Room air quality sensor (temperature / RH / CO2) · BACnet points list

Senva AQ Series wall air quality sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The AQ Series is a Senva wall sensor with native BACnet MS/TP. For temperature, RH, dew point and CO2 it gives a smoothed value, a raw value and resettable min/max Analog Inputs, plus the occupant set point. Analog Values hold calibration, smoothing, CO2 auto-cal, set point range and internal relay settings; a commandable Binary Output drives the relay.

This page lists 62 BACnet objects for the Senva AQ Series wall air quality sensor (BACnet MS/TP) — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Senva’s own free documentation, linked below.

Manufacturer
Senva
Model
AQ Series wall air quality sensor (BACnet MS/TP)
Equipment
Room air quality sensor (temperature / RH / CO2)
Equipment type
Thermostats, sensors & meters
BACnet objects
62 (50 writable)
Transport
BACnet MS/TP
Firmware
1.0.5 (PICS Feb 12, 2016)
Also known as
AQ Series, AQW, AQW-XXXXXXX, Senva AQ CO2 sensor, Senva AQ temperature humidity CO2
Source document
BACnet Protocol Guide AQ Series · 154-0012-0E · rev. 2016-02-12
Download CSV 62 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Senva’s current documentation and the live device before use. Not official Senva information. Terms of use.

BMS integration notes: Senva AQ Series wall air quality sensor (BACnet MS/TP)

Integration in brief

Set baud and MAC with the auto-configuration wizard or Setup Menu (BACnet stays off until both are set), choose BACnet temperature units with MSV 2, then read the smoothed temperature, RH and CO2. The BMS can command the relay through BO 0 when the internal relay program is disabled.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Relay OutputRelay command (commandable)Command
AI 0TemperatureSpace temperatureRead
AI 4Relative HumiditySpace RH (humidity models)Read
AI 12CO2 ConcentrationSpace CO2, ppm (CO2 models)Read
AI 16User Set PointOccupant set pointRead
BI 0User Push ButtonOccupant push buttonRead

Enable & remote start

The internal relay program writes BO 0 at the priority in AV 25 (default 14) unless MSV 4 is set to Disabled; BMS commands at a higher priority win.

Network setup

Watch out for

Senva AQ Series wall air quality sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

62 of 62 shown
Type
Multi-state
Access
Show
Senva AQ Series wall air quality sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TemperatureSmoothed temperature°F / °CRead
AI1Temperature (unsmoothed)Latest calibrated temperature reading°F / °CRead
AI2Minimum TemperatureLowest temperature since reset; write to reset°F / °CWrite
AI3Maximum TemperatureHighest temperature since reset; write to reset°F / °CWrite
AImin4Relative HumiditySmoothed relative humidity (humidity models)%RHRead
AI5Relative Humidity (unsmoothed)Latest calibrated relative humidity reading (humidity models)%RHRead
AI6Minimum Relative HumidityLowest relative humidity since reset; write to reset%RHWrite
AI7Maximum Relative HumidityHighest relative humidity since reset; write to reset%RHWrite
AI8Dew Point TemperatureSmoothed dew point temperature (humidity models)°F / °CRead
AI9Dew Point Temperature (unsmoothed)Latest calibrated dew point temperature reading (humidity models)°F / °CRead
AI10Minimum Dew Point TemperatureLowest dew point temperature since reset; write to reset°F / °CWrite
AI11Maximum Dew Point TemperatureHighest dew point temperature since reset; write to reset°F / °CWrite
AImin12CO2 ConcentrationSmoothed CO2 concentration (CO2 models)ppmRead
AI13CO2 Concentration (unsmoothed)Latest calibrated CO2 concentration reading (CO2 models)ppmRead
AI14Minimum CO2 ConcentrationLowest CO2 concentration since reset; write to resetppmWrite
AI15Maximum CO2 ConcentrationHighest CO2 concentration since reset; write to resetppmWrite
AImin16User Set PointOccupant set point from slider or buttonsper MSV 3Read
AI17Minimum User Set PointLowest set point since reset; write to resetWrite
AI18Maximum User Set PointHighest set point since reset; write to resetWrite
AV0MAC AddressMS/TP address, 0-127 (not configured by default)Write
AV1Device UptimeTime since last restartsRead
AV2Device Restart CountNumber of restartsRead
AV3Display ContrastLCD contrast, 0-100 % (default 50)%Write
AV4Display Rotate TimeSeconds per value in display rotation (default 10)sWrite
AV5Temperature Calibration SlopeTemperature calibration gain (default 1.0)Write
AV6Temperature Calibration OffsetTemperature calibration offset (default 0)°F / °CWrite
AV7Temperature Response TimeTemperature smoothing time (default 30)sWrite
AV8Relative Humidity Calibration SlopeRH calibration gain (default 1.0)Write
AV9Relative Humidity Calibration OffsetRH calibration offset (default 0)%RHWrite
AV10Relative Humidity Response TimeRH smoothing time (default 30)sWrite
AV11Dew Point Calibration SlopeDew point calibration gain (default 1.0)Write
AV12Dew Point Calibration OffsetDew point calibration offset (default 0)°F / °CWrite
AV13Dew Point Response TimeDew point smoothing time (default 30)sWrite
AV14CO2 Calibration SlopeCO2 calibration gain (default 1.0)Write
AV15CO2 Calibration OffsetCO2 calibration offset (default 0)ppmWrite
AV16CO2 Response TimeCO2 smoothing time (default 30)sWrite
AV17CO2 Auto Calibration PeriodCO2 auto-cal period, 0-60 days, 0 = off (default 14)daysWrite
AV18CO2 Auto Calibration TargetCO2 auto-cal target (default 400)ppmWrite
AV19CO2 Auto Calibration WindowCO2 auto-cal window (default 200)ppmWrite
AV20User Set Point Minimum ValueBottom of set point range (default 50 °F)per MSV 3Write
AV21User Set Point Maximum ValueTop of set point range (default 95 °F)per MSV 3Write
AV22User Set Point IncrementSet point step size (default 1.0)per MSV 3Write
AV23Internal Relay Program ThresholdRelay trip threshold (default 800); units follow MSV 4Write
AV24Internal Relay Program HysteresisRelay hysteresis (default 100); units follow MSV 4Write
AV25Internal Relay Program PriorityPriority the internal relay logic writes BO 0 at, 6-16 (default 14)Write
AV26Temperature Override ValueDisplay override for temperature; NULL clears°F / °CWrite
AV27Relative Humidity Override ValueDisplay override for RH; NULL clears%RHWrite
AV28Dew Point Temperature Override ValueDisplay override for dew point; NULL clears°F / °CWrite
AV29CO2 Concentration Override ValueDisplay override for CO2; NULL clearsppmWrite
BImin0User Push ButtonPush button state (if fitted); read by the controllerRead
BOmin0Relay OutputRelay command (commandable; internal program writes at AV 25 priority)Command
BV0Identify DeviceShows the MAC address on the display while activeWrite
BV1Temperature Override EnableDisplay shows AV 26 instead of AI 0Write
BV2Relative Humidity Override EnableDisplay shows AV 27 instead of AI 4Write
BV3Dew Point Temperature Override EnableDisplay shows AV 28 instead of AI 8Write
BV4CO2 Concentration Override EnableDisplay shows AV 29 instead of AI 12Write
MV0Display SelectionValues shown on the display (default User Selection)Write1=Display Off, 2=User Selection, 3=Temperature Only, 4=Relative Humidity Only, 5=Temperature and Relative Humidity, 6=CO2 Only, 7=Temperature And CO2, 8=Relative Humidity and CO2, 9=Temperature, Relative Humidity, and CO2, 10=Dew Point Only, 11=Set Point Only
MV1Display Temperature UnitsTemperature units on the displayWrite1=User Selection, 2=Degrees Fahrenheit, 3=Degrees Celsius
MV2BACnet Temperature UnitsTemperature units for BACnet values (default °F)Write1=Degrees Fahrenheit, 2=Degrees Celsius
MV3User Set Point UnitsUnits shown with the set point (default °F)Write1=Disabled, 2=No Units (value only), 3=Degrees Fahrenheit, 4=Degrees Celsius, 5=Relative Humidity (%RH), 6=Parts Per Million (ppm), 7=Pounds per Square Inch (psi), 8=Kilopascals (kPa), 9=Inches of Water Column ("WC)
MV4Internal Relay Program SourceValue the internal relay logic compares (default CO2)Write1=Disabled, 2=Temperature, 3=Temperature (unsmoothed), 4=Relative Humidity, 5=Relative Humidity (unsmoothed), 6=Dew Point Temperature, 7=Dew Point Temperature (unsmoothed), 8=CO2 Concentration, 9=CO2 Concentration (unsmoothed), 10=User Set Point
MV5Internal Relay Program PolarityRelay logic direction (default Active High)Write1=Active High, 2=Active Low
Object ID lookup: Senva AQ Series wall air quality sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AQ Series wall air quality sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Senva AQ Series wall air quality sensor (BACnet MS/TP)

How many BACnet points does the Senva AQ Series wall air quality sensor (BACnet MS/TP) have?

This list has 62 BACnet objects: 19 analog inputs, 30 analog values, 1 binary input, 1 binary output, 5 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Senva AQ Series wall air quality sensor (BACnet MS/TP) BACnet points are writable?

50 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Senva AQ Series wall air quality sensor (BACnet MS/TP) BACnet documentation?

The source is BACnet Protocol Guide AQ Series (154-0012-0E), revision 2016-02-12, published free by Senva at https://www.senvainc.com/catalog/documents/downloadcenter/AQ%20Series%20BACnet%20Protocol%20Guide%20-%20Version%201.0.5.pdf.

What are the minimum BACnet points to integrate the Senva AQ Series wall air quality sensor (BACnet MS/TP)?

Start with BO 0 Relay Output (Relay command (commandable)); AI 0 Temperature (Space temperature); AI 4 Relative Humidity (Space RH (humidity models)); AI 12 CO2 Concentration (Space CO2, ppm (CO2 models)); AI 16 User Set Point (Occupant set point); BI 0 User Push Button (Occupant push button).

How do I enable BMS control of the Senva AQ Series wall air quality sensor (BACnet MS/TP)?

The internal relay program writes BO 0 at the priority in AV 25 (default 14) unless MSV 4 is set to Disabled; BMS commands at a higher priority win.

How do I check these points on the real AQ Series wall air quality sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Senva BACnet points lists

Source: BACnet Protocol Guide AQ Series · 154-0012-0E · rev. 2016-02-12. Object names, instances and units are reproduced as published; descriptions are our own.