Energy recovery ventilation unit controller · BACnet points list

Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list BACnet points list

Updated 12 November 2026

Short answer

The EcoSmart Connect (CO) controller is a BACnet MS/TP device (default MAC address 4). This July 2026 manual lists 207 objects: AVs and multistate values in the 28501-28992 range (unit enable, software setpoint, fan speed command, sensor readings, up to eight RM room modules, configuration and alarms), four schedules and seven trend logs. The object numbering differs from Nuaire's 2022 list, so match the list to the unit's manual.

This page lists 207 BACnet objects for the Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list — 119 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Nuaire’s own free documentation, linked below.

Manufacturer
Nuaire
Model
EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list
Equipment
Energy recovery ventilation unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
207 (119 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Nuaire EcoSmart Connect, EcoSmart Connect, Ecosmart Connect (CO), ESC, XBOXER XBC, XBC, BPS, BOXER, Nuaire Connect, Nuaire 672059
Source document
Ecosmart Connect (CO) Control Operation Manual, BACnet object list · 672059 · rev. 2026-07-27
Download CSV 207 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Nuaire’s current documentation and the live device before use. Not official Nuaire information. Terms of use.

BMS integration notes: Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list

Integration in brief

Write MV 28511 Unit Enable to 1 (On) to run the unit, then set AV 28632 Fan Speed Command (0-100 %) and AV 28654 Software Setpoint (12-28 °C). Read the supply, fresh and return air temperatures, MV 28536 Fan Command and the alarm MSVs; MV 28660 resets alarms. Nuaire recommends writing AVs and MSVs at priority 16.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 28511Unit EnableUnit enable (0 = Off, 1 = On)Write
AV 28632Fan Speed CommandFan speed demand, 0-100 %Write
AV 28654Software SetpointTemperature setpoint from the network, 12-28 °CWrite
MV 28660Reset AlarmAlarm reset (1 = Reset)Write
MV 28536Fan CommandFan enable output (OUT10) statusRead
AV 28501Supply Air TemperatureSupply air temperatureRead
AV 28502Fresh Air IntakeFresh (outdoor) air temperatureRead
AV 28503Return Air TemperatureReturn air temperatureRead
MV 28538Unit Fault StatusFault relay status (0 = Alarm, 1 = Normal)Read
MV 28664Active Critical AlarmsCritical alarm active (1 = Alarm)Read

Enable & remote start

The unit runs when any enable source is active: the Unit Enable MSV (local display or network), volt-free inputs, night cooling, the internal enable schedule, a fan speed override or a room module PIR. When the enable is removed the unit runs on for the run-on time.

Sensors & values from the BMS

MV 28612 Setpoint Operation picks whether the last changed setpoint wins, software only, or last changed with a timeout.

Network setup

Watch out for

Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

207 of 207 shown
Type
AnalogMulti-state
Access
Show
Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list BACnet Points List
DescriptionStates
MV28508Unit SelectionUnit Type; default XBC; LCD page 1Write0=XBC, 1=BPS, 2=BOXER
MV28509Heating TypeSelection of Heating Type; default None; LCD page 1Write0=None, 1=LPHW, 2=Electric Heater, 3=3rd Party
MV28510Cooling TypeSelection of Cooling Type; default None; LCD page 1Write0=None, 1=Chilled Water, 2=Heat Pump, 3=Reverse Cycle DX
MV28525Tacho Board Fitteddefault No; LCD page 3Write0=No, 1=Yes
MV28616Fan ConfigFan Configuration for Boxer Units; default Both; LCD page 15Write0=Supply, 1=Extract, 2=Both
MV28689PAC Board Fitteddefault No; LCD page 26Write0=No, 1=Yes
MVmin28511Unit EnableEnable the Unit; default Off; LCD page 2Write0=Off, 1=On
MV28522VF EnableVolt Free Enable (IN5); default Off; LCD page 3Read0=Normal, 1=Alarm
MV28991Enable Schedule ActiveEnable Schedules Current State; default Off; LCD page 27Write0=Off, 1=On
SCH1Enable ScheduleEnable Internal Schedule; LCD page 33Write
AV28621SF Max DemandSupply Temperature Max Demand; Range 0-100 %; default 100; LCD page 51%Write
AV28622SF Min DemandSupply Temperature Min Demand; Range 0-100 %; default 20; LCD page 51%Write
AV28623EF Max DemandExtract Fan Maximum Demand; Range 0-100 %; default 100; LCD page 52%Write
AV28624EF Min DemandExtract Fan Minimum Demand; Range 0-100 %; default 20; LCD page 52%Write
AV28694Heat Pump Fan MinHeat Pump Minimum Fan Speed; Range 0-100%; default 40%; LCD page 57%Write
SCH4Night Cooling ScheduleNight Cooling Internal Schedule; LCD page 32Write
SCH3Purge SchedulePurge Mode Internal Schedule; LCD page 32Write
SCH2Alarm Reset ScheduleReset the Alarms; LCD page 33Write
MV28534Bypass DamperBypass damper Status (Output OUT6); default Inactive; LCD page 4Read0=Inactive, 1=Active
MV28620Damper Override LVManual Damper override; default Auto; LCD page 16Write0=Auto, 1=HX, 2=Bypass
MV28629Fan BoostEnable Fan Boost; default Off; LCD page 16Write0=Off, 1=On
AV28630EF Boost SpeedExtract Fan Boost Speed; Range 0-100 %; default 100; LCD page 52%Write
AV28631SF Boost SpeedSupply Temperature Boost Speed; Range 0-100 %; default 100; LCD page 53%Write
MV28656Trickle ModeTrickle Mode Enabled; default Off; LCD page 19Write0=Off, 1=On
AV28690Trickle DeadbandSetpoint deadband to be used while unit is in trickle; Range 0-100 degC°CWrite
MV28661Fan ActiveFan Run-on Active; default 0; LCD page 20Read0=False, 1=True
AV28617Run-onRun on time for Fan Signal; Range 0-120 seconds; default 0sWrite
MV28524IO Damper Fitteddefault No; LCD page 3Write0=No, 1=Yes
MV28657Re-circ OverrideRecirculation Override (State 0 = Auto, State 1 = Open, State 2 = Close)Write0=Auto, 1=Open, 2=Close
MV28663Fan to Damper DelayIO Damper Delay Active; default 0; LCD page 21Read0=False, 1=True
AV28693IO Damper DelayRange 0-120 seconds; default 60; LCD page 49sWrite
MVmin28538Unit Fault StatusFault Relay (Output OUT9); default Normal; LCD page 2Read0=Alarm, 1=Normal
MVmin28536Fan CommandFan Enable Command (Output OUT10); default Off; LCD page 4Read0=Off, 1=On
AV28530Supply Fan Speed AOSupply Fan Speed Analogue Output; Range 0-10 V; default 0VRead
AV28531Extract Fan Speed AOExtract Fan Speed Analogue Output; Range 0-10 V; default 0VRead
MV28625EF Setback EnableExtract Fan Setback from Supply; default Off; LCD page 16Write0=Off, 1=On
MV28627SF Setback EnableSupply Fan Setback from Extract; default Off; LCD page 16Write0=Off, 1=On
AV28626EF Setback SpeedSet the speed for the Setback; Range 0-100 %; default 30%Write
AV28628SF Setback SpeedSet the percentage setback for the Supply Fan Setback; Range 0-100 %; default 30%Write
MV28608Temp Sensor OperationTemperature Sensor Operation; default RM Average; LCD page 13Write0=RM Average, 1=Return Air Only, 2=RM & Return Air
MV28612Setpoint OperationSetpoint Input Operation; default Software Only; LCD page 14Write0=Last Changed, 1=Software Only, 2=Last Changed with Timeout
MV28615Control TypeTemperature Control Selection - State 0 (Supply Temp Control / State 1 (Return Temp Control)Write0=Supply Temp, 1=Room Temp
MV28658Reverse Cycle Backup HeatingEnables OUT3 heating output if Backup heating is present for Reverse cycle systemsWrite0=Off, 1=On
AV28640SA-T Low LimitSupply Low Temperature Low Limit; Range 5-15 deg C; default 8°CWrite
AV28651Max Supply TempReturn Temp Control Maximum Supply Temperature; Range 30-40 deg C; default 35°CWrite
AV28652Min Supply TempReturn Temp Control Minimum Supply Temperature; Range 10-20 deg C; default 12°CWrite
AVmin28654Software SetpointNetwork Temperature Setpoint; Range 12-28 deg C; default 22; LCD page 56°CWrite
AV28692Back Heater Temp DifferentialBackup heater setpoint differential (added to setpoint); Range -20-20 deg C; default -4°CWrite
AVmin28501Supply Air TemperatureSupply Air temperature; Range -20-100 deg C; LCD page 41°CRead
AVmin28502Fresh Air IntakeFresh air Temperature; Range -20-100 deg C; LCD page 42°CRead
AVmin28503Return Air TemperatureRange -20-100 deg C; LCD page 42°CRead
AV28504Room TemperatureRange -20-100 deg C; LCD page 42°CRead
AV28695Back Heater Air Of f TempBackup Heater Air Off Temperature (BPS Heat Pump only IN18); Range 0-100 deg C°CWrite
MV28635Heat BoostHeat Boost Enable; default Off; LCD page 17Write0=Off, 1=On
AV28636Heat Boost SetpointRange 0-50°C; default 35°C; LCD page 54°CWrite
MV28535Heat DemandHeat / Recirc Demand (Output OUT8); default Off; LCD page 4Read0=Off, 1=On
AV28532Heating OutputRange 0-100 %; default 0; LCD page 46%Read
MV28537Cooling DemandCooling Demand Status; default Off; LCD page 2Read0=Off, 1=On
MV28645Cooling Output TypeOUT4 Mode Selection; default Cooling Demand; LCD page 18Write0=Cooling Demand, 1=ESClassic BMS
AV28533Cooling OutputRange 0-100 %; default 0; LCD page 47%Read
MV28595IN16 FunctionIN16 Function Input; default None; LCD page 10Write0=None, 1=N/A, 2=N/A, 3=0 to 10V CO2 Sensor, 4=0 to 10V Temp Sensor, 5=0 to 10V Hum Sensor, 6=0 to 10V Press Sensor
MV28596IN17 FunctionIN17 Function Input; default None; LCD page 10Write0=None, 1=Fan Speed Control, 2=0 to 10V BMS, 3=0 to 10V CO2 Sensor, 4=0 to 10V Temp Sensor, 5=0 to 10V Hum Sensor, 6=0 to 10V Press Sensor
MV285970-10v Temp Range for IN16 & IN170-10v Temp Range Select for IN4 & IN5; default 0 to 50 degCWrite0=0 to 50 degC, 1=0 to 40 degC, 2=0 to 100 degC, 3=0 to 80 degC, 4=0 to 90 degC
MV285980-10v Press Range for IN16 & IN170-10v Pressure Range Select for IN16 & IN17; default 0 to 1000 PaWrite0=0 to 25 Pa, 1=0 to 50 Pa, 2=0 to 100 Pa, 3=0 to 300 Pa, 4=0 to 500 Pa, 5=0 to 1000 Pa, 6=0 to 1600 Pa, 7=0 to 2500 Pa, 8=0 to 3000 Pa
MV285990-10v CO2 Range for IN16 & IN170-10v CO2 Range Select for IN16 & IN17; default 0 to 2,000Write0=0 to 2000, 1=0 to 4,000, 2=0 to 5,000, 3=0 to 10,000, 4=0 to 20,000
MV28600IN16 is Temperaturedefault FALSE; LCD page 11Write0=False, 1=True
MV28601IN16 is Humiditydefault FALSE; LCD page 12Write0=False, 1=True
MV28602IN16 is CO2default FALSE; LCD page 12Write0=False, 1=True
MV28603IN16 is Pressuredefault FALSE; LCD page 12Write0=False, 1=True
MV28604IN17 is Temperaturedefault FALSE; LCD page 12Write0=False, 1=True
MV28605IN17 is Humiditydefault FALSE; LCD page 13Write0=False, 1=True
MV28606IN17 is CO2default FALSE; LCD page 13Write0=False, 1=True
MV28607IN17 is Pressuredefault FALSE; LCD page 13Write0=False, 1=True
MV28523VF2 InputVolt Free Input (IN6); default Off; LCD page 3Write0=Off, 1=On
MV28653VF2 ModeVolt Free 2 Mode; default Fan Boost; LCD page 19Write0=None, 1=Fan Boost, 2=Heating Boost, 3=Extract Setback, 4=Supply Setback
AV28526Effective SetpointCurrent Effective Setpoint; Range 0-100 deg C; default 22; LCD page 45°CRead
AV28527Eff CO2Current Effective CO2 of the Room; Range 0-100 ppm; default 0.1ppmRead
AV28528Effective Zone HumidityCurrent Effective Humidity of the Room; Range 0-100 %RH; default 0.1%RHRead
AV28529Effective PressureCurrent Effective Room Pressure; Range 0-100 Pa; default 0; LCD page 46PaRead
AV28634Frost Protection TemperatureMinimum Temperature for Frost protection to start; Range 5-15 deg C; default 5°CWrite
AV28691Frost Protection Fan OffFrost protection fan run-on timer; Range 0-600 seconds; default 300sWrite
MV28637Hibernate Modedefault Off; LCD page 17Write0=Off, 1=On
MV28642NFC EnableNight Free Cooling Enable; default Off; LCD page 18Write0=Off, 1=On
MV28643NFC Schedule ActiveNight Free Cooling Schedule Input; default Off; LCD page 18Write0=Off, 1=On
AV28641NFC Fan SpeedNight Free Cooling Fan Speed; Range 0-100%; default 60; LCD page 54%Write
AV28644NFC Min TempNight Free Cooling Minimum Temperature; Range 0-100 deg C; default 12°CWrite
MV28647Purge Enabledefault Off; LCD page 18Write0=Off, 1=On
MV28993Purge Schedule ActiveSet the purge schedule; default Off; LCD page 27Write0=Off, 1=On
AV28649Purge Fan SpeedRange 0-100%; default 60; LCD page 55%Write
AV28650Purge Low SA-T SetpointPurge Maximum Temperature; Range 5-15 deg C; default 12; LCD page 56°CWrite
MV28539RM199 StatusStatus of Network Sensor 1; default 0; LCD page 2Read0=False, 1=True
MV28544RM199 Fan Speed RequestRM199 Fan Speed; default Auto; LCD page 4Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28545RM199 Occupancydefault Occupied; LCD page 5Write0=Occupied, 1=Unoccupied
MV28546RM200 StatusStatus of Network Sensor 2; default 0; LCD page 5Read0=False, 1=True
MV28551RM200 Fan Speed RequestRM200 Fan Speed; default Auto; LCD page 5Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28552RM200 Occupancydefault Occupied; LCD page 5Write0=Occupied, 1=Unoccupied
MV28553RM201 StatusStatus of Network Sensor 3; default 0; LCD page 6Read0=False, 1=True
MV28558RM201 Fan Speed RequestRM201 Fan Speed; default Auto; LCD page 6Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28559RM201 Occupancydefault Occupied; LCD page 6Write0=Occupied, 1=Unoccupied
MV28560RM202 StatusStatus of Network Sensor 4; default 0; LCD page 6Read0=False, 1=True
MV28565RM202 Fan Speed RequestFan speed override status of RM202; default Auto; LCD page 7Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28566RM202 Occupancydefault Occupied; LCD page 7Write0=Occupied, 1=Unoccupied
MV28567RM203 StatusStatus of Network Sensor 5; default 0; LCD page 7Read0=False, 1=True
MV28572RM203 Fan Speed RequestRM203 Fan Speed; default Auto; LCD page 7Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28573RM203 Occupancydefault Occupied; LCD page 8Write0=Occupied, 1=Unoccupied
MV28574RM204 StatusStatus of Network Sensor 6; default 0; LCD page 8Read0=False, 1=True
MV28579RM204 Fan Speed RequestFan speed override status of RM204; default Auto; LCD page 8Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28580RM204 Occupancydefault Occupied; LCD page 8Write0=Occupied, 1=Unoccupied
MV28581RM205 StatusStatus of Network Sensor 7; default 0; LCD page 9Read0=False, 1=True
MV28586RM205 Fan Speed RequestRM205 Fan Speed; default Auto; LCD page 9Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28587RM205 Occupancydefault Occupied; LCD page 9Write0=Occupied, 1=Unoccupied
MV28588RM206 StatusStatus of Network Sensor 8; default 0; LCD page 9Read0=False, 1=True
MV28593RM206 Fan Speed RequestRM206 Fan Speed; default Auto; LCD page 10Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28594RM206 OccupancyRM205 Occupancy; default Occupied; LCD page 10Write0=Occupied, 1=Unoccupied
AV28592RM206 Sensor SetpointRM206 Setpoint; Range 12-28 deg C; LCD page 37°CWrite
AV28583RM205 Humidity AIRM205 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 37%RHRead
AV28582RM205 Temp AIRM205 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 37°CRead
AV28584RM205 CO2 AIRM205 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 37ppmRead
AV28578RM204 Sensor SetpointRM204 Setpoint; Range 12-28 deg C; LCD page 38°CWrite
AV28577RM204 CO2 AIRM204 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 38ppmRead
AV28576RM204 Humidity AIRM204 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 38%RHRead
AV28575RM204 Temp AIRM204 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 38°CRead
AV28571RM203 Sensor SetpointRM203 Setpoint; Range 12-28 deg C; LCD page 39°CWrite
AV28570RM203 CO2 AIRM203 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 39ppmRead
AV28569RM203 Humidity AIRM203 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 39%RHRead
AV28568RM203 Temp AIRM203 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 39°CRead
AV28564RM202 Sensor SetpointRM202 Setpoint; Range 12-28 deg C; LCD page 39°CWrite
AV28562RM202 Humidity AIRM202 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 40%RHRead
AV28561RM202 Temp AIRM202 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 40°CRead
AV28557RM201 Sensor SetpointRM201 Setpoint; Range 12-28 deg C; LCD page 40°CWrite
AV28563RM202 CO2 AIRM202 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 40ppmRead
AV28556RM201 CO2 AIRM201 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 41ppmRead
AV28555RM201 Humidity AIRM201 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 41%RHRead
AV28554RM201 Temp AIRM201 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 41°CRead
AV28540RM199 Temp AIRM199 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 47°CRead
AV28541RM199 Humidity AIRM199 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 47%RHRead
AV28542RM199 CO2 AIRM199 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 47ppmRead
AV28549RM200 CO2 AIRM200 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 48ppmRead
AV28547RM200 Temp AIRM200 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 48°CRead
AV28548RM200 Humidity AIRM200 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 48%RHRead
AV28543RM199 Sensor SetpointRM199 Setpoint; Range 12-28 deg C; LCD page 48°CWrite
AV28550RM200 Sensor SetpointRM200 Setpoint; Range 12-28 deg C; LCD page 49°CWrite
AV28585RM205 Sensor SetpointRM205 Setpoint; Range 12-28 deg C; LCD page 49°CWrite
AV28589RM206 Temp AIRM206 Temperature Sensor Analogue Input; Range 0-40 deg C; LCD page 50°CRead
AV28590RM206 Humidity AIRM206 Humidity Sensor Analogue Input; Range 0-100 %RH; LCD page 50%RHRead
AV28591RM206 CO2 AIRM206 CO2 Sensor Analogue Input; Range 0-2000 ppm; LCD page 50ppmRead
MV28613BMS Temperature OutputBMS Configuration Output; default Auto; LCD page 15Read0=Auto, 1=None, 2=Heating, 3=Cooling
MV28512IN16 CO2 SensorIN16 CO2; Range 0-2000 ppm; default 0ppm; LCD page 42ppmRead
MV28513IN16 Temperature SensorIN16 Temperature; Range 0-50 deg C; LCD page 43°CRead
AV28514IN16 Humidity SensorIN16 Relative Humidity; Range 0-100% RH; default 0%; LCD page 43%RHRead
AV28515IN16 Pressure SensorIN16 Pressure; Range 0 to 2000 Pa; default 0 PaPaRead
AV28516IN17 CO2 SensorIN17 CO2; Range 0 to 2,000 ppm; default 0 ppmppmRead
AV28517IN17 Temperature SensorIN17 Temperature; Range 0 to 50 degC; default 0°C; LCD page 44°CRead
AV28518IN17 Humidity SensorIN17 Relative Humidity; Range 0-100 %RH; default 0%; LCD page 44%RHRead
AV28519IN17 Pressure SensorIN17 Pressure; Range 0 to 2000 Pa; default 0 PaPaRead
AV28520IN17 Fan Speed ControlIN17 Fan Speed; Range 0-100%; default 0%; LCD page 44%Read
AV28521IN17 BMS 0-10vRange 0-100%; default 0%; LCD page 45%Read
MV28609Humidity Sensor OperationHumidity Sensor Operation; default Average RH%; LCD page 14Write0=Average RH%, 1=Minimum RH%, 2=Ignore RH%
MV28610CO2 Sensor OperationCO2 Sensor Operation; default Average CO2; LCD page 14Write0=Average CO2, 1=Maximum CO2, 2=Ignore CO2
MV28611Pressure Sensor OperationPressure Sensor Operation; default Average; LCD page 14Write0=Average, 1=Maximum, 2=Ignore
MV28614Ignore PIR Occ SensorsOccupancy Sensor Enabled; default No; LCD page 15Write0=No, 1=Yes
MV28662Occupancy StatusOccupancy mode wo Runon; default Occupied; LCD page 20Read0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28618BMS 0-10v Input0-10V Network Fan speed demand, along with OUT4 output in “ESClassic BMS” mode; Range 0-10 VVWrite
AV28619CO2 SetpointIn-Room CO2 Setpoint; Range 0-2000 ppm; default 650; LCD page 51ppmWrite
AVmin28632Fan Speed Command0-10V Network Fan Speed Demand; Range 0-100 %; default 0%Write
AV28638Humidity SetpointIn-room humidity Setpoint; Range 40-60 %RH; default 50; LCD page 54%RHWrite
AV28646Pressure SetpointStatic Pressure Setpoint; Range 0-1000 Pa; default 400; LCD page 55PaWrite
MV28633Fire AlarmFire Alarm Network Input; default Normal; LCD page 17Read0=Normal, 1=Alarm
MV28675Fire Alarm StateFire Alarm; default Normal; LCD page 24Write0=Normal, 1=Alarm
MV28639Low Temp Alarm ActionLow Supply Temp Action; default Alarm Only; LCD page 17Write0=Alarm Only, 1=Alarm and Stop fans
MVmin28660Reset AlarmReset the Alarms; default Off; LCD page 20Write0=Off, 1=Reset
MVmin28664Active Critical AlarmsCritical Alarm; default Normal; LCD page 21Read0=Normal, 1=Alarm
MV28665Maintenance Alarmdefault Normal; LCD page 21Read0=Normal, 1=Alarm
MV28666Thermal Wheel Alarmdefault Normal; LCD page 21Read0=Normal, 1=Alarm
MV28668Supply Filter Alarmdefault Normal; LCD page 22Read0=Alarm, 1=Normal
MV28669Return Filter Alarmdefault Normal; LCD page 22Read0=Alarm, 1=Normal
MV28670Tacho AlarmXBC Tacho Board Alarm - Fan Fault Alarm; default NormalRead0=Normal, 1=Alarm
MV28671Supply Fan AlarmsSupply Fan Alarm; default Normal; LCD page 22Read0=Alarm, 1=Normal
MV28672Return Fan AlarmsReturn Fan Alarm; default Normal; LCD page 23Read0=Alarm, 1=Normal
MV28667Condensate Alarmdefault Normal; LCD page 23Read0=Alarm, 1=Normal
MV28673Heat Pump Alarmdefault Normal; LCD page 23Read0=Alarm, 1=Normal
MV28674IO Damper Alarmdefault Normal; LCD page 23Read0=Normal, 1=Alarm
MV28676Frost Alarmdefault Normal; LCD page 24Read0=Normal, 1=Alarm
MV28677PAC Board AlarmPAC Board Alarm (BPS, Reverse Cycle DX Only); default NormalRead0=Normal, 1=Alarm
MV28677Sensor AlarmTemperature Sensor Alarm; default Normal; LCD page 24Read0=Normal, 1=Alarm
MV28678Low SA-T AlarmLow Supply Air Temperature Alarm; default Normal; LCD page 25Read0=Normal, 1=Alarm
MV28992Alarm Reset Schedule ActiveSchedule when to reset any alarms; default Off; LCD page 27Write0=Off, 1=Reset
TL1Room Temperature TrendUsed for Trending the Room Temperature; LCD page 35Read
TL2Room CO2 TrendUsed for Trending the Room CO2; LCD page 35Read
TL3Room Humidity TrendTrend of the Room Humidity Input; LCD page 35Read
TL4Setpoint TrendUsed for Trending the Temperature Setpoint; LCD page 36Read
TL5Supply Air Temperature TrendUsed for Trending the Supply Air Temperature; LCD page 36Read
TL6Return Air Temperature TrendUsed for Trending the Extract Air Temperature; LCD page 36Read
TL7Fresh Air Intake TrendTrend of the Intake Air Temperature of the unit; LCD page 36Read
MV28655PID Tuning ResetTuning Reset for PID Loops; default FALSE; LCD page 19Write0=False, 1=True
MV28680Wiring VerificationInternal Factory Testing - Full Functionality; default Off; LCD page 25Write0=Off, 1=On
MV28681Test Mode(Fan)Internal Factory Testing - Fan Only (Resets on Power Cycle); default OffWrite0=Off, 1=On
MV28682Test Mode(Heater)Internal Factory Testing - Heater and Fan (Resets on Power Cycle); default OffWrite0=Off, 1=On
MV28683Test Mode(Overheat)Internal Factory Testing - Heater Only (Resets on Power Cycle); default OffWrite0=Off, 1=On
MV28684Test Mode (DX Heat Only-BPS)Internal Factory Testing - Cooling Only (Resets on Power Cycle); default OffWrite0=Off, 1=On
MV28685Test Mode(Cooling BPS)Internal Factory Testing - Cooling and Fan (Resets on Power Cycle); default OffWrite0=Off, 1=On
MV28507Baud RateCommunication Speed; default 38400; LCD page 27Write0=Auto, 1=1200, 2=9600, 3=19200, 4=38400, 5=76800
MV28679SW-VAC3000-1CSoftware Version Number; default Off; LCD page 28Read0=Off, 1=On
MV28686Default UnitsDefault Measurement Units; default IP; LCD page 28Write0=IP, 1=SI
AV28687Pin CodePin Code for Inbuilt LCD; Range 0-9999; default 0; LCD page 58Write
AV29505Device OIDDevice Instance Number; Range 0-4194302; default Unique; LCD page 58Write
AV29506AddressDevice MS/TP Address; Range 4-127; default 4; LCD page 58Write
Object ID lookup: Nuaire EcoSmart Connect control, 2026 object list point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list

How many BACnet points does the Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list have?

This list has 207 BACnet objects: 85 analog values, 4 schedules, 111 multi-state values, 7 trend logs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list BACnet points are writable?

119 of the 207 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list BACnet documentation?

The source is Ecosmart Connect (CO) Control Operation Manual, BACnet object list (672059), revision 2026-07-27, published free by Nuaire at https://info.nuaire.co.uk/IandM/672059.pdf.

What are the minimum BACnet points to integrate the Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list?

Start with MV 28511 Unit Enable (Unit enable (0 = Off, 1 = On)); AV 28632 Fan Speed Command (Fan speed demand, 0-100 %); AV 28654 Software Setpoint (Temperature setpoint from the network, 12-28 °C); MV 28660 Reset Alarm (Alarm reset (1 = Reset)); MV 28536 Fan Command (Fan enable output (OUT10) status); AV 28501 Supply Air Temperature (Supply air temperature); AV 28502 Fresh Air Intake (Fresh (outdoor) air temperature); AV 28503 Return Air Temperature (Return air temperature); MV 28538 Unit Fault Status (Fault relay status (0 = Alarm, 1 = Normal)); MV 28664 Active Critical Alarms (Critical alarm active (1 = Alarm)).

How do I enable BMS control of the Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list?

The unit runs when any enable source is active: the Unit Enable MSV (local display or network), volt-free inputs, night cooling, the internal enable schedule, a fan speed override or a room module PIR. When the enable is removed the unit runs on for the run-on time.

Can the BMS supply sensor values to the Nuaire EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list?

MV 28612 Setpoint Operation picks whether the last changed setpoint wins, software only, or last changed with a timeout.

How do I check these points on the real EcoSmart Connect (CO) control (XBOXER XBC, BPS, BOXER), 2026 object list?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Nuaire BACnet points lists

Source: Ecosmart Connect (CO) Control Operation Manual, BACnet object list · 672059 · rev. 2026-07-27. Object names, instances and units are reproduced as published; descriptions are our own.