- FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP
Electromagnetic flow meter · BACnet points list
ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet points list
Updated 6 November 2026
The FT-3000 series mag meter has a native BACnet MS/TP port. It exposes flow rate (and percent of scale), board temperatures and battery charge as Analog Inputs, forward and reverse total and partial volumes as both Analog Values and Positive Integer Values, a reset BV, a battery-state MSV and two BitString alarm words.
This page lists 17 BACnet objects for the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ONICON’s own free documentation, linked below.
- Manufacturer
- ONICON
- Model
- FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP
- Equipment
- Electromagnetic flow meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 17 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- BACnet firmware 2.0.0, application 1.06.0000.0004 (PICS 02/23/2025)
- Default device instance
- 4194303 (not initialized; must be set before use)
- Also known as
- FT-3200, FT-3000, FT-32**-*****-21**, ONICON FT-3000 BACnet
Reference only, provided as-is: verify against ONICON’s current documentation and the live device before use. Not official ONICON information. Terms of use.
BMS integration notes: ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP
In menu 8-Communication set the MAC address, baud, Max Master and a device instance (it ships as 4194303, not initialized). Read flow rate, the forward total volume and the alarm bitstrings; write RST_SEL_CNT only to reset the selected partial counters.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | FLOW_RATE | Flow rate in configured units | Read |
| AV 0 | TOT_VOL_POS_V | Forward flow total volume | Read |
| AV 2 | TOT_VOL_NEG_V | Reverse flow total volume | Read |
| AI 1 | FLOW_RATE_(PC) | Flow, % of full scale | Read |
| Other 0 | MEA_ERROR | Measurement alarm bits (empty pipe, flow limits) | Read |
| Other 1 | SYS_ERROR | System alarm bits (battery, temp, power) | Read |
Network setup
- Settings are in menu 8-Communication, behind the programming access code.
- MAC 0-127 = MS/TP master, 128-254 = slave; baud 9600, 19200, 38400, 57600 or 76800; field-settable 120 ohm termination (switches 1 and 2).
- Device instance ships as 4194303 ('not initialized'); set 1-4,194,302 before use. Once changed it cannot be set back to 4194303.
- Bnet W.E. controls whether the device instance, name, location and description can be written over BACnet.
- No segmentation.
Watch out for
- The meter does not take part properly until the device instance is changed from 4194303.
- Volumes appear twice (AV as REAL and PIV as integer counter); pick one type and map it consistently.
- RST_SEL_CNT always reads Inactive; it is a reset strobe, not a state.
ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | FLOW_RATE | Flow rate | configurable (gpm, l/s...) | Read | |
| AImin | 1 | FLOW_RATE_(PC) | Flow rate as % of full scale | % | Read | |
| AI | 2 | BRD_T1_TEMP | Board temperature T1 | °C or °F | Read | |
| AI | 3 | BRD_T2_TEMP | Board temperature T2 | °C or °F | Read | |
| AI | 4 | BATT CHARGE | Battery charge | % | Read | |
| AVmin | 0 | TOT_VOL_POS_V | Total volume, positive (forward) flow | configurable volume | Read | |
| AV | 1 | PAR_VOL_POS_V | Partial (resettable) volume, positive flow | configurable volume | Read | |
| AVmin | 2 | TOT_VOL_NEG_V | Total volume, negative (reverse) flow | configurable volume | Read | |
| AV | 3 | PAR_VOL_NEG_V | Partial (resettable) volume, negative flow | configurable volume | Read | |
| BV | 0 | RST_SEL_CNT | Reset selected counters (write Active) | Command | 0=No Command, 1=Reset Command | |
| Othermin | 0 | MEA_ERROR | BitString Value: measurement alarm bits | Read | bit 0 overflow, 1 pulse 1 overflow, 2 pulse 2 overflow, 3 flow min, 4 flow max, 5 signal error, 6 excitation error, 7 empty pipe | |
| Othermin | 1 | SYS_ERROR | BitString Value: system alarm bits | Read | bit 0 battery fault, 1 low battery, 2 over temperature, 3 power fail | |
| PIV | 0 | TOT_VOL_POS_C | Total volume, positive flow (integer counter) | configurable volume | Read | |
| PIV | 1 | PAR_VOL_POS_C | Partial volume, positive flow (integer counter) | configurable volume | Read | |
| PIV | 2 | TOT_VOL_NEG_C | Total volume, negative flow (integer counter) | configurable volume | Read | |
| PIV | 3 | PAR_VOL_NEG_C | Partial volume, negative flow (integer counter) | configurable volume | Read | |
| MV | 0 | BATT_STATE | Battery status | Read | 1=Battery OK, 2=Battery Low, 3=Battery Empty, 4=Battery Fault |
No points match these filters.
Object ID lookup: ONICON FT-3000 series inline electromagnetic flow meter, BACnet MS/TP point IDs by name
Integration notes
- Units follow the meter's configured volume and flow units; the supplement lists the supported BACnet unit codes (metric and US, per second/minute/hour/day).
- MEA_ERROR and SYS_ERROR are BitString Value objects (listed as type Other); the bit meanings are in the states column.
- RST_SEL_CNT acts like a strobe: writing Active resets the selected counters, and the device clears the priority array so it always reads Inactive.
- Analog Input Present_Value and Reliability are writable only for testing on non-MID meters with Out_Of_Service set.
- A Network Port object (NP MS/TP, instance 0) is also present.
- Source: FT-3000 Series BACnet Supplement DOC-0007832 Rev.A, section 2.2.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP
How many BACnet points does the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP have?
This list has 17 BACnet objects: 5 analog inputs, 4 analog values, 1 binary value, 1 multi-state value, 4 positive integer values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet points are writable?
1 of the 17 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet documentation?
The source is FT-3000 Series Inline Electromagnetic Flow Meter BACnet Supplement (DOC-0007832 Rev.A), published free by ONICON at https://www.onicon.com/wp-content/uploads/2025/06/ft-3200-bacnet-supplement-DOC-0007832.pdf.
What are the minimum BACnet points to integrate the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP?
Start with AI 0 FLOW_RATE (Flow rate in configured units); AV 0 TOT_VOL_POS_V (Forward flow total volume); AV 2 TOT_VOL_NEG_V (Reverse flow total volume); AI 1 FLOW_RATE_(PC) (Flow, % of full scale); Other 0 MEA_ERROR (Measurement alarm bits (empty pipe, flow limits)); Other 1 SYS_ERROR (System alarm bits (battery, temp, power)).
How do I check these points on the real FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ONICON BACnet points lists
- Turbine flow meter (insertion)
ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)
ONICON F-1500 series insertion turbine flow meters with the communication type set to BACnet MS/TP.
Also known as: F-1500, F-1500 Series Turbine Meter, ONICON F-1500 BACnet - Ultrasonic flow meter
ONICON F-4600 Inline Ultrasonic Flow Meter (LCD)
ONICON F-4600 inline ultrasonic flow meters with LCD and the BACnet MS/TP output.
Also known as: F-4600, F-4600-BAC, F4600, ONICON F-4600 - BTU (energy) meter
ONICON System-10-BAC BTU Meter Network Interface
ONICON System-10 BTU meters fitted with the BACnet network interface (BACnet MS/TP or BACnet IP).
Also known as: System-10-BAC, System-10, System 10 BTU meter, ONICON System-10 - BTU (energy) meter, two-channel
ONICON System-1000 Flow and Energy Measurement System
ONICON System-1000 flow and energy (BTU) meters, single or two-channel, with the BACnet MS/TP or BACnet IP network option.
Also known as: System-1000, SYS-1000, SYS-1100-111, SYS-1100-121, SYS-1200-111, SYS-1200-121, ONICON System 1000 BTU meter - BTU (energy) meter
ONICON System-20 BTU Meter
ONICON System-20 BTU meters with the RS485 BACnet MS/TP interface, used on chilled and hot water loops.
Also known as: System-20, System 20, ONICON System-20, S-20 BTU meter - BTU (energy) meter, clamp-on ultrasonic
ONICON System-40 BTU Measurement System
ONICON System-40 BTU measurement systems (clamp-on ultrasonic flow plus supply/return temperature) with the BACnet MS/TP interface.
Also known as: System-40, System 40, System-40-BAC, ONICON System-40
Source: FT-3000 Series Inline Electromagnetic Flow Meter BACnet Supplement · DOC-0007832 Rev.A. Object names, instances and units are reproduced as published; descriptions are our own.