BTU (energy) meter · BACnet points list

ONICON System-10-BAC BTU Meter Network Interface BACnet points list

Updated 4 November 2026

Short answer

The System-10-BAC interface puts an ONICON System-10 BTU meter on BACnet MS/TP or BACnet IP. It exposes energy and flow rate, supply and return temperatures, energy and volume totals, an auxiliary pulse total and the operating mode, plus BVs that zero each total. The meter runs in single, dual or bi-directional mode, which decides which totals carry data.

This page lists 17 BACnet objects for the ONICON System-10-BAC BTU Meter Network Interface — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ONICON’s own free documentation, linked below.

Manufacturer
ONICON
Model
System-10-BAC BTU Meter Network Interface
Equipment
BTU (energy) meter
Equipment type
Thermostats, sensors & meters
BACnet objects
17 (5 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
v1.01fA
Default device instance
57017
Also known as
System-10-BAC, System-10, System 10 BTU meter, ONICON System-10
Source document
System-10-BAC Network Interface Installation Guide · 0652-12 · rev. 08/16
Download CSV 17 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ONICON’s current documentation and the live device before use. Not official ONICON information. Terms of use.

BMS integration notes: ONICON System-10-BAC BTU Meter Network Interface

Integration in brief

Read the energy rate, flow and both temperatures, and the energy and volume totals that match the meter's operating mode (AV 6). Totals are reset from the BMS by writing the zero BVs at priority 8.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Energy RateEnergy rate, Btu/h by defaultRead
AI 2Volume RateFlow rate, gpm by defaultRead
AI 3Supply TemperatureSupply water temperatureRead
AI 4Return TemperatureReturn water temperatureRead
AV 1Mode 1 Energy TotalEnergy total (mode 1 / single mode)Read
AV 2Mode 1 Volume TotalVolume total (mode 1 / single mode)Read
AV 12Mode 1 Mode 2 IndicationActive mode: 1 = Mode 1, 2 = Mode 2Read

Network setup

Watch out for

ONICON System-10-BAC BTU Meter Network Interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

17 of 17 shown
Type
Binary
Access
Show
ONICON System-10-BAC BTU Meter Network Interface BACnet Points List
DescriptionStates
AImin1Energy RateBtu/hRead
AImin2Volume RategpmRead
AImin3Supply Temperature°FRead
AImin4Return Temperature°FRead
AVmin1Mode 1 Energy TotalEnergy total; the only energy register in single modeBtuRead
AVmin2Mode 1 Volume TotalVolume total; the only volume register in single modegalRead
AV3Mode 2 Energy TotalOnly used in dual modeBtuRead
AV4Mode 2 Volume TotalOnly used in dual modegalRead
AV5Auxiliary Input Total (Di3)Pulse total on input Di3; no units reportedRead
AV6Operating Mode (Single, Dual or Bi-directional)Configured operating modeRead0=None, 1=Single, 2=Dual, 3=BiDir
AVmin12Mode 1 Mode 2 IndicationWhich mode is activeRead1=Mode 1, 2=Mode 2
AV13BACnet InstanceDevice instance numberRead
BV11Zero Mode 1 Energy TotalSet active at priority 8 to reset the totalWrite0=Inactive, 1=Active (reset)
BV12Zero Mode 1 Volume TotalSet active at priority 8 to reset the totalWrite0=Inactive, 1=Active (reset)
BV13Zero Mode 2 Energy TotalSet active at priority 8 to reset the totalWrite0=Inactive, 1=Active (reset)
BV14Zero Mode 2 Volume TotalSet active at priority 8 to reset the totalWrite0=Inactive, 1=Active (reset)
BV15Zero Auxiliary Input TotalSet active at priority 8 to reset the totalWrite0=Inactive, 1=Active (reset)
Object ID lookup: ONICON System-10-BAC BTU Meter Network Interface point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the System-10-BAC BTU Meter Network Interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ONICON System-10-BAC BTU Meter Network Interface

How many BACnet points does the ONICON System-10-BAC BTU Meter Network Interface have?

This list has 17 BACnet objects: 4 analog inputs, 8 analog values, 5 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ONICON System-10-BAC BTU Meter Network Interface BACnet points are writable?

5 of the 17 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ONICON System-10-BAC BTU Meter Network Interface BACnet documentation?

The source is System-10-BAC Network Interface Installation Guide (0652-12), revision 08/16, published free by ONICON at https://www.onicon.com/wp-content/uploads/0652-12-System-10-BAC-Network-Interface-Installation-for-email-07-18-1.pdf.

What are the minimum BACnet points to integrate the ONICON System-10-BAC BTU Meter Network Interface?

Start with AI 1 Energy Rate (Energy rate, Btu/h by default); AI 2 Volume Rate (Flow rate, gpm by default); AI 3 Supply Temperature (Supply water temperature); AI 4 Return Temperature (Return water temperature); AV 1 Mode 1 Energy Total (Energy total (mode 1 / single mode)); AV 2 Mode 1 Volume Total (Volume total (mode 1 / single mode)); AV 12 Mode 1 Mode 2 Indication (Active mode: 1 = Mode 1, 2 = Mode 2).

How do I check these points on the real System-10-BAC BTU Meter Network Interface?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ONICON BACnet points lists

Source: System-10-BAC Network Interface Installation Guide · 0652-12 · rev. 08/16. Object names, instances and units are reproduced as published; descriptions are our own.