Connect to an active MS/TP network and let the TG auto-detect baud, protocol and address, then read the gas readings and MSV 170. The relays and buzzer run automatically from the setpoints; the BMS can override them through the BO priority array.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 210Fan RelayFan relay; BMS can override (commandable)Command
AI 320Sensor 1 Gas ConcentrationSensor 1 gas readingWrite
AI 330Sensor 2 Gas ConcentrationSensor 2 gas readingWrite
MV 170System StateNormal, Warning, Alarm or Extended AlarmRead
BO 230Alarm RelayAlarm relay stateCommand
AV 158Sensor 1 Sensor LifeDays of sensor 1 life leftRead

Enable & remote start

The device writes the relays at priority 16 from the system state; commands at priorities 1-5 override immediately, 7-15 respect minimum on/off times. Priority 6 is reserved.

Network setup

Watch out for

Senva TG Series toxic gas detector (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

61 of 61 shown
Type
Multi-stateOther
Access
Show
Senva TG Series toxic gas detector (BACnet MS/TP) BACnet Points List
DescriptionStates
AI310TemperatureExternal air temperature (thermistor models); write 0 resets stats°F / °CWrite
AI312SmoothedTemperature, smoothed°F / °CRead
AI314MinimumTemperature, lowest since reset°F / °CWrite
AI316MaximumTemperature, highest since reset°F / °CWrite
AI318AverageTemperature, average since reset°F / °CWrite
AImin320Sensor 1 Gas ConcentrationSensor 1 gas concentrationppmWrite
AI322SmoothedSensor 1 gas, smoothedppmRead
AI324MinimumSensor 1 gas, lowest since resetppmWrite
AI326MaximumSensor 1 gas, highest since resetppmWrite
AI328AverageSensor 1 gas, average since resetppmWrite
AImin330Sensor 2 Gas ConcentrationSensor 2 gas concentrationppmWrite
AI332SmoothedSensor 2 gas, smoothedppmRead
AI334MinimumSensor 2 gas, lowest since resetppmWrite
AI336MaximumSensor 2 gas, highest since resetppmWrite
AI338AverageSensor 2 gas, average since resetppmWrite
AI380Power Supply VoltageInternal supply voltage (1-2 V below external)VWrite
AI382SmoothedSupply voltage, smoothedVRead
AI384MinimumSupply voltage, lowest since resetVWrite
AI386MaximumSupply voltage, highest since resetVWrite
AI388AverageSupply voltage, average since resetVWrite
AV103Reset CountLifetime count of firmware resetsRead
AV104Up TimeTime since last resetsRead
AV123MAC AddressMS/TP address, 0-254; writing turns Auto MAC offWrite
AV124RS485 Baud RateRS-485 baud rate, 1200-460800; writing turns Auto Baud offWrite
AV130Temperature Calibration OffsetTemperature calibration offsetWrite
AV134Smoothed Temperature Response TimeSmoothed temperature response time (default 30)sWrite
AV135Gas 1 Response TimeGas 1 smoothing time (default 10)sWrite
AV136Gas 2 Response TimeGas 2 smoothing time (default 10)sWrite
AV150Sensor 1 Warning SetpointSensor 1 gas level for Warning stateppmWrite
AV152Sensor 1 Alarm SetpointSensor 1 gas level for Alarm stateppmWrite
AV154Sensor 1 HysteresisSensor 1 hysteresis (default 0)ppmWrite
AV156Sensor 1 AdjustmentSensor 1 scale adjustment (default 100 %)%Write
AVmin158Sensor 1 Sensor LifeSensor 1 remaining life (starts at 1825)daysRead
AV160Sensor 2 Warning SetpointSensor 2 gas level for Warning stateppmWrite
AV162Sensor 2 Alarm SetpointSensor 2 gas level for Alarm stateppmWrite
AV164Sensor 2 HysteresisSensor 2 hysteresis (default 0)ppmWrite
AV166Sensor 2 AdjustmentSensor 2 scale adjustment (default 100 %)%Write
AV168Sensor 2 Sensor LifeSensor 2 remaining life (starts at 1825)daysRead
AV190System Configuration ResetWrite 9699690 to reset configuration to factory (reads 0)Write
AV192Statistics ResetWrite 4765089 to reset all statistics (reads 0)Write
AV198ReservedReservedRead
AV212Fan Maximum Off TimeFan relay maximum off time, 0 = ignored (default 0)sWrite
AV232Alarm Maximum Off TimeAlarm relay maximum off time, 0 = ignored (default 0)sWrite
AV252Buzzer DelayBuzzer delay after Alarm state (default 1800)sWrite
BOmin210Fan RelayFan relay; on automatically at Warning or aboveCommand
BOmin230Alarm RelayAlarm relay; on automatically at Alarm or aboveCommand
BO250Alarm BuzzerAlarm buzzer; on at Extended AlarmCommand
BV111Identify DeviceIdentify mode: LEDs on, MAC address blinksWrite
BV112Auto ProtocolAutomatic protocol detection (default Active)Write
BV113Auto MAC AddressAutomatic MAC address selection (default Active)Write
BV114Auto Baud RateAutomatic baud detection (default Active)Write
BV115Auto ParityAutomatic parity detection (default Active)Write
BV118Buzzer OverrideForces the buzzer off (persists)Write
BV195Auto Reset StatisticsReading a min/max/average also resets it (default Inactive)Write
BV196Sensor 1 Pulse StatusSensor 1 electrochemical pulse health checkWrite
BV197Sensor 2 Pulse StatusSensor 2 electrochemical pulse health checkWrite
MV122RS485 ProtocolRS-485 protocol selection (default Auto)Write1=Auto Protocol, 2=BACnet, 3=Modbus RTU, 4=Modbus ASCII, 5=BACnet and Modbus RTU, 6=BACnet and Modbus ASCII, 7=Modbus RTU and ASCII, 8=Any Protocol
MV126RS485 ParityRS-485 parity (default Auto)Write1=Auto, 2=No Parity, 3=Odd Parity, 4=Even Parity
MV133Temperature UnitsTemperature units (default °F)Write1=Degrees Fahrenheit, 2=Degrees Celsius
MVmin170System StateSystem alarm stateRead1=Normal, 2=Warning, 3=Alarm, 4=Extended Alarm
FILE25000User ConfigurationCopy of the device configuration for supportRead
Object ID lookup: Senva TG Series toxic gas detector point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TG Series toxic gas detector (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Senva TG Series toxic gas detector (BACnet MS/TP)

How many BACnet points does the Senva TG Series toxic gas detector (BACnet MS/TP) have?

This list has 61 BACnet objects: 20 analog inputs, 24 analog values, 3 binary outputs, 9 binary values, 1 file, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Senva TG Series toxic gas detector (BACnet MS/TP) BACnet points are writable?

50 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Senva TG Series toxic gas detector (BACnet MS/TP) BACnet documentation?

The source is BACnet Protocol Guide TG (154-0035-0B), revision 2021-03-12, published free by Senva at https://www.senvainc.com/catalog/documents/downloadcenter/TG%20BACnet%20Protocol%20Guide%20154-0035-0B.pdf.

What are the minimum BACnet points to integrate the Senva TG Series toxic gas detector (BACnet MS/TP)?

Start with BO 210 Fan Relay (Fan relay; BMS can override (commandable)); AI 320 Sensor 1 Gas Concentration (Sensor 1 gas reading); AI 330 Sensor 2 Gas Concentration (Sensor 2 gas reading); MV 170 System State (Normal, Warning, Alarm or Extended Alarm); BO 230 Alarm Relay (Alarm relay state); AV 158 Sensor 1 Sensor Life (Days of sensor 1 life left).

How do I enable BMS control of the Senva TG Series toxic gas detector (BACnet MS/TP)?

The device writes the relays at priority 16 from the system state; commands at priorities 1-5 override immediately, 7-15 respect minimum on/off times. Priority 6 is reserved.

How do I check these points on the real TG Series toxic gas detector (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Senva BACnet points lists

Source: BACnet Protocol Guide TG · 154-0035-0B · rev. 2021-03-12. Object names, instances and units are reproduced as published; descriptions are our own.