Energy recovery ventilation unit controller · BACnet points list

Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list BACnet points list

Updated 12 November 2026

Short answer

The EcoSmart Connect controller is a BACnet MS/TP device (default MAC address 4) built into Nuaire XBC, BPS and BOXER units. Nuaire's object list has 192 numbered objects, all AVs and multistate values in the 28501-28693 range: unit enable, network setpoint and fan speed command, sensor readings from up to eight RM room modules, configuration selections, and alarm MSVs. Two schedules and seven trend logs are listed without instance numbers and are not included here.

This page lists 192 BACnet objects for the Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list — 117 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Nuaire’s own free documentation, linked below.

Manufacturer
Nuaire
Model
EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list
Equipment
Energy recovery ventilation unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
192 (117 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Nuaire EcoSmart Connect, EcoSmart Connect, ESC, XBOXER XBC, XBC, BPS H-CO, Boxer BPS, BOXER, Nuaire 672040
Source document
EcoSmart Connect Control Operation Manual, 1.36 BACnet Object List (By Category) · 672040 · rev. 2022-02-15
Download CSV 192 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Nuaire’s current documentation and the live device before use. Not official Nuaire information. Terms of use.

BMS integration notes: Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list

Integration in brief

Write MV 28512 Unit Enable to On to run the unit, then set AV 28637 Fan Speed Command (0-100 %) and AV 28669 Network Setpoint. Read the fresh, supply and return air temperatures, MV 28537 Fan Command and the alarm MSVs; MV 28681 resets alarms. Nuaire recommends writing AVs and MSVs at priority 16.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 28512Unit EnableUnit enable (Off / On)Write
AV 28637Fan Speed CommandFan speed demand, 0-100 %Write
AV 28669Network SetpointTemperature setpoint from the network, 12-28Write
MV 28681Alarm ResetAlarm resetWrite
MV 28537Fan CommandFan enable output (OUT10) statusRead
AV 28502Supply Air TemperatureSupply air temperatureRead
AV 28501Fresh Air intakeFresh (outdoor) air temperatureRead
AV 28503Return Air TemperatureReturn air temperatureRead
MV 28539Unit Fault StatusFault relay statusRead
MV 28685Active Critical AlarmsCritical alarm activeRead

Enable & remote start

The unit runs when any enable source is active: the Unit Enable MSV (local display or network), volt-free inputs, night cooling, the weekly schedule, a fan speed override or a room module PIR. When the enable is removed the unit runs on for the run-on time.

Sensors & values from the BMS

MV 28613 Setpoint Operation picks whether the last changed setpoint wins, software only, or last changed with a timeout (AV 28665 Setpoint Timeout). AV 28623 accepts a 0-10 V style fan speed demand from the network.

Network setup

Watch out for

Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

192 of 192 shown
Type
AnalogMulti-state
Access
Show
Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list BACnet Points List
DescriptionStates
MV28508Baud RateBaud rate; default Auto; LCD page 1WriteAuto / 1200 / 9600 / 19200 / 38400 / 76800
MV28509Unit SelectionUnit Type; default State 0; LCD page 1Write0=XBC, 1=BPS, 2=BOXER
MV28510Heating TypeSelection of Heating Type; default State 0; LCD page 1Write0=None, 1=LPHW, 2=Electric Heater, 3=3rd Party
MV28511Cooling TypeSelection of Cooling Type; default State 0; LCD page 2Write0=None, 1=Chilled Water, 2=3rd Party, 3=Reverse Cycle DX
MVmin28512Unit EnableEnable the Unit; default Off; LCD page 2WriteOff / On
MVmin28539Unit Fault StatusFault Relay (Output OUT9); default Normal; LCD page 2ReadAlarm / Normal / Hold
MV28540RM199 StatusStatus of Network Sensor 1; default FALSE; LCD page 2ReadFalse / True / Hold
MV28523Alarm Circuit 1default Normal; LCD page 3ReadAlarm / Normal / Hold
MV28524Alarm Circuit 2default Normal; LCD page 3ReadAlarm / Normal / Hold
MV28525SL InputSL Enable (Input IN5); default Off; LCD page 3ReadOff / On / Hold
MV28538Cooling DemandCooling Demand Status; default Off; LCD page 3ReadOff / On / Hold
MV28526SL2 InputSL2 Enable (Input IN6); default Off; LCD page 4ReadOff / On / Hold
MV28535Bypass DamperBypass damper Status (Output OUT6); default Inactive; LCD page 4ReadInactive / Active / Hold
MV28536Heat DemandHeat / Recirc Demand (Output OUT8); default Off; LCD page 4ReadOff / On / Hold
MVmin28537Fan CommandFan Enable Command (Output OUT10); default On; LCD page 4ReadOff / On / Hold
MV28547RM200 StatusStatus of Network Sensor 2; default FALSE; LCD page 5ReadFalse / True / Hold
MV28554RM201 StatusStatus of Network Sensor 3; default FALSE; LCD page 5ReadFalse / True / Hold
MV28561RM202 StatusStatus of Network Sensor 4; default FALSE; LCD page 5ReadFalse / True / Hold
MV28568RM203 StatusStatus of Network Sensor 5; default FALSE; LCD page 5ReadFalse / True / Hold
MV28575RM204 StatusStatus of Network Sensor 6; default FALSE; LCD page 6ReadFalse / True / Hold
MV28582RM205 StatusStatus of Network Sensor 7; default FALSE; LCD page 6ReadFalse / True / Hold
MV285990-10v Press Range for IN16 & IN170-10v Pressure Range Select for IN16 & IN17; default State 0Write0=0-25, 1=0-50, 2=0-100, 3=0-300, 4=0-500, 5=0-1000, 6=0-1600, 7=0-2500, 8=0-3000
MV286000-10v CO2 Range for IN16 & IN170-10v CO2 Range Select for IN16 & IN17; default State 0Write0=0-2000, 1=0-4000, 2=0-5000, 3=0-10000, 4=0-20000
MV28601IN16 is TemperatureIs IN16 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28602IN16 is HumidityIs IN16 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28603IN16 is CO2Is IN16 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28604IN16 is PressureIs IN16 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28605IN17 is TemperatureIs IN17 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28606IN17 is HumidityIs IN17 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28607IN17 is CO2Is IN17 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
MV28608IN17 is PressureIs IN17 setup as =; default FALSE; LCD page 6WriteFalse / True / Hold
AV28545RM199 Fan Speed RequestRM199 Fan Speed; LCD page 6Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28546RM199 OccupancyLCD page 6Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28552RM200 Fan Speed RequestRM200 Fan Speed; LCD page 6Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28564RM202 CO2 AIRM202 CO2 Sensor Analogue Input; Range 0-2000; LCD page 6Read
AV28565RM202 Sensor SetpointRM202 Setpoint; Range 0-100; LCD page 6Write
AV28571RM203 CO2 AIRM203 CO2 Sensor Analogue Input; Range 0-2000; LCD page 6Read
AV28583RM205 Temp AIRM205 Temperature Sensor Analogue Input; Range 0-40; LCD page 6Read
AV28584RM205 Humidity AIRM205 Humidity Sensor Analogue Input; Range 0-100; LCD page 6Read
AV28590RM206 Temp AIRM206 Temperature Sensor Analogue Input; Range 0-40; LCD page 6Read
MV28589RM206 StatusStatus of Network Sensor 8; default FALSE; LCD page 7ReadFalse / True / Hold
MV28596IN16 FunctionIN16 Function Input; default State 0; LCD page 7Write0=None, 1=N/A, 2=N/A, 3=0-10v CO2 Sensor, 4=0-10v Temp Sensor, 5=0-10v Hum Sensor, 6=0-10v Press Sensor
MV28597IN17 FunctionIN17 Function Input; default State 0; LCD page 7Write0=None, 1=FS Control, 2=0-10v BMS, 3=0-10v CO2 Sensor, 4=0-10v Temp Sensor, 5=0-10v Hum Sensor, 6=0-10v Press Sensor
MV285980-10v Temp Range for IN16 & IN170-10v Temp Range Select for IN16 & IN17; default State 0WriteState 0 / State 1 / State 2 / State 3 / State 4
AV28553RM200 OccupancyLCD page 7Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28572RM203 Sensor SetpointRM203 Setpoint; Range 0-100; LCD page 7Write
AV28591RM206 Humidity AIRM206 Humidity Sensor Analogue Input; Range 0-100; LCD page 7Read
MV28609Temp Sensor OperationTemperature Sensor Operation; default State 0; LCD page 8Write0=RM Average, 1=Return Air Only, 2=RM & Return Air Average
MV28610Humidity Sensor OperationHumidity Sensor Operation; default State 0; LCD page 8Write0=Average, 1=Minimum, 2=Ignore
MV28611CO2 Sensor OperationCO2 Sensor Operation; default State 0; LCD page 8Write0=Average, 1=Minimum, 2=Ignore
MV28612Pressure Sensor OperationPressure Sensor Operation; default State 0; LCD page 8Write0=Average, 1=Minimum, 2=Ignore
MV28613Setpoint OperationSetpoint Input Operation; default State 0; LCD page 9Write0=Last Changed, 1=Software Only, 2=Last Changed with timeout
MV28614Supp Heat OutputBMS Configuration Input; default State 0; LCD page 9Write0=Auto, 1=None, 2=Heating, 3=Cooling
MV28615Fan Speed Override ControlFan Speed Override Operation; default State 0; LCD page 9Write0=Override has Priority, 1=Revert to Auto after Timeout
MV28616Occ Sensor EnableOccupancy Sensor Enabled; default No; LCD page 9WriteNo / Yes
MV28617OA Damper InterlockIO Damper Fitted; default No; LCD page 10WriteNo / Yes
MV28618Tacho Board Fitteddefault No; LCD page 10WriteNo / Yes
MV28619Control TypeTemperature Control Selection - State 0 (Supply Temp Control / State 1 (Return Temp Control)WriteState 0 / State 1
MV28620Fan ConfigFan Configuration for Boxer Units; default State 2; LCD page 10Write0=Supply Only, 1=Extract Only, 2=Both
MV28624Fan Off DelayAuto Run-On; default Off; LCD page 11WriteOff / On
MV28626Damper Override LVManual Damper override; default State 0; LCD page 11Write0=Auto, 1=HX, 2=Bypass
MV28635Fan BoostEnable Fan Boost; default Off; LCD page 11WriteOff / On
MV28638Fire AlarmFire Alarm Network Input; default Normal; LCD page 11WriteNormal / Alarm
MV28643Hibernate Modedefault Off; LCD page 12WriteOff / On
MV28647Low Temp Alarm ActionLow Supply Temp Action; default State 0; LCD page 12Write0=Alarm Only, 1=Alarm & Stop Fans
MV28651NFC SchNight Cooling Sampling Schedule; default Off; LCD page 12WriteOff / On
MV28652NFC Sch EnableNight Cooling Schedule Enable; default Off; LCD page 12WriteOff / On
MV28653Cooling Output TypeOUT4 Mode Selection; default State 0; LCD page 13Write0=Cooling Demand, 1=ESClassic BMS
MV28655PurgePurge Enable; default Off; LCD page 13WriteOff / On
MV28656Purge CommandPurge Schedule; default Off; LCD page 13WriteOff / On
MV28668SL2 ModeSwitch Live 2 Mode; default State 0; LCD page 13Write0=None, 1=Fan Boost, 2=Heating Boost, 3=Extract Setback
MV28633EF Setback from SFSetback Speed of Extract from Supply for Positive Pressure; default OffWriteOff / On
MV28674PID Tuning ModeTuning Reset for PID Loops; default FALSE; LCD page 14WriteFalse / True / Hold
MV28675Trickle ModeTrickle Mode Enabled; default Off; LCD page 14WriteOff / On
MV28680Local ScheduleUnit Enable (Via Schedule); default On; LCD page 14WriteOff / On
MVmin28681Alarm ResetReset the Alarms; default FALSE; LCD page 14WriteFalse / True / Hold
MV28641Heat BoostEnable heater Function; default Off; LCD page 14WriteOff / On
MV28682Fan ActiveFan Run-on Active; default FALSE; LCD page 15ReadFalse / True / Hold
MV28683Occupancy StatusOccupancy mode wo Runon; default 0; LCD page 15Read0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
MV28684Fan to Damper DelayIO Damper Delay Active; default FALSE; LCD page 15ReadFalse / True / Hold
MVmin28685Active Critical AlarmsCritical Alarm; default Normal; LCD page 15ReadNormal / Alarm
MV28677Re-circ OverrideRe-circulation Override; default State 0; LCD page 15Write0=Auto, 1=Open, 2=Close
MV28686Maintenance Alarmdefault Normal; LCD page 16ReadNormal / Alarm
MV28688Condensate Alarmdefault Normal; LCD page 16ReadNormal / Alarm
MV28689Dirty Pre-filter alarmdefault Normal; LCD page 16ReadNormal / Alarm
MV28692Supply Fan Alarmdefault Normal; LCD page 16ReadNormal / Alarm
MV28690Return Air dirty filter alarmExtract Filter dirty alarm; default Normal; LCD page 17ReadNormal / Alarm
MV28693Return Fan Alarmdefault Normal; LCD page 17ReadNormal / Alarm
MV28687Thermal Wheel Alarmdefault Normal; LCD page 18ReadNormal / Alarm
MV28691Tacho Alarmdefault Normal; LCD page 18ReadNormal / Alarm
AVmin28501Fresh Air intakeFresh air Temperature; Range 0-100; LCD page 25Read
AVmin28502Supply Air TemperatureSupply Air temperature; Range 0-100; LCD page 25Read
AVmin28503Return Air TemperatureRange 0-100; LCD page 25Read
AV28504Room TemperatureRange 0-100; LCD page 25Read
AV28505AddressDevice MS/TP Address; Range 4-127; default 4; LCD page 26Write
AV28506Device OIDDevice Instance Number; default 5; LCD page 26Write
AV28527Effective SetpointCurrent Effective Setpoint; Range 0-100; LCD page 26Read
AV28534Cooling OutputRange 0-100; LCD page 26Read
AV28528Effective CO2Current Effective Room CO2; Range 0-100; LCD page 27Read
AV28529Effective HumidityCurrent Effective Room Humidity; Range 0-100; LCD page 27Read
AV28530Effective PressureCurrent Effective Room Pressure; Range 0-100; LCD page 27Read
AV28531Supply Fan Speed AOSupply Fan Speed Analogue Output; Range 0-10; LCD page 27Read
AV28532Exhaust Fan Speed AOExtract Fan Speed Analogue Output; Range 0-10; LCD page 28Read
AV28533Heating OutputRange 0-100; LCD page 28Read
AV28640Frost Protection TemperatureMinimum Temperature for Frost protection to start; LCD page 28Write
AV28654Duct Static Pressure SetpointPressure Target; Range 0-1500; default 400; LCD page 28Write
AV28513IN15 CO2 SensorRange 0-100; LCD page 28Read
AV28514IN15 Temperature SensorRange 0-100; LCD page 28Read
AV28515IN15 Humidity SensorRange 0-100; LCD page 28Read
AV28516IN15 Pressure SensorRange 0-100; LCD page 28Read
AV28517IN16 CO2 SensorRange 0-100; LCD page 28Read
AV28518IN16 Temperature SensorRange 0-100; LCD page 28Read
AV28519IN16 Humidity SensorRange 0-100; LCD page 28Read
AV28520IN16 Pressure SensorRange 0-100; LCD page 28Read
AV28521IN16 Fan Speed ControlRange 0-100; LCD page 28Read
AV28522IN16 BMS 0-10vRange 0-100; LCD page 28Read
AV28625CO2 SetpointIn-Room CO2 Setpoint; Range 0-200; LCD page 29Write
AV28627DeadbandTemperature Deadband for Supply temperature control; Range 0-10; LCD page 29Write
AV28636Fan Override TimeoutTime period for Fan Override; Range 0-7200; LCD page 29Write
AV28639Frost Protection Fan off DelayDelay Timer for Fan during frost protection; Range 0-600; LCD page 29Write
AV28631Extract Fan Max DemandExtract Fan Maximum Demand; Range 0-100; default 100; LCD page 29Write
AV28632Extract Fan Min DemandExtract Fan Minimum Demand; Range 0-100; default 20; LCD page 29Write
AV28634Extract Fan Setback SpeedSet the speed for the Setback; Range 0-100; default 30Write
AV28541RM199 Temp AIRM199 Temperature Sensor Analogue Input; Range 0-40; LCD page 29Read
AV28542RM199 Humidity AIRM199 Humidity Sensor Analogue Input; Range 0-100; LCD page 29Read
AV28555RM201 Temp AIRM201 Temperature Sensor Analogue Input; Range 0-40; LCD page 29Read
AV28556RM201 Humidity AIRM201 Humidity Sensor Analogue Input; Range 0-100; LCD page 29Read
AV28559RM201 Fan Speed RequestRM201 Fan Speed; LCD page 29Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28560RM201 OccupancyLCD page 29Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28573RM203 Fan Speed RequestRM203 Fan Speed; LCD page 29Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28574RM203 OccupancyLCD page 29Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28578RM204 CO2 AIRM204 CO2 Sensor Analogue Input; Range 0-2000; LCD page 29Read
AV28579RM204 Sensor SetpointRM204 Setpoint; Range 0-100; LCD page 29Write
AV28592RM206 CO2 AIRM206 CO2 Sensor Analogue Input; Range 0-2000; LCD page 29Read
AV28593RM206 Sensor SetpointRM206 Setpoint; Range 0-100; LCD page 29Write
AV28621Alarm DelayA time delay for the alarm signal; Range 0-120; LCD page 30Write
AV28622Auto Run-on Scale Factora multiplier for the run-on timer.; Range 0-10; LCD page 30Write
AV28623BMS 0-10V Input0-10V Network Fan speed demand, along with OUT4 output in "ESClassic BMS" mode; Range 0-10Write
AVmin28637Fan Speed Command0-10V Network Fan Speed Demand; Range 0-100; LCD page 30Write
AV28628Extract Fan Max VoltageExtract Fan Maximum Voltage; Range 0-10; default 10; LCD page 30Write
AV28629Extract Fan Start VoltExtract Fan Minimum Voltage; Range 0-10; default 1; LCD page 30Write
AV28630Extract Fan Boost SpeedRange 0-100; default 100; LCD page 30Write
AV28543RM199 CO2 AIRM199 CO2 Sensor Analogue Input; Range 0-2000; LCD page 30Read
AV28544RM199 Sensor SetpointRM199 Setpoint; Range 0-100; LCD page 30Write
AV28548RM200 Temp AIRM200 Temperature Sensor Analogue Input; Range 0-40; LCD page 30Read
AV28549RM200 Humidity AIRM200 Humidity Sensor Analogue Input; Range 0-100; LCD page 30Read
AV28557RM201 CO2 AIRM201 CO2 Sensor Analogue Input; Range 0-2000; LCD page 30Read
AV28558RM201 Sensor SetpointRM201 Setpoint; Range 0-100; LCD page 30Write
AV28562RM202 Temp AIRM202 Temperature Sensor Analogue Input; Range 0-40; LCD page 30Read
AV28563RM202 Humidity AIRM202 Humidity Sensor Analogue Input; Range 0-100; LCD page 30Read
AV28566RM202 Fan Speed RequestRM202 Fan Speed; LCD page 30Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28567RM202 OccupancyLCD page 30Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28576RM204 Temp AIRM204 Temperature Sensor Analogue Input; Range 0-40; LCD page 30Read
AV28577RM204 Humidity AIRM204 Humidity Sensor Analogue Input; Range 0-100; LCD page 30Read
AV28580RM204 Fan Speed RequestRM204 Fan Speed; LCD page 30Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28581RM204 OccupancyLCD page 30Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28585RM205 CO2 AIRM205 CO2 Sensor Analogue Input; Range 0-2000; LCD page 30Read
AV28586RM205 Sensor SetpointRM205 Setpoint; Range 0-100; LCD page 30Write
AV28594RM206 Fan Speed RequestRM206 Fan Speed; LCD page 30Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28595RM206 OccupancyLCD page 30Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28644SA-T High LimitSupply High Temperature High Limit; Range 40-60; default 50; LCD page 31Write
AV28645Humidity SetpointIn-room humidity Setpoint; Range 40-60; default 50; LCD page 31Write
AV28648SA-T Low LimitSupply Low Temperature Low Limit; Range 5-15; default 8; LCD page 31Write
AV28649Max Auto Run-onRun on Time; Range 0-1200; default 600; LCD page 31Write
AV28550RM200 CO2 AIRM200 CO2 Sensor Analogue Input; Range 0-2000; LCD page 31Read
AV28551RM200 Sensor SetpointRM200 Setpoint; Range 0-100; LCD page 31Write
AV28569RM203 Temp AIRM203 Temperature Sensor Analogue Input; Range 0-40; LCD page 31Read
AV28570RM203 Humidity AIRM203 Humidity Sensor Analogue Input; Range 0-100; LCD page 31Read
AV28587RM205 Fan Speed RequestRM205 Fan Speed; LCD page 31Write0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28588RM205 OccupancyLCD page 31Write0=Occupied, 1=Unoccupied, 2=Bypass, 3=Standby
AV28646Damper DelayRange 0-120; default 0; LCD page 32Write
AV28650NFC Fan SpeedNight Free Cooling Fan Speed; Range 0-100; default 60; LCD page 32Write
AV28657Purge Fan SpeedRange 0-100; default 60; LCD page 32Write
AV28658Purge Low SA-T SetpointPurge Maximum Temperature; Range 30-21; default 5; LCD page 32Write
AV28659Purge Min TempPurge Minimum Temperature; Range 0-30; default 15; LCD page 32Write
AV28642Heat Boost SetpointHeat Boost Temperature Setpoint; Range 30-40; default 35; LCD page 32Write
AV28660RTC Max Supply TempReturn Temp Control Maximum Supply Temp; Range 30-40; default 35Write
AV28661RTC Min Supply TempReturn Temp Control Minimum Supply Temp; Range 10-20; default 12Write
AV28662Run-on (Boost)Run-On (Boost) speed; Range 0-120; default 0; LCD page 33Write
AV28663Run-on (Enable)Run-On (Enable) speed; Range 0-120; default 0; LCD page 33Write
AV28664Setpoint ScheduleRange 12-28; default 0; LCD page 34Write
AV28665Setpoint TimeoutRange 0-7200; default 0; LCD page 34Write
AV28666Supply Fan Max VoltSupply Temperature Max Voltage; Range 0-10; default 10; LCD page 34Write
AV28667Supply Fan Start VoltSupply Temperature Start Voltage; Range 0-100; default 1; LCD page 34Write
AVmin28669Network SetpointNetwork Temperature Setpoint; Range 12-28; default 22; LCD page 35Write
AV28670Supply Fan Boost SpeedSupply Temperature Boost Speed; Range 0-100; default 100; LCD page 35Write
AV28671Supply Fan Max DemandSupply Temperature Max Demand; Range 0-100; default 100; LCD page 35Write
AV28672Supply Fan Min DemandSupply Temperature Min Demand; Range 0-100; default 20; LCD page 35Write
AV28673Trickle DeadbandTrickle Temperature Deadband; Range 0-10; default 5; LCD page 36Write
AV28678Re-circ OffsetRe-circulation offset temperature; Range 0-100; LCD page 40Write
AV28676Fan Start Delay (BPS Only)For R32 Delay; Range 0-300; default 300; LCD page 41Write
MV28679Reverse Cycle Backup Heatingdefault Off; LCD page 42WriteOff / On
Object ID lookup: Nuaire EcoSmart Connect control, 2022 object list point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list

How many BACnet points does the Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list have?

This list has 192 BACnet objects: 113 analog values, 79 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list BACnet points are writable?

117 of the 192 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list BACnet documentation?

The source is EcoSmart Connect Control Operation Manual, 1.36 BACnet Object List (By Category) (672040), revision 2022-02-15, published free by Nuaire at https://info.nuaire.co.uk/IandM/672040.pdf.

What are the minimum BACnet points to integrate the Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list?

Start with MV 28512 Unit Enable (Unit enable (Off / On)); AV 28637 Fan Speed Command (Fan speed demand, 0-100 %); AV 28669 Network Setpoint (Temperature setpoint from the network, 12-28); MV 28681 Alarm Reset (Alarm reset); MV 28537 Fan Command (Fan enable output (OUT10) status); AV 28502 Supply Air Temperature (Supply air temperature); AV 28501 Fresh Air intake (Fresh (outdoor) air temperature); AV 28503 Return Air Temperature (Return air temperature); MV 28539 Unit Fault Status (Fault relay status); MV 28685 Active Critical Alarms (Critical alarm active).

How do I enable BMS control of the Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list?

The unit runs when any enable source is active: the Unit Enable MSV (local display or network), volt-free inputs, night cooling, the weekly schedule, a fan speed override or a room module PIR. When the enable is removed the unit runs on for the run-on time.

Can the BMS supply sensor values to the Nuaire EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list?

MV 28613 Setpoint Operation picks whether the last changed setpoint wins, software only, or last changed with a timeout (AV 28665 Setpoint Timeout). AV 28623 accepts a 0-10 V style fan speed demand from the network.

How do I check these points on the real EcoSmart Connect control (XBOXER XBC, BPS, BOXER), 2022 object list?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Nuaire BACnet points lists

Source: EcoSmart Connect Control Operation Manual, 1.36 BACnet Object List (By Category) · 672040 · rev. 2022-02-15. Object names, instances and units are reproduced as published; descriptions are our own.