Turbine flow meter (insertion) · BACnet points list

ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The F-1500 turbine meter can run BACnet MS/TP on its RS-485 port. It exposes 19 Analog Inputs (volume, mass and energy flow, two temperatures, pressure, density, two totalizers, output channel values, velocity and turbine diagnostics), three alarm Binary Inputs, an external-input BI and a totalizer-reset BV.

This page lists 24 BACnet objects for the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ONICON’s own free documentation, linked below.

Manufacturer
ONICON
Model
F-1500 insertion turbine flow meter (BACnet MS/TP)
Equipment
Turbine flow meter (insertion)
Equipment type
Thermostats, sensors & meters
BACnet objects
24 (1 writable)
Transport
BACnet MS/TP
Firmware
Application software 1.07
Default device instance
7
Also known as
F-1500, F-1500 Series Turbine Meter, ONICON F-1500 BACnet
Source document
F-1500 Insertion Turbine Flow Meter Installation and Operation Manual · DOC-0003872
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ONICON’s current documentation and the live device before use. Not official ONICON information. Terms of use.

BMS integration notes: ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)

Integration in brief

Set the communication type to BACnet in the diagnostics menu, then set baud and MAC address in the output menu and power-cycle. Read volume flow, the totalizer and the alarms; write the Reset BV to clear the totalizer.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Volume FlowVolumetric flow rateRead
AI 8Totalizer 1Accumulated total (mass, volume or energy)Read
AI 7Energy FlowEnergy rate (energy-measuring builds)Read
AI 3Temperature 1Process temperature 1Read
BI 1Alarm1Alarm 1 activeRead
BI 2Alarm2Alarm 2 activeRead
BI 3Alarm3Alarm 3 activeRead

Network setup

Watch out for

ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

24 of 24 shown
Type
Analog
Access
Show
ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Volume FlowVolumetric flow rateconfigurable (gpm, ft3/min, l/s, m3/h...)Read
AI2Mass FlowMass flow rateconfigurable (lb/h, kg/s...)Read
AImin3Temperature 1Temperature 1°F, °C or KRead
AI4Temperature 2Temperature 2°F, °C or KRead
AI5PressurePressureconfigurable (psi, inH2O, bar, kPa...)Read
AI6DensityFluid densitykg/m3Read
AImin7Energy FlowEnergy rateconfigurable (kW, Btu/h, MBH, MW, hp)Read
AImin8Totalizer 1Totalizer 1 (mass, volume or energy)configurableRead
AI9Totalizer 2Totalizer 2 (mass, volume or energy)configurableRead
AI10StatusRegisterMeter status registerRead
AI11Channel 1 (4-20 mA)Analog output channel 1mARead
AI12Channel 2 (4-20 mA)Analog output channel 2mARead
AI13Channel 3 (4-20 mA)Analog output channel 3mARead
AI14Scaled FreqScaled frequency outputHzRead
AI15Flow VelocityFlow velocityft/sRead
AI16ViscosityFluid viscositycPRead
AI17FrequencyTurbine frequencyHzRead
AI18Turbine AmpTurbine signal amplitudemVRead
AI19FilterSettingInput filter settingHzRead
BImin1Alarm1Alarm 1 (1 only if enabled and active)Read
BImin2Alarm2Alarm 2 (1 only if enabled and active)Read
BImin3Alarm3Alarm 3 (1 only if enabled and active)Read
BI4ExternalExternal input (always reads 0)Read
BV1ResetResets the totalizerWrite
Object ID lookup: ONICON F-1500 insertion turbine flow meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the F-1500 insertion turbine flow meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)

How many BACnet points does the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) have?

This list has 24 BACnet objects: 19 analog inputs, 4 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet points are writable?

1 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ONICON F-1500 insertion turbine flow meter (BACnet MS/TP) BACnet documentation?

The source is F-1500 Insertion Turbine Flow Meter Installation and Operation Manual (DOC-0003872), published free by ONICON at https://www.onicon.com/wp-content/uploads/2024/11/F-1500-Insertion-Turbine-Flow-Meter-Manual-DOC-0003872.pdf.

What are the minimum BACnet points to integrate the ONICON F-1500 insertion turbine flow meter (BACnet MS/TP)?

Start with AI 1 Volume Flow (Volumetric flow rate); AI 8 Totalizer 1 (Accumulated total (mass, volume or energy)); AI 7 Energy Flow (Energy rate (energy-measuring builds)); AI 3 Temperature 1 (Process temperature 1); BI 1 Alarm1 (Alarm 1 active); BI 2 Alarm2 (Alarm 2 active); BI 3 Alarm3 (Alarm 3 active).

How do I check these points on the real F-1500 insertion turbine flow meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ONICON BACnet points lists

Source: F-1500 Insertion Turbine Flow Meter Installation and Operation Manual · DOC-0003872. Object names, instances and units are reproduced as published; descriptions are our own.