Electromagnetic flow / BTU meter · BACnet points list

ONICON FT-3500 insertion electromagnetic flow / BTU meter BACnet points list

Updated 12 November 2026

Short answer

The FT-3500 is an insertion electromagnetic flow meter that can also calculate thermal energy from supply and return temperatures. Over BACnet MS/TP or BACnet IP it reports energy and flow rates, temperatures, forward and reverse totals with year-to-date, previous-year, daily and 30-day totals, run hours, aux pulse totals, a mode flag and an 18-state error code.

This page lists 37 BACnet objects for the ONICON FT-3500 insertion electromagnetic flow / BTU meter — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ONICON’s own free documentation, linked below.

Manufacturer
ONICON
Model
FT-3500 insertion electromagnetic flow / BTU meter
Equipment
Electromagnetic flow / BTU meter
Equipment type
Thermostats, sensors & meters
BACnet objects
37 (7 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
1.8.0 (application 2.6.0)
Default device instance
57017
Also known as
FT-3500, FT-3500-1, FT-3500-2, FT3500, ONICON FT-3500
Source document
FT-3500 Insertion Electromagnetic Flow Meter Manual · DOC-0006324 · rev. Rev. H (PICS dated 01/03/2023)
Download CSV 37 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ONICON’s current documentation and the live device before use. Not official ONICON information. Terms of use.

BMS integration notes: ONICON FT-3500 insertion electromagnetic flow / BTU meter

Integration in brief

Read AI 2 for flow and, on energy meters, AI 1 plus the supply and return temperatures. Trend AV 1 or AV 2 for totals; use the YTD and previous-year AVs for billing reports. Map MSV 0 for meter faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2Volume RateFlow rateRead
AI 1Energy RateEnergy rate (BTU configuration)Read
AV 1Mode 1 Energy TotalMode 1 (forward) energy totalRead
AV 2Mode 1 Volume TotalMode 1 (forward) volume totalRead
AI 3Supply TemperatureSupply temperatureRead
AI 4Return TemperatureReturn temperatureRead
BI 0Mode IndicationMode 1 = forward cooling, mode 2 = reverse heatingRead
MV 0ErrorsMeter error state, 1 = NormalRead

Network setup

Watch out for

ONICON FT-3500 insertion electromagnetic flow / BTU meter BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

37 of 37 shown
Type
BinaryMulti-state
Access
Show
ONICON FT-3500 insertion electromagnetic flow / BTU meter BACnet Points List
DescriptionStates
AImin1Energy RateThermal energy rateBTU/h, kW or tonsRead
AImin2Volume RateFlow rateL/s, L/min, L/h, m³/h, GPM, CFS or CFMRead
AImin3Supply TemperatureSupply water temperature°C or °FRead
AImin4Return TemperatureReturn water temperature°C or °FRead
AI5Delta TemperatureSupply-return temperature difference°C or °FRead
AVmin1Mode 1 Energy TotalForward / cooling energy totalBTU, ton-h or kWhRead
AVmin2Mode 1 Volume TotalForward volume totalliters, m³, gallons or ft³Read
AV3Mode 2 Energy TotalReverse / heating energy totalBTU, ton-h or kWhRead
AV4Mode 2 Volume TotalReverse volume totalliters, m³, gallons or ft³Read
AV5Aux Input 1 TotalAuxiliary pulse input 1 total; write 0 to resetcountsCommand
AV6Aux Input 2 TotalAuxiliary pulse input 2 total; write 0 to resetcountsCommand
AV7Aux Input 3 TotalAuxiliary pulse input 3 total; write 0 to resetcountsCommand
AV8Total Run HrTotal run hourshRead
AV9Run Hr Mode 1Run hours in mode 1hRead
AV10Run Hr Mode 2Run hours in mode 2hRead
AV11Mode 1 YTD Energy TotalMode 1 energy total, year-to-dateBTU, ton-h or kWhRead
AV12Mode 1 PrevYr Energy TotalMode 1 energy total, previous yearBTU, ton-h or kWhRead
AV13Mode 1 User Energy TotalMode 1 energy total, user-defined; write 0 to resetBTU, ton-h or kWhCommand
AV14Mode 1 Yesterday Energy TotalMode 1 energy total, yesterdayBTU, ton-h or kWhRead
AV15Mode 1 Last 30 Days Energy TotalMode 1 energy total, last 30 daysBTU, ton-h or kWhRead
AV16Mode 1 YTD Volume TotalMode 1 volume total, year-to-dateliters, m³, gallons or ft³Read
AV17Mode 1 PrevYr Volume TotalMode 1 volume total, previous yearliters, m³, gallons or ft³Read
AV18Mode 1 User Volume TotalMode 1 volume total, user-defined; write 0 to resetliters, m³, gallons or ft³Command
AV19Mode 1 Yesterday Volume TotalMode 1 volume total, yesterdayliters, m³, gallons or ft³Read
AV20Mode 1 Last 30 Days Volume TotalMode 1 volume total, last 30 daysliters, m³, gallons or ft³Read
AV21Mode 2 YTD Energy TotalMode 2 energy total, year-to-dateBTU, ton-h or kWhRead
AV22Mode 2 PrevYr Energy TotalMode 2 energy total, previous yearBTU, ton-h or kWhRead
AV23Mode 2 User Energy TotalMode 2 energy total, user-defined; write 0 to resetBTU, ton-h or kWhCommand
AV24Mode 2 Yesterday Energy TotalMode 2 energy total, yesterdayBTU, ton-h or kWhRead
AV25Mode 2 Last 30 Days Energy TotalMode 2 energy total, last 30 daysBTU, ton-h or kWhRead
AV26Mode 2 YTD Volume TotalMode 2 volume total, year-to-dateliters, m³, gallons or ft³Read
AV27Mode 2 PrevYr Volume TotalMode 2 volume total, previous yearliters, m³, gallons or ft³Read
AV28Mode 2 User Volume TotalMode 2 volume total, user-defined; write 0 to resetliters, m³, gallons or ft³Command
AV29Mode 2 Yesterday Volume TotalMode 2 volume total, yesterdayliters, m³, gallons or ft³Read
AV30Mode 2 Last 30 Days Volume TotalMode 2 volume total, last 30 daysliters, m³, gallons or ft³Read
BImin0Mode IndicationCurrent operating mode, channel 1ReadMode 1 = Forward Cooling, Mode 2 = Reverse Heating
MVmin0ErrorsHardware or functional fault stateRead1=Normal, 2=EEPROMFail, 3=I2CFail, 4=VelTblCrrpt, 5=PipCfgMssng, 6=GrnTtlCrrpt, 7=YrTtlCrrpt, 8=ElecDiffOOR, 9=Elec0 D/C, 10=Elec1 D/C, 11=ElecBckwrds, 12=CoilOpen, 13=CoilShort, 14=CoilOOR, 15=EmptyPipe, 16=BrdTempFail, 17=3.3VRailLow, 18=RtcFail
Object ID lookup: ONICON FT-3500 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FT-3500 insertion electromagnetic flow / BTU meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ONICON FT-3500 insertion electromagnetic flow / BTU meter

How many BACnet points does the ONICON FT-3500 insertion electromagnetic flow / BTU meter have?

This list has 37 BACnet objects: 5 analog inputs, 30 analog values, 1 binary input, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ONICON FT-3500 insertion electromagnetic flow / BTU meter BACnet points are writable?

7 of the 37 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ONICON FT-3500 insertion electromagnetic flow / BTU meter BACnet documentation?

The source is FT-3500 Insertion Electromagnetic Flow Meter Manual (DOC-0006324), revision Rev. H (PICS dated 01/03/2023), published free by ONICON at https://www.onicon.com/download/ft-3500-insertion-electromagnetic-flow-meter-manual/?v=6064.

What are the minimum BACnet points to integrate the ONICON FT-3500 insertion electromagnetic flow / BTU meter?

Start with AI 2 Volume Rate (Flow rate); AI 1 Energy Rate (Energy rate (BTU configuration)); AV 1 Mode 1 Energy Total (Mode 1 (forward) energy total); AV 2 Mode 1 Volume Total (Mode 1 (forward) volume total); AI 3 Supply Temperature (Supply temperature); AI 4 Return Temperature (Return temperature); BI 0 Mode Indication (Mode 1 = forward cooling, mode 2 = reverse heating); MV 0 Errors (Meter error state, 1 = Normal).

How do I check these points on the real FT-3500 insertion electromagnetic flow / BTU meter?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ONICON BACnet points lists

Source: FT-3500 Insertion Electromagnetic Flow Meter Manual · DOC-0006324 · rev. Rev. H (PICS dated 01/03/2023). Object names, instances and units are reproduced as published; descriptions are our own.