Gas detector / sensor (toxic gas, dual sensor) · BACnet points list

Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The TGR is a Senva recessed toxic gas sensor with BACnet MS/TP. Analog Inputs give each sensor's reading, 5/15/60-minute time-weighted averages, alarm state, status bits and calibration/life days, plus relay and device status. Analog Values hold gas type and span, warning/alarm setpoints and hysteresis, fire-safety TWA and IDLH setpoints, relay timing and the RS-485 settings.

This page lists 59 BACnet objects for the Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Senva’s own free documentation, linked below.

Manufacturer
Senva
Model
TGR Series recessed toxic gas sensor (BACnet MS/TP)
Equipment
Gas detector / sensor (toxic gas, dual sensor)
Equipment type
Thermostats, sensors & meters
BACnet objects
59 (26 writable)
Transport
BACnet MS/TP
Firmware
VSBHP 14.10, application 1.1.x (PICS 5/13/2021)
Also known as
TGR, TGR-XXX, Senva TGR toxic gas, Senva TGR recessed gas detector
Source document
BACnet Protocol Guide TGR Series · 154-0048-0A · rev. 2023 (0A)
Download CSV 59 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Senva’s current documentation and the live device before use. Not official Senva information. Terms of use.

BMS integration notes: Senva TGR Series recessed toxic gas sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP address and baud, then read each sensor's reading and alarm state and the overall air quality state. Warning and alarm setpoints are written once; AV 37 silences the alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Sensor1ReadingsSensor 1 gas readingRead
AI 9Sensor2ReadingSensor 2 gas readingRead
AI 20AirQualityStateOverall state: 0 Normal to 4 Extended AlarmRead
AI 18AlarmRelayStateAlarm relay stateRead
AI 17TroubleRelayStateTrouble relay stateRead
AI 19SystemStatusDevice error bitsRead

Network setup

Watch out for

Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

59 of 59 shown
Type
Access
Show
Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Sensor1ReadingsSensor 1 instantaneous readingRead
AI2Sensor1TWA5ReadingSensor 1 5-minute time-weighted averageRead
AI3Sensor1TWA15ReadingSensor 1 15-minute time-weighted averageRead
AI4Sensor1TWA60ReadingSensor 1 60-minute time-weighted averageRead
AI5Sensor1AirQualitySensor 1 alarm stateRead0=Normal, 1=Trouble, 2=Warning, 3=Alarm, 4=Extended Alarm
AI6Sensor1StatusSensor 1 status bitsReadBit flags: 1=Sensor Never Present, 2=EOL, 4=Pulse Failure, 8=Init failure, 16=No Sensor Present, 32=Other, 64=Sensor detected, 128=Sensor Ready
AI7Sensor1CalDaysRemainingDays until sensor 1 needs recalibrationdaysRead
AI8Sensor1LifeDaysRemainingDays of sensor 1 life leftdaysRead
AImin9Sensor2ReadingSensor 2 instantaneous readingRead
AI10Sensor2TWA5ReadingSensor 2 5-minute time-weighted averageRead
AI11Sensor2TWA15ReadingSensor 2 15-minute time-weighted averageRead
AI12Sensor2TWA60ReadingSensor 2 60-minute time-weighted averageRead
AI13Sensor2AirQualitySensor 2 alarm stateRead0=Normal, 1=Trouble, 2=Warning, 3=Alarm, 4=Extended Alarm
AI14Sensor2StatusSensor 2 status bitsReadBit flags: 1=Sensor Never Present, 2=EOL, 4=Pulse Failure, 8=Init failure, 16=No Sensor Present, 32=Other, 64=Sensor detected, 128=Sensor Ready
AI15Sensor2CalDaysRemainingDays until sensor 2 needs recalibrationdaysRead
AI16Sensor2LifeDaysRemainingDays of sensor 2 life leftdaysRead
AImin17TroubleRelayStateTrouble relay stateRead
AImin18AlarmRelayStateAlarm relay stateRead
AImin19SystemStatusDevice status bitsReadBit flags: 1=I2C error, 2=CRC error, 4=Write Error, 8=Using Factory Defaults, 16=Sensor error, 32=sensor warning, 64=nfc error, 128=assert
AImin20AirQualityStateOverall device alarm stateRead0=Normal, 1=Trouble, 2=Warning, 3=Alarm, 4=Extended Alarm
AV1Sensor1GasTypeSensor 1 gas typeRead
AV2Sensor1SpanMaxHighest value sensor 1 can measureRead
AV3Sensor1SpanMinLowest value sensor 1 can measureRead
AV4Sensor1WarningSensor 1 warning relay setpointWrite
AV5Sensor1AlarmSensor 1 alarm relay setpointWrite
AV6Sensor1HysteresisSensor 1 drop below setpoint before alarm clearsWrite
AV7Sensor1TWA5SPSensor 1 5-min TWA alarm setpoint (fire safety mode)Read
AV8Sensor1TWA15SPSensor 1 15-min TWA alarm setpoint (fire safety mode)Read
AV9Sensor1TWA60SPSensor 1 60-min TWA alarm setpoint (fire safety mode)Read
AV10Sensor1FactoryResetResets sensor 1 calibration to factoryRead
AV11Sensor2GasTypeSensor 2 gas typeRead
AV12Sensor2SpanMaxHighest value sensor 2 can measureRead
AV13Sensor2SpanMinLowest value sensor 2 can measureRead
AV14Sensor2WarningSensor 2 warning relay setpointWrite
AV15Sensor2AlarmSensor 2 alarm relay setpointWrite
AV16Sensor2HysteresisSensor 2 drop below setpoint before alarm clearsWrite
AV17Sensor2TWA5SPSensor 2 5-min TWA alarm setpoint (fire safety mode)Read
AV18Sensor2TWA15SPSensor 2 15-min TWA alarm setpoint (fire safety mode)Read
AV19Sensor2TWA60SPSensor 2 60-min TWA alarm setpoint (fire safety mode)Read
AV20Sensor2CalResetResets sensor 2 calibration to factoryWrite
AV21CO2Offset*CO2 offset (CO2 sensor only)ppmWrite
AV22CO2AutoCal*CO2 auto-calibration on/off (CO2 sensor only)Write
AV23CO2AutoCalBaseline*CO2 auto-calibration baseline (CO2 sensor only)ppmWrite
AV24CO2AutoCalPeriod*CO2 auto-calibration period (CO2 sensor only)daysWrite
AV25TroubleRelayPolarityTrouble relay active polarityWrite
AV26TroubleRelayOnTimeTrouble relay minimum off timeWrite
AV27TroubleRelayOffTimeTrouble relay maximum off timeWrite
AV28AlarmRelayPolarityAlarm relay active polarityWrite
AV29AlarmRelayOnTimeAlarm relay minimum off timeWrite
AV30AlarmRelayOffTimeAlarm relay maximum off timeWrite
AV31FactoryResetRestores factory defaultsWrite
AV32ProtocolCommunication protocol in useWrite
AV33MACAddressBACnet MS/TP addressWrite
AV35BaudRateBaud rateWrite
AV36Data/Parity/StopData bits, parity and stop bitsWrite
AV37SilenceEnableSilences the device alarmWrite
AV38FireControlModeEnabledEnables fire control (fire safety) modeWrite
AV39Sensor 1 IDLH SetpointSensor 1 IDLH level; instant alarm in fire safety modeWrite
AV40Sensor 2 IDLH SetpointSensor 2 IDLH level; instant alarm in fire safety modeWrite
Object ID lookup: Senva TGR Series recessed toxic gas sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TGR Series recessed toxic gas sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Senva TGR Series recessed toxic gas sensor (BACnet MS/TP)

How many BACnet points does the Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) have?

This list has 59 BACnet objects: 20 analog inputs, 39 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) BACnet points are writable?

26 of the 59 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Senva TGR Series recessed toxic gas sensor (BACnet MS/TP) BACnet documentation?

The source is BACnet Protocol Guide TGR Series (154-0048-0A), revision 2023 (0A), published free by Senva at https://www.senvainc.com/catalog/documents/downloadcenter/TGR%20BACnet%20Guide.pdf.

What are the minimum BACnet points to integrate the Senva TGR Series recessed toxic gas sensor (BACnet MS/TP)?

Start with AI 1 Sensor1Readings (Sensor 1 gas reading); AI 9 Sensor2Reading (Sensor 2 gas reading); AI 20 AirQualityState (Overall state: 0 Normal to 4 Extended Alarm); AI 18 AlarmRelayState (Alarm relay state); AI 17 TroubleRelayState (Trouble relay state); AI 19 SystemStatus (Device error bits).

How do I check these points on the real TGR Series recessed toxic gas sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Senva BACnet points lists

Source: BACnet Protocol Guide TGR Series · 154-0048-0A · rev. 2023 (0A). Object names, instances and units are reproduced as published; descriptions are our own.