Energy recovery ventilation unit controller · BACnet points list

Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) BACnet points list

Updated 12 November 2026

Short answer

The FAC controller in Nuaire XBOXER XBC units (EcoSmart Connect CO) is a BACnet MS/TP device; a BACnet IP router (ESCO-IPN) is offered for IP networks. The manual's list by instance number has 166 objects in the 10005-18258 range: temperatures and room module values (AI), fan and heating outputs, relay states, setpoints and fan settings (AV), enables, modes and alarms (MSV), six schedules and a calendar. Nuaire's BPS and Boxer BPS manuals (671828, 671873) use mostly the same instances.

This page lists 166 BACnet objects for the Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) — 88 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Nuaire’s own free documentation, linked below.

Manufacturer
Nuaire
Model
XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)
Equipment
Energy recovery ventilation unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
166 (88 writable)
Transport
BACnet MS/TP
Firmware
Strategy SW-FAC2612-2-12A (per object 17340)
Also known as
Nuaire XBOXER, XBC, XBC10, XBC65, EcoSmart Connect FAC, Nuaire BPS ESC, Boxer BPS EcoSmart Connect, BPS H-CO, Nuaire 671748
Source document
XBOXER XBC unit sizes 10-65 with EcoSmart Connect (CO) control - Installation and Maintenance, 12.1 BACnet Object List (By Instance Number) · 671748 · rev. 2020-11-25
Download CSV 166 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Nuaire’s current documentation and the live device before use. Not official Nuaire information. Terms of use.

BMS integration notes: Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)

Integration in brief

Set MV 10218 Enable to On (2) to run the unit, then write AV 17761 Fan Speed Demand (0 % = trickle) and AV 10309 Software Setpoint. Read the supply, fresh and extract air temperatures, BO 10191 Fan Enabled Cmd and the alarm MSVs; BV 10332 resets latched alarms. Variables are normally written at priority 16.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10218EnableSoftware enable (1 = Off, 2 = On)Write
AV 17761Fan Speed DemandFan speed demand, % (0 % = trickle)Write
AV 10309Software SetpointTemperature setpoint, °CWrite
BV 10332Reset AlarmsReset latched alarmsWrite
BO 10191Fan Enabled CmdFan enable relay stateRead
AI 10005Supply Air Temp (B)Supply air temperatureRead
AI 10008Fresh Air Temp (H)Fresh (outdoor) air temperatureRead
AI 10011Extract Air Temp (C)Extract air temperatureRead
BO 10188Fault Relay CmdFault relay (0 = Alarm, 1 = Normal)Read
MV 15309Critical AlarmLatched critical alarm (2 = Alarm)Read

Enable & remote start

The unit runs from the software Enable MSV, the switched-live enable input (IN8), the schedule, night cooling, purge, or room module PIR and fan override inputs. MV 10214 SetPoint Op decides whether the software setpoint or the last changed setpoint is used.

Sensors & values from the BMS

AV 17773 BMS 0-10v Input is a virtual 0-10 V input for ESClassic BMS mode (MV 17608 OUT4 Mode). AV 17971 sets how long a changed setpoint holds before reverting when 'last changed with timeout' is selected.

Network setup

Watch out for

Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

166 of 166 shown
Type
Multi-state
Access
Show
Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) BACnet Points List
DescriptionStates
AImin10005Supply Air Temp (B)The supply air temperature°CRead
AImin10008Fresh Air Temp (H)The fresh air temperature°CRead
AImin10011Extract Air Temp (C)The extract air temperature°CRead
AI10017RM199 HumidityThe Humidity at RM address 199%RHRead
AI10029RM199 TempThe temperature at RM address 199°CRead
AI10032IN4The 0-10 voltage at input 4VRead
AI10035IN5The 0-10 voltage at input 5VRead
AI10050RM200 TempThe temperature at RM address 200°CRead
AI10053RM200 HumidityThe Humidity at RM address 200%RHRead
AI10065RM201 TempThe temperature at RM address 201°CRead
AI10068RM202 TempThe temperature at RM address 202°CRead
AI10071RM203 TempThe temperature at RM address 203°CRead
AI10077RM201 HumidityThe Humidity at RM address 201%RHRead
AI10092RM202 HumidityThe Humidity at RM address 202%RHRead
AI10107RM203 HumidityThe Humidity at RM address 203%RHRead
AI10137RM212 CO2The CO2 at RM address 212ppmRead
AI10140RM213 CO2The CO2 at RM address 213ppmRead
AI10143RM214 CO2The CO2 at RM address 214ppmRead
AI10146RM215 CO2The CO2 at RM address 215ppmRead
AO10173Output 4Configurable output 4 (OUT4)%Read
AO10176Extract Fan OutputThe 0-10v signal to the extract fanVRead
AO10179Heating OutputThe 0-10v signal to the heating output%Read
AO10182Supply Fan OutputThe 0-10v signal to the supply fanVRead
AV10023RM199 SetpointThe setpoint at RM address 199°CRead
AV10074RM200 SetpointThe setpoint at RM address 200°CRead
AV10083RM201 SetpointThe setpoint at RM address 201°CRead
AV10098RM202 SetpointThe setpoint at RM address 202°CRead
AV10113RM203 SetpointThe setpoint at RM address 203°CRead
AV10262Alarm DelayAlarm hold off period; default 10sWrite
AV10263Auto-Run on Max-TimeMaximum Run-on Max Time; default 900sWrite
AV10264Auto-run-on Scale FactorScale Factor for automatic run-on time; default 2Write
AV10265CO2 TargetTarget CO2 Value; default 650ppmWrite
AV10266DeadbandDead band for temp control; default 3°CWrite
AV10267Run-on (Enable)Run-on timer value; default 0sWrite
AV10268Extract Fan MaxIndividual fan maximum speed setting; default 100%Write
AV10270Extract Fan MinIndividual fan minimum speed setting; default 20%Write
AV10272Run-on (Boost)Boost run-on time; default 0sWrite
AV10273Supply Fan Boost SpeedSupply Fan boost speed; default 100%Write
AV10274Frost Prot. Fan OffMinimum time the supply fan will stop in a frost protection state; default 300sWrite
AV10275Frost Prot. TempSupply temperature at which frost protection becomes active; default 4°CWrite
AV10276Heat Boost SetpointHeater Boost Setpoint; default 35°CWrite
AV10277High Temp AlarmSupply temp which will trip the high supply alarm; default 50°CWrite
AV10278Humidity TargetRelative Humidity Target; default 50%RHWrite
AV10279IO Damper DelayDelay between starting the fan relay and the fan output.; default 0sWrite
AV10280Low Temp AlarmSupply temp which will trip the low supply alarm; default 8°CWrite
AV10281Night C Fan SpeedThe night cool fan speed; default 60%Write
AV10302Nigh C Min TempThe minimum temperature that will stop night cooling; default 12°CWrite
AV10303Pressure TargetTarget pressure value; default 400PaWrite
AV10304Purge Fan Speeddefault 60%Write
AV10305Purge Min TempThe minimum temperature that will stop night cooling; default 12°CWrite
AV10306RTC Boost BandThe Return Temperature Control Boost Band; default 15°CWrite
AV10307RTC Max Supply TempMaximum supply temp when in RTC mode; default 35°CWrite
AV10308RTC Min Supply TempMinimum supply temp when in RTC mode; default 12°CWrite
AVmin10309Software Setpointdefault 22°CWrite
AV10310STC H/C PrefSTC Heat/Cool Pref; default 50Write
AV10311STC HX Efficiencydefault 0.8Write
AV10312Supply Fan MaxIndividual fan maximum speed setting; default 100%Write
AV10314Supply Fan MinIndividual fan minimum speed setting; default 20%Write
AV10316Trickle DeadbandSetpoint deadband used when trickling with no enable signal.; default 5°CWrite
AV11296Room Air TempThe room air temperature°CRead
AV13980CO2 LevelThe CO2 LevelppmRead
AV14297HumidityThe Humidity Level% RHRead
AV14534Active SetpointThe setpoint currently used°CRead
AV17273EF Max VoltThe upper voltage for the extract fan; default 10VWrite
AV17274EF Start VoltThe voltage required to start the extract fan; default 1VWrite
AV17275SF Max VoltThe upper voltage for the supply fan; default 10VWrite
AV17276SF Start VoltThe voltage required to start the extract fan; default 1VWrite
AV17419Extract Boost SpeedThe extract fan boost speed; default 100%Write
AVmin17761Fan Speed DemandA user entered fan speed demand. 0% = trickle speed; default 0%Write
AV17773BMS 0-10v InputA virtual BMS voltage input using an ESClassic BMS table; default 0VWrite
AV17830Fan Speed ScheduleCurrent state of the Fan Speed Demand Schedule object.; default 0%Write
AV17971Setpoint TimeoutTime before reverting to software setpoint.; default 3600sWrite
AV17977Fan Override TimeoutTime before reverting to auto fan speed.; default 3600sWrite
AV18215Setpoint ScheduleCurrent state of the Setpoint Schedule object.; default 22°CWrite
AV18258Extract Setback SpeedThe extract fan speed when Extract Setback is enabled.; default 30%Write
BI10161SL EnableThe state of the enable input (IN8)Read0=Off, 1=On
BI10164SL2 InputThe state of the configurable input (IN9)Read0=Off, 1=On
BI10167Alarm Circuit 1The state of Alarm Circuit 1Read0=Alarm, 1=Normal
BI10170Alarm Circuit 2The state of Alarm Circuit 2Read0=Alarm, 1=Normal
BO10185Bypass Damper CmdThe controller’s signal to the HX bypass. (Active = Bypass, Inactive = Heat Exchange)Read0=Inactive, 1=Active
BOmin10188Fault Relay CmdThe state of the fault relay. (Fault = De-energised)Read0=Alarm, 1=Normal
BOmin10191Fan Enabled CmdThe state of the fan enabled relay.Read0=Off, 1=On
BO10194Cooling Demand CmdThe state of the cooling demand relay.Read0=Off, 1=On
BO10197Heating Demand CmdThe state of the heating demand relay.Read0=Off, 1=On
BV10020RM199 Occupancy StatusThe occupancy status at RM address 199Read0=Occupied, 1=Unoccupied
BV10056RM200 Occupancy StatusThe occupancy status at RM address 200Read0=Occupied, 1=Unoccupied
BV10080RM201 Occupancy StatusThe occupancy status at RM address 201Read0=Occupied, 1=Unoccupied
BV10095RM202 Occupancy StatusThe occupancy status at RM address 202Read0=Occupied, 1=Unoccupied
BV10110RM203 Occupancy StatusThe occupancy status at RM address 203Read0=Occupied, 1=Unoccupied
BVmin10332Reset AlarmsChanging this value will reset any latched alarms; default FALSEWrite0=False, 1=True
BV12880Tuning ResetResets the PID auto tuning loops; default FALSEWrite0=False, 1=True
CAL10496Local CalendarWrite
SCH10496Time ScheduleLocal Time ScheduleWrite
SCH10499Purge Time ScheduleWrite
SCH15875Night C SampleDaytime schedule for winter or summer decision makingWrite
SCH16014Night C ScheduleNight Cooling ScheduleWrite
SCH17798Fan Speed ScheduleA schedule for fan speed demand (0% = Trickle speed)Write
SCH18215Setpoint ScheduleA schedule for setpoint adjustment.Write
MV10014RM199 Fan SpeedFan Speed Override Status of RM199Read1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MV10044RM199 Occ DisplayOccupancy Display at RM address 199Read1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby
MV10062RM200 Occ DisplayOccupancy Display at RM address 200Read1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby
MV10089RM201 Occ DisplayOccupancy Display at RM address 201Read1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby
MV10104RM202 Occ DisplayOccupancy Display at RM address 202Read1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby
MV10119RM203 Occ DisplayOccupancy Display at RM address 203Read1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby
MV102000-10 v CO2 RangeCO2 sensor output rangeWrite1=0-2,000ppm, 2=0- 4,000ppm, 3=0-5,000ppm, 4=0-10,000ppm, 5=0- 20,000ppm
MV10201CO2 Sensor OpCO2 sensor operationWrite1=Average CO2, 2=Max CO2, 3=Ignore CO2
MV10202SL2 ModeSet the function of switched live 2; default Fan BoostWrite1=None, 2=Fan Boost, 3=Heater Boost, 4=Extract Setback
MV10203Cooling TypeSet the type of cooling fitted.; default NoneWrite1=None, 2=Chilled Water, 3=3rd-Party
MV10204Damper OverrideOverride bypass damper position; default AutoWrite1=Auto, 1=Heat Exchange, 2=Bypass
MV10205Heat BoostSoftware enabled Heater boost; default OffWrite1=Off, 2=On
MV10206Heating TypeSet the type of heating fitted.; default As per BuildWrite1=None, 2=LPHW, 3=Electric, 4=3rd-Party
MV10207H Sensor OpHumidity Sensor Operation; default Average RH%Write1=Average RH%, 2=Max RH%, 3=Ignore RH%
MV10208Ignore PIR SensorsIgnore all MSTP network PIR sensors; default NoWrite1=No, 2=Yes
MV10209IN4 FunctionFunction of the UI4 input; default NoneWrite1=None, 2=N/A, 3=N/A, 4=0-10V CO2 Sensor, 5=0- 10V Temperature Sensor, 6=0-10V Humidity Sensor, 7=0-10V Pressure Sensor
MV10210IN5 FunctionFunction of the UI5 input; default NoneWrite1=None, 2=Fan Speed Control, 3=0-10v BMS, 4=0-10V CO2 Sensor, 5=0- 10V Temperature Sensor, 6=0-10V Humidity Sensor, 7=0-10V Pressure Sensor
MV10211Low Temp ActionAction taken when the low supply alarm is engaged.; default Alarm OnlyWrite1=Alarm only, 2=Alarm and stop fans
MV102120-10v Press. RangePressure sensor range; default 0 to 1000PaWrite1=0-25Pa, 2=0-50Pa, 3=0-100Pa, 4=0-300Pa, 5=0-500Pa, 6=0-1000Pa, 7=0-1600Pa, 8=0-2500Pa, 9=0-3000Pa
MV10213P sens. OpPressure sensor operation; default Average ValueWrite1=Average, 2=Max, 3=Ignore
MV10214SetPoint OpSetpoint operation; default Last Value ChangedWrite1=Last Changed, 2=Software Only, 3=Last Changed with Timeout
MV10215T Sens. OpTemperature sensor operation; default NS AverageWrite1=NS Average, 2=Return Air Only, 3=NS & Return Average
MV102160-10v Temp RangeTemperature sensor range; default 0 to 50°CWrite1=0 to 50°C, 2=0 to 40°C, 3=0 to 100°C, 4=0 to 80°C, 5=0 to 90°C
MV10217Auto Run-onAuto-run on mode; default OffWrite1=Off, 2=On
MVmin10218EnableSoftware enable switch; default OffWrite1=Off, 2=On
MV10219Enable via ScheduleEnabled via ScheduleRead1=Off, 2=On
MV10240Fan BoostSoftware enabled Fan boost; default OffWrite1=Off, 2=On
MV10241Hibernate ModeUnit is ready for hibernation; default OffWrite1=Off, 2=On
MV10242Night C ModeThis input will enable night cool mode.; default OffWrite1=Off, 2=On
MV10243Purge ActiveThis input will enable purge mode; default OffWrite1=Off, 2=On
MV10244Tacho PCB FittedIs a “Taco Bell” PCB fitted.; default As per BuildWrite1=No, 2=Yes
MV10245Temp Control ModeTemperature control mode; default Supply TempWrite1=Supply Temp, 2=Room Temp
MV10246Test (Fan)Fan Test (Factory Use Only)Write1=Off, 2=On
MV10247Test (Heater)Heater Test (Factory Use Only)Write1=Off, 2=On
MV10248Test (Override Fan)Overtemp Test (Factory Use Only)Write1=Off, 2=On
MV10249Test (Wiring)Wiring Test (Factory Use Only)Write1=Off, 2=On
MV10250Trickle ModeEnable trickle mode; default OffWrite1=Off, 2=On
MV10512Purge Time ScheduleState of the Purge Time ScheduleRead1=Off, 2=On
MV14703RM199 Fan DisplayFan Speed Override Display at RM address 199Read1=No Status, 2=Off, 3=Low, 4=Medium, 5=High, 6=Auto-Off, 7=Auto-Low, 8=Auto-Medium, 9=Auto-High
MVmin15309Critical AlarmUnit is latched in critical alarmRead1=Normal, 2=Alarm
MV15310Maint. AlarmMaintenance AlarmRead1=Normal, 2=Alarm
MV16008Night C SampleNight Cooling Sample ScheduleRead1=Off, 2=On
MV16014Night C ScheduleNight Cooling Running ScheduleRead1=Off, 2=On
MV17009XBC Sensor AlarmXBC Sensor Out of RangeRead1=Normal, 2=Alarm
MV17011Low SA-T AlarmLow Supply Air AlarmRead1=Normal, 2=Alarm
MV17012High SA-T AlarmHigh Supply Air AlarmRead1=Normal, 2=Alarm
MV17013Frost AlarmRead1=Normal, 2=Alarm
MV17281Ala (A Cir 1)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17282Norm (A Cir 1)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17285Ala (Low Supply Temp)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17286Norm (Low Supply Temp)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17289Norm (High Supply Temp)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17290Ala (High Supply Temp)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17293Ala (A Cir 2)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17294Norm (A Cir 2)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17316Ala (Frost)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17317Norm (Frost)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17320Ala (XBC Sensor Fault)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17321Norm (XBC Sensor Fault)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17340SW-FAC2612-2-12AStrategy Version; default OffRead1=Off, 2=On
MV17365Fire AlarmEngage Fire Alarm ModeWrite1=Normal, 2=Alarm
MV17409Ala (Fire Alarm)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17411Norm (Fire Alarm)For LCD Event Signal OnlyRead1=Normal, 2=Alarm
MV17608OUT4 ModeChooses the mode of Analogue Output 4; default Cooling DemandWrite1=Cooling Demand, 2=ESClassic BMS Mode
MV17610ESC BMS Thermic OutputChooses whether to demand thermal output in 0-10v ESClassic BMS mode; default AutoWrite1=Auto, 2=None, 3=Heating, 4=Cooling
MV17669IO Damper FittedSelects whether IO dampers are fitted on alarm circuit 2; default NoWrite1=No, 2=Yes
MV17769Extract SetbackPuts the extract fan to setback speed; default OffWrite1=Off, 2=On
MV17975Fan Override OperationChooses the operation of the 3-speed fan override.; default Override Has PriorityWrite1=Overide Has Priority, 2=Revert to Auto after Timeout
Object ID lookup: Nuaire XBOXER XBC with EcoSmart Connect control, FAC controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)

How many BACnet points does the Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) have?

This list has 166 BACnet objects: 19 analog inputs, 4 analog outputs, 52 analog values, 4 binary inputs, 5 binary outputs, 7 binary values, 1 calendar, 6 schedules, 68 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) BACnet points are writable?

88 of the 166 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list) BACnet documentation?

The source is XBOXER XBC unit sizes 10-65 with EcoSmart Connect (CO) control - Installation and Maintenance, 12.1 BACnet Object List (By Instance Number) (671748), revision 2020-11-25, published free by Nuaire at https://info.nuaire.co.uk/IandM/671748.pdf.

What are the minimum BACnet points to integrate the Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)?

Start with MV 10218 Enable (Software enable (1 = Off, 2 = On)); AV 17761 Fan Speed Demand (Fan speed demand, % (0 % = trickle)); AV 10309 Software Setpoint (Temperature setpoint, °C); BV 10332 Reset Alarms (Reset latched alarms); BO 10191 Fan Enabled Cmd (Fan enable relay state); AI 10005 Supply Air Temp (B) (Supply air temperature); AI 10008 Fresh Air Temp (H) (Fresh (outdoor) air temperature); AI 10011 Extract Air Temp (C) (Extract air temperature); BO 10188 Fault Relay Cmd (Fault relay (0 = Alarm, 1 = Normal)); MV 15309 Critical Alarm (Latched critical alarm (2 = Alarm)).

How do I enable BMS control of the Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)?

The unit runs from the software Enable MSV, the switched-live enable input (IN8), the schedule, night cooling, purge, or room module PIR and fan override inputs. MV 10214 SetPoint Op decides whether the software setpoint or the last changed setpoint is used.

Can the BMS supply sensor values to the Nuaire XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)?

AV 17773 BMS 0-10v Input is a virtual 0-10 V input for ESClassic BMS mode (MV 17608 OUT4 Mode). AV 17971 sets how long a changed setpoint holds before reverting when 'last changed with timeout' is selected.

How do I check these points on the real XBOXER XBC with EcoSmart Connect (CO) control, FAC controller (10xxx object list)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Nuaire BACnet points lists

Source: XBOXER XBC unit sizes 10-65 with EcoSmart Connect (CO) control - Installation and Maintenance, 12.1 BACnet Object List (By Instance Number) · 671748 · rev. 2020-11-25. Object names, instances and units are reproduced as published; descriptions are our own.