Turbine flow meter (insertion) · BACnet points list
ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The F-1500 turbine meter can run BACnet MS/TP on its RS-485 port. It exposes 19 Analog Inputs (volume, mass and energy flow, two temperatures, pressure, density, two totalizers, output channel values, velocity and turbine diagnostics), three alarm Binary Inputs, an external-input BI and a totalizer-reset BV.
This page lists 24 BACnet objects for the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ONICON’s own free documentation, linked below.
- Manufacturer
- ONICON
- Model
- F-1500 insertion turbine flow meter (BACnet MS/TP)
- Equipment
- Turbine flow meter (insertion)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 24 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application software 1.07
- Default device instance
- 7
- Also known as
- F-1500, F-1500 Series Turbine Meter, ONICON F-1500 BACnet
Reference only, provided as-is: verify against ONICON’s current documentation and the live device before use. Not official ONICON information. Terms of use.
BMS integration notes: ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)
Set the communication type to BACnet in the diagnostics menu, then set baud and MAC address in the output menu and power-cycle. Read volume flow, the totalizer and the alarms; write the Reset BV to clear the totalizer.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Volume Flow | Volumetric flow rate | Read |
| AI 8 | Totalizer 1 | Accumulated total (mass, volume or energy) | Read |
| AI 7 | Energy Flow | Energy rate (energy-measuring builds) | Read |
| AI 3 | Temperature 1 | Process temperature 1 | Read |
| BI 1 | Alarm1 | Alarm 1 active | Read |
| BI 2 | Alarm2 | Alarm 2 active | Read |
| BI 3 | Alarm3 | Alarm 3 active | Read |
Network setup
- Factory menu password 16363. Set Diagnostics > Config Code > comm type to BACnet, then Output menu > Baud Rate and MAC address.
- Baud 9600, 19200, 38400 or 76800; MAC 0-127 (MS/TP master only).
- Device object default instance 7; Max Master 127; Max Info Frames 1; no segmentation; max APDU 300.
- Device Communication Control password: vortek.
- Power-cycle the meter after changing settings.
Watch out for
- The manual's setup steps end by switching comm type back to HART after setting baud/MAC; check the comm type reads BACnet before commissioning.
- Max Info Frames is 1 and Max Master 127; neither is writable over BACnet.
ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Volume Flow | Volumetric flow rate | configurable (gpm, ft3/min, l/s, m3/h...) | Read | |
| AI | 2 | Mass Flow | Mass flow rate | configurable (lb/h, kg/s...) | Read | |
| AImin | 3 | Temperature 1 | Temperature 1 | °F, °C or K | Read | |
| AI | 4 | Temperature 2 | Temperature 2 | °F, °C or K | Read | |
| AI | 5 | Pressure | Pressure | configurable (psi, inH2O, bar, kPa...) | Read | |
| AI | 6 | Density | Fluid density | kg/m3 | Read | |
| AImin | 7 | Energy Flow | Energy rate | configurable (kW, Btu/h, MBH, MW, hp) | Read | |
| AImin | 8 | Totalizer 1 | Totalizer 1 (mass, volume or energy) | configurable | Read | |
| AI | 9 | Totalizer 2 | Totalizer 2 (mass, volume or energy) | configurable | Read | |
| AI | 10 | StatusRegister | Meter status register | Read | ||
| AI | 11 | Channel 1 (4-20 mA) | Analog output channel 1 | mA | Read | |
| AI | 12 | Channel 2 (4-20 mA) | Analog output channel 2 | mA | Read | |
| AI | 13 | Channel 3 (4-20 mA) | Analog output channel 3 | mA | Read | |
| AI | 14 | Scaled Freq | Scaled frequency output | Hz | Read | |
| AI | 15 | Flow Velocity | Flow velocity | ft/s | Read | |
| AI | 16 | Viscosity | Fluid viscosity | cP | Read | |
| AI | 17 | Frequency | Turbine frequency | Hz | Read | |
| AI | 18 | Turbine Amp | Turbine signal amplitude | mV | Read | |
| AI | 19 | FilterSetting | Input filter setting | Hz | Read | |
| BImin | 1 | Alarm1 | Alarm 1 (1 only if enabled and active) | Read | ||
| BImin | 2 | Alarm2 | Alarm 2 (1 only if enabled and active) | Read | ||
| BImin | 3 | Alarm3 | Alarm 3 (1 only if enabled and active) | Read | ||
| BI | 4 | External | External input (always reads 0) | Read | ||
| BV | 1 | Reset | Resets the totalizer | Write |
No points match these filters.
Object ID lookup: ONICON F-1500 insertion turbine flow meter point IDs by name
AI1Volume FlowAI2Mass FlowAI3Temperature 1AI4Temperature 2AI5PressureAI6DensityAI7Energy FlowAI8Totalizer 1AI9Totalizer 2AI10StatusRegisterAI11Channel 1 (4-20 mA)AI12Channel 2 (4-20 mA)AI13Channel 3 (4-20 mA)AI14Scaled FreqAI15Flow VelocityAI16ViscosityAI17FrequencyAI18Turbine AmpAI19FilterSettingBI1Alarm1BI2Alarm2BI3Alarm3BI4ExternalBV1Reset
Integration notes
- Which values carry data depends on the meter build and configuration; several objects are marked 'TBD' in the manual's description column.
- Units follow the meter's configured display units. The manual prints rate units for the totalizers; the totalizer unit depends on whether it counts mass, volume or energy.
- AI 8 and AI 9 are printed as one row ('Totalizer 1 & Totalizer 2'); the PICS lists them separately as AI 8 and AI 9.
- Present_Value and Out_Of_Service are listed as writable for AI, BI and BV; writing an input's Present_Value only makes sense with Out_Of_Service set.
- BI 4 always reads 0.
- Source: F-1500 manual DOC-0003872, section 4.3 (PICS dated 19-April-2012).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the F-1500 insertion turbine flow meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)
How many BACnet points does the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) have?
This list has 24 BACnet objects: 19 analog inputs, 4 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet points are writable?
1 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet documentation?
The source is F-1500 Insertion Turbine Flow Meter Installation and Operation Manual (DOC-0003872), published free by ONICON at https://www.onicon.com/wp-content/uploads/2024/11/F-1500-Insertion-Turbine-Flow-Meter-Manual-DOC-0003872.pdf.
What are the minimum BACnet points to integrate the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)?
Start with AI 1 Volume Flow (Volumetric flow rate); AI 8 Totalizer 1 (Accumulated total (mass, volume or energy)); AI 7 Energy Flow (Energy rate (energy-measuring builds)); AI 3 Temperature 1 (Process temperature 1); BI 1 Alarm1 (Alarm 1 active); BI 2 Alarm2 (Alarm 2 active); BI 3 Alarm3 (Alarm 3 active).
How do I check these points on the real F-1500 insertion turbine flow meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ONICON BACnet points lists
- Ultrasonic flow meter
ONICON F-4600 Inline Ultrasonic Flow Meter (LCD)
ONICON F-4600 inline ultrasonic flow meters with LCD and the BACnet MS/TP output.
Also known as: F-4600, F-4600-BAC, F4600, ONICON F-4600 - Electromagnetic flow meter
ONICON FT-3000 series (FT-3200) inline electromagnetic flow meter, BACnet MS/TP
ONICON FT-3000 series inline electromagnetic flow meters with the BACnet MS/TP output (PICS model FT-32**-*****-21**).
Also known as: FT-3200, FT-3000, FT-32**-*****-21**, ONICON FT-3000 BACnet - BTU (energy) meter
ONICON System-10-BAC BTU Meter Network Interface
ONICON System-10 BTU meters fitted with the BACnet network interface (BACnet MS/TP or BACnet IP).
Also known as: System-10-BAC, System-10, System 10 BTU meter, ONICON System-10 - BTU (energy) meter, two-channel
ONICON System-1000 Flow and Energy Measurement System
ONICON System-1000 flow and energy (BTU) meters, single or two-channel, with the BACnet MS/TP or BACnet IP network option.
Also known as: System-1000, SYS-1000, SYS-1100-111, SYS-1100-121, SYS-1200-111, SYS-1200-121, ONICON System 1000 BTU meter - BTU (energy) meter
ONICON System-20 BTU Meter
ONICON System-20 BTU meters with the RS485 BACnet MS/TP interface, used on chilled and hot water loops.
Also known as: System-20, System 20, ONICON System-20, S-20 BTU meter - BTU (energy) meter, clamp-on ultrasonic
ONICON System-40 BTU Measurement System
ONICON System-40 BTU measurement systems (clamp-on ultrasonic flow plus supply/return temperature) with the BACnet MS/TP interface.
Also known as: System-40, System 40, System-40-BAC, ONICON System-40
Source: F-1500 Insertion Turbine Flow Meter Installation and Operation Manual · DOC-0003872. Object names, instances and units are reproduced as published; descriptions are our own.