ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet points list

Updated 6 November 2026

Short answer

The FT-3000 series mag meter has a native BACnet MS/TP port. It exposes flow rate (and percent of scale), board temperatures and battery charge as Analog Inputs, forward and reverse total and partial volumes as both Analog Values and Positive Integer Values, a reset BV, a battery-state MSV and two BitString alarm words.

This page lists 17 BACnet objects for the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ONICON’s own free documentation, linked below.

Manufacturer
ONICON
Model
FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP
Equipment
Electromagnetic flow meter
Equipment type
Thermostats, sensors & meters
BACnet objects
17 (1 writable)
Transport
BACnet MS/TP
Firmware
BACnet firmware 2.0.0, application 1.06.0000.0004 (PICS 02/23/2025)
Default device instance
4194303 (not initialized; must be set before use)
Also known as
FT-3200, FT-3000, FT-32**-*****-21**, ONICON FT-3000 BACnet
Source document
FT-3000 Series Inline Electromagnetic Flow Meter BACnet Supplement · DOC-0007832 Rev.A
Download CSV 17 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ONICON’s current documentation and the live device before use. Not official ONICON information. Terms of use.

BMS integration notes: ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP

Integration in brief

In menu 8-Communication set the MAC address, baud, Max Master and a device instance (it ships as 4194303, not initialized). Read flow rate, the forward total volume and the alarm bitstrings; write RST_SEL_CNT only to reset the selected partial counters.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0FLOW_RATEFlow rate in configured unitsRead
AV 0TOT_VOL_POS_VForward flow total volumeRead
AV 2TOT_VOL_NEG_VReverse flow total volumeRead
AI 1FLOW_RATE_(PC)Flow, % of full scaleRead
Other 0MEA_ERRORMeasurement alarm bits (empty pipe, flow limits)Read
Other 1SYS_ERRORSystem alarm bits (battery, temp, power)Read

Network setup

Watch out for

ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

17 of 17 shown
Type
BinaryMulti-state
Access
Show
ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet Points List
DescriptionStates
AImin0FLOW_RATEFlow rateconfigurable (gpm, l/s...)Read
AImin1FLOW_RATE_(PC)Flow rate as % of full scale%Read
AI2BRD_T1_TEMPBoard temperature T1°C or °FRead
AI3BRD_T2_TEMPBoard temperature T2°C or °FRead
AI4BATT CHARGEBattery charge%Read
AVmin0TOT_VOL_POS_VTotal volume, positive (forward) flowconfigurable volumeRead
AV1PAR_VOL_POS_VPartial (resettable) volume, positive flowconfigurable volumeRead
AVmin2TOT_VOL_NEG_VTotal volume, negative (reverse) flowconfigurable volumeRead
AV3PAR_VOL_NEG_VPartial (resettable) volume, negative flowconfigurable volumeRead
BV0RST_SEL_CNTReset selected counters (write Active)Command0=No Command, 1=Reset Command
Othermin0MEA_ERRORBitString Value: measurement alarm bitsReadbit 0 overflow, 1 pulse 1 overflow, 2 pulse 2 overflow, 3 flow min, 4 flow max, 5 signal error, 6 excitation error, 7 empty pipe
Othermin1SYS_ERRORBitString Value: system alarm bitsReadbit 0 battery fault, 1 low battery, 2 over temperature, 3 power fail
PIV0TOT_VOL_POS_CTotal volume, positive flow (integer counter)configurable volumeRead
PIV1PAR_VOL_POS_CPartial volume, positive flow (integer counter)configurable volumeRead
PIV2TOT_VOL_NEG_CTotal volume, negative flow (integer counter)configurable volumeRead
PIV3PAR_VOL_NEG_CPartial volume, negative flow (integer counter)configurable volumeRead
MV0BATT_STATEBattery statusRead1=Battery OK, 2=Battery Low, 3=Battery Empty, 4=Battery Fault
Object ID lookup: ONICON FT-3000 series inline electromagnetic flow meter, BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP

How many BACnet points does the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP have?

This list has 17 BACnet objects: 5 analog inputs, 4 analog values, 1 binary value, 1 multi-state value, 4 positive integer values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet points are writable?

1 of the 17 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP BACnet documentation?

The source is FT-3000 Series Inline Electromagnetic Flow Meter BACnet Supplement (DOC-0007832 Rev.A), published free by ONICON at https://www.onicon.com/wp-content/uploads/2025/06/ft-3200-bacnet-supplement-DOC-0007832.pdf.

What are the minimum BACnet points to integrate the ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP?

Start with AI 0 FLOW_RATE (Flow rate in configured units); AV 0 TOT_VOL_POS_V (Forward flow total volume); AV 2 TOT_VOL_NEG_V (Reverse flow total volume); AI 1 FLOW_RATE_(PC) (Flow, % of full scale); Other 0 MEA_ERROR (Measurement alarm bits (empty pipe, flow limits)); Other 1 SYS_ERROR (System alarm bits (battery, temp, power)).

How do I check these points on the real FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ONICON BACnet points lists

Source: FT-3000 Series Inline Electromagnetic Flow Meter BACnet Supplement · DOC-0007832 Rev.A. Object names, instances and units are reproduced as published; descriptions are our own.