Variable frequency drive BACnet IP option module · BACnet points list

Nidec Control Techniques SI-BACnet IP option module BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The SI-BACnet IP is a plug-in option that puts a Control Techniques drive on BACnet IP. It exposes the same kinds of objects as the H300 onboard port (I/O, speed reference, run and reset, output values, PID loops, filter timers, energy meter, ten user-configurable AVs) but numbers the Analog Values differently and adds a multistate drive-status object and two network port objects.

This page lists 58 BACnet objects for the Nidec Control Techniques SI-BACnet IP option module — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Nidec Control Techniques’s documentation hosted by BACnet International, not by Nidec Control Techniques itself, so treat it as unofficial.

Manufacturer
Nidec Control Techniques
Model
SI-BACnet IP option module
Equipment
Variable frequency drive BACnet IP option module
Equipment type
VFDs & pumps
BACnet objects
58 (30 writable)
Transport
BACnet IP
Firmware
01.00.02.06 (PICS)
Also known as
SI-BACnet IP, SI-BACnet, 82400000022600, Control Techniques BACnet/IP module
Source document
SI-BACnet IP PICS · rev. 2024-09-14 (unofficial copy, hosted by BACnet International)
Download CSV 58 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Nidec Control Techniques’s current documentation and the live device before use. Not official Nidec Control Techniques information. Terms of use.

BMS integration notes: Nidec Control Techniques SI-BACnet IP option module

Integration in brief

Command BV 3 Drive Run Fwrd and AV 1 Speed Ref, reset trips with BV 6, and read output frequency, current, power, BV 4 Drive Healthy, MV 1 Drive Status and AV 15 Last Trip.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 3#BV_03 Drive Run FwrdRun forward commandCommand
AV 1#AV_01 Speed RefSpeed reference, HzCommand
BV 6#BV_06 Drive ResetTrip reset (write active)Write
BI 7#BI_07 Drive Binary IP7Drive enable input stateRead
AV 10#AV_10 Output FrequencyOutput frequency, HzRead
AV 9#AV_09 Output CurrentMotor current, ARead
AV 11#AV_11 Output PowerOutput power, kWRead
BV 4#BV_04 Drive HealthyDrive healthy (no trip)Read
MV 1#MSV_01 Drive StatusDrive health and trip stateRead
AV 15#AV_15 Last TripLast trip codeRead

Network setup

Watch out for

Nidec Control Techniques SI-BACnet IP option module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

58 of 58 shown
Type
Multi-state
Access
Show
Nidec Control Techniques SI-BACnet IP option module BACnet Points List
DescriptionStates
AI1#AI_01 Drive Analog IP1Analog input 1 on drive%Read
AI2#AI_02 Drive Analog IP2Analog input 2 on drive%Read
AO1#AO_01 Drive Analog OP1Analog output 1 on drive%Command
AO2#AO_02 Drive Analog OP2Analog output 2 on drive%Command
AVmin1#AV_01 Speed RefFrequency/speed referenceHzCommand
AV2#AV_02 PID1 Dig RefPID 1 digital reference%Command
AV3#AV_03 PID1 Dig FbackPID 1 digital feedback%Command
AV4#AV_04 PID2 Dig RefPID 2 digital reference%Command
AV5#AV_05 PID2 Dig FbackPID 2 digital feedback%Command
AV6#AV_06 Max Speed RefMaximum reference clampHzWrite
AV7#AV_07 User Trip ParamUser tripWrite
AV8#AV_08 Filtr Change(dt)Time between filter changeshWrite
AVmin9#AV_09 Output CurrentMotor output currentARead
AVmin10#AV_10 Output FrequencyDrive output frequencyHzRead
AVmin11#AV_11 Output PowerDrive output powerkWRead
AV12#AV_12 Output TorqueOutput torque, % of full load%Read
AV13#AV_13 Output SpeedMotor speedrpmRead
AV14#AV_14 Drive Status WdDrive status wordRead
AVmin15#AV_15 Last TripLast drive trip codeRead
AV16#AV_16 Nxt Filtr ChTimeTime until next filter changehRead
AV17#AV_17 Enrgy Meter(MWh)Energy meter, MWh partMWhRead
AV18#AV_18 Enrgy Meter(kWh)Energy meter, kWh partkWhRead
AV19#AV_19 PID1 RefPID 1 total reference%Read
AV20#AV_20 PID1 FbackPID 1 total feedback%Read
AV21#AV_21 PID1 OutputPID 1 output%Read
AV22#AV_22 PID2 RefPID 2 total reference%Read
AV23#AV_23 PID2 FbackPID 2 total feedback%Read
AV24#AV_24 PID2 OutputPID 2 output%Read
AV25#AV_25 User ConfigurableUser-selectable drive parameter 1Write
AV26#AV_26 User ConfigurableUser-selectable drive parameter 2Write
AV27#AV_27 User ConfigurableUser-selectable drive parameter 3Write
AV28#AV_28 User ConfigurableUser-selectable drive parameter 4Write
AV29#AV_29 User ConfigurableUser-selectable drive parameter 5Write
AV30#AV_30 User ConfigurableUser-selectable drive parameter 6Write
AV31#AV_31 User ConfigurableUser-selectable drive parameter 7Write
AV32#AV_32 User ConfigurableUser-selectable drive parameter 8Write
AV33#AV_33 User ConfigurableUser-selectable drive parameter 9Write
AV34#AV_34 User ConfigurableUser-selectable drive parameter 10Write
BI1#BI_01 Drive Binary IP1Digital input 1 on drive (bi-directional)Read
BI2#BI_02 Drive Binary IP2Digital input 2 on drive (bi-directional)Read
BI3#BI_03 Drive Binary IP3Digital input 3 on drive (bi-directional)Read
BI4#BI_04 Drive Binary IP4Digital input 4 on driveRead
BI5#BI_05 Drive Binary IP5Digital input 5 on driveRead
BI6#BI_06 Drive Binary IP6Digital input 6 on driveRead
BImin7#BI_07 Drive Binary IP7Drive enable inputRead
BO1#BO_01 Drive Binary OP1Digital output 1 (bi-directional)Command
BO2#BO_02 Drive Binary OP2Digital output 2 (bi-directional)Command
BO3#BO_03 Drive Binary OP3Digital output 3 (bi-directional)Command
BO4#BO_04 Drive Binary OP424 V outputCommand
BO5#BO_05 Drive Binary Rl1Drive relay 1Command
BO6#BO_06 Drive Binary Rl2Drive relay 2Command
BV1#BV_01 Reset Enrgy MetrReset the energy meterWrite
BV2#BV_02 Filtr Change RqdFilter change due; can only be written inactiveWrite
BVmin3#BV_03 Drive Run FwrdRun forward commandCommand
BVmin4#BV_04 Drive HealthyDrive healthy statusRead
BV5#BV_05 Drive WarningDrive warningRead
BVmin6#BV_06 Drive ResetDrive reset; can only be written active from inactiveWrite
MVmin1#MSV_01 Drive StatusDrive health and trip stateRead
Object ID lookup: Nidec Control Techniques SI-BACnet IP option module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SI-BACnet IP option module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nidec Control Techniques SI-BACnet IP option module

How many BACnet points does the Nidec Control Techniques SI-BACnet IP option module have?

This list has 58 BACnet objects: 2 analog inputs, 2 analog outputs, 34 analog values, 7 binary inputs, 6 binary outputs, 6 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nidec Control Techniques SI-BACnet IP option module BACnet points are writable?

30 of the 58 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Nidec Control Techniques SI-BACnet IP option module BACnet documentation?

Nidec Control Techniques does not publish it on its own website. This list comes from SI-BACnet IP PICS, revision 2024-09-14, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/nidec%20control%20techniques%20ltd./PICS%20si-bacnetip_pics.pdf. Ask Nidec Control Techniques or its representative for the current revision.

What are the minimum BACnet points to integrate the Nidec Control Techniques SI-BACnet IP option module?

Start with BV 3 #BV_03 Drive Run Fwrd (Run forward command); AV 1 #AV_01 Speed Ref (Speed reference, Hz); BV 6 #BV_06 Drive Reset (Trip reset (write active)); BI 7 #BI_07 Drive Binary IP7 (Drive enable input state); AV 10 #AV_10 Output Frequency (Output frequency, Hz); AV 9 #AV_09 Output Current (Motor current, A); AV 11 #AV_11 Output Power (Output power, kW); BV 4 #BV_04 Drive Healthy (Drive healthy (no trip)); MV 1 #MSV_01 Drive Status (Drive health and trip state); AV 15 #AV_15 Last Trip (Last trip code).

How do I check these points on the real SI-BACnet IP option module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Nidec Control Techniques BACnet points lists

Source: SI-BACnet IP PICS · rev. 2024-09-14. Object names, instances and units are reproduced as published; descriptions are our own.