Variable frequency drive BACnet IP option module · BACnet points list
Nidec Control Techniques SI-BACnet IP option module BACnet points list
Updated 12 November 2026Unofficial source
The SI-BACnet IP is a plug-in option that puts a Control Techniques drive on BACnet IP. It exposes the same kinds of objects as the H300 onboard port (I/O, speed reference, run and reset, output values, PID loops, filter timers, energy meter, ten user-configurable AVs) but numbers the Analog Values differently and adds a multistate drive-status object and two network port objects.
This page lists 58 BACnet objects for the Nidec Control Techniques SI-BACnet IP option module — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Nidec Control Techniques’s documentation hosted by BACnet International, not by Nidec Control Techniques itself, so treat it as unofficial.
- Manufacturer
- Nidec Control Techniques
- Model
- SI-BACnet IP option module
- Equipment
- Variable frequency drive BACnet IP option module
- Equipment type
- VFDs & pumps
- BACnet objects
- 58 (30 writable)
- Transport
- BACnet IP
- Firmware
- 01.00.02.06 (PICS)
- Also known as
- SI-BACnet IP, SI-BACnet, 82400000022600, Control Techniques BACnet/IP module
- Source document
- SI-BACnet IP PICS · rev. 2024-09-14 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against Nidec Control Techniques’s current documentation and the live device before use. Not official Nidec Control Techniques information. Terms of use.
BMS integration notes: Nidec Control Techniques SI-BACnet IP option module
Command BV 3 Drive Run Fwrd and AV 1 Speed Ref, reset trips with BV 6, and read output frequency, current, power, BV 4 Drive Healthy, MV 1 Drive Status and AV 15 Last Trip.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 3 | #BV_03 Drive Run Fwrd | Run forward command | Command |
| AV 1 | #AV_01 Speed Ref | Speed reference, Hz | Command |
| BV 6 | #BV_06 Drive Reset | Trip reset (write active) | Write |
| BI 7 | #BI_07 Drive Binary IP7 | Drive enable input state | Read |
| AV 10 | #AV_10 Output Frequency | Output frequency, Hz | Read |
| AV 9 | #AV_09 Output Current | Motor current, A | Read |
| AV 11 | #AV_11 Output Power | Output power, kW | Read |
| BV 4 | #BV_04 Drive Healthy | Drive healthy (no trip) | Read |
| MV 1 | #MSV_01 Drive Status | Drive health and trip state | Read |
| AV 15 | #AV_15 Last Trip | Last trip code | Read |
Network setup
- Network Port objects: only foreign-device (BBMD registration) properties are writable.
Watch out for
- BV 6 Drive Reset can only be written active from inactive; BV 2 can only be written inactive.
Nidec Control Techniques SI-BACnet IP option module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | #AI_01 Drive Analog IP1 | Analog input 1 on drive | % | Read | |
| AI | 2 | #AI_02 Drive Analog IP2 | Analog input 2 on drive | % | Read | |
| AO | 1 | #AO_01 Drive Analog OP1 | Analog output 1 on drive | % | Command | |
| AO | 2 | #AO_02 Drive Analog OP2 | Analog output 2 on drive | % | Command | |
| AVmin | 1 | #AV_01 Speed Ref | Frequency/speed reference | Hz | Command | |
| AV | 2 | #AV_02 PID1 Dig Ref | PID 1 digital reference | % | Command | |
| AV | 3 | #AV_03 PID1 Dig Fback | PID 1 digital feedback | % | Command | |
| AV | 4 | #AV_04 PID2 Dig Ref | PID 2 digital reference | % | Command | |
| AV | 5 | #AV_05 PID2 Dig Fback | PID 2 digital feedback | % | Command | |
| AV | 6 | #AV_06 Max Speed Ref | Maximum reference clamp | Hz | Write | |
| AV | 7 | #AV_07 User Trip Param | User trip | Write | ||
| AV | 8 | #AV_08 Filtr Change(dt) | Time between filter changes | h | Write | |
| AVmin | 9 | #AV_09 Output Current | Motor output current | A | Read | |
| AVmin | 10 | #AV_10 Output Frequency | Drive output frequency | Hz | Read | |
| AVmin | 11 | #AV_11 Output Power | Drive output power | kW | Read | |
| AV | 12 | #AV_12 Output Torque | Output torque, % of full load | % | Read | |
| AV | 13 | #AV_13 Output Speed | Motor speed | rpm | Read | |
| AV | 14 | #AV_14 Drive Status Wd | Drive status word | Read | ||
| AVmin | 15 | #AV_15 Last Trip | Last drive trip code | Read | ||
| AV | 16 | #AV_16 Nxt Filtr ChTime | Time until next filter change | h | Read | |
| AV | 17 | #AV_17 Enrgy Meter(MWh) | Energy meter, MWh part | MWh | Read | |
| AV | 18 | #AV_18 Enrgy Meter(kWh) | Energy meter, kWh part | kWh | Read | |
| AV | 19 | #AV_19 PID1 Ref | PID 1 total reference | % | Read | |
| AV | 20 | #AV_20 PID1 Fback | PID 1 total feedback | % | Read | |
| AV | 21 | #AV_21 PID1 Output | PID 1 output | % | Read | |
| AV | 22 | #AV_22 PID2 Ref | PID 2 total reference | % | Read | |
| AV | 23 | #AV_23 PID2 Fback | PID 2 total feedback | % | Read | |
| AV | 24 | #AV_24 PID2 Output | PID 2 output | % | Read | |
| AV | 25 | #AV_25 User Configurable | User-selectable drive parameter 1 | Write | ||
| AV | 26 | #AV_26 User Configurable | User-selectable drive parameter 2 | Write | ||
| AV | 27 | #AV_27 User Configurable | User-selectable drive parameter 3 | Write | ||
| AV | 28 | #AV_28 User Configurable | User-selectable drive parameter 4 | Write | ||
| AV | 29 | #AV_29 User Configurable | User-selectable drive parameter 5 | Write | ||
| AV | 30 | #AV_30 User Configurable | User-selectable drive parameter 6 | Write | ||
| AV | 31 | #AV_31 User Configurable | User-selectable drive parameter 7 | Write | ||
| AV | 32 | #AV_32 User Configurable | User-selectable drive parameter 8 | Write | ||
| AV | 33 | #AV_33 User Configurable | User-selectable drive parameter 9 | Write | ||
| AV | 34 | #AV_34 User Configurable | User-selectable drive parameter 10 | Write | ||
| BI | 1 | #BI_01 Drive Binary IP1 | Digital input 1 on drive (bi-directional) | Read | ||
| BI | 2 | #BI_02 Drive Binary IP2 | Digital input 2 on drive (bi-directional) | Read | ||
| BI | 3 | #BI_03 Drive Binary IP3 | Digital input 3 on drive (bi-directional) | Read | ||
| BI | 4 | #BI_04 Drive Binary IP4 | Digital input 4 on drive | Read | ||
| BI | 5 | #BI_05 Drive Binary IP5 | Digital input 5 on drive | Read | ||
| BI | 6 | #BI_06 Drive Binary IP6 | Digital input 6 on drive | Read | ||
| BImin | 7 | #BI_07 Drive Binary IP7 | Drive enable input | Read | ||
| BO | 1 | #BO_01 Drive Binary OP1 | Digital output 1 (bi-directional) | Command | ||
| BO | 2 | #BO_02 Drive Binary OP2 | Digital output 2 (bi-directional) | Command | ||
| BO | 3 | #BO_03 Drive Binary OP3 | Digital output 3 (bi-directional) | Command | ||
| BO | 4 | #BO_04 Drive Binary OP4 | 24 V output | Command | ||
| BO | 5 | #BO_05 Drive Binary Rl1 | Drive relay 1 | Command | ||
| BO | 6 | #BO_06 Drive Binary Rl2 | Drive relay 2 | Command | ||
| BV | 1 | #BV_01 Reset Enrgy Metr | Reset the energy meter | Write | ||
| BV | 2 | #BV_02 Filtr Change Rqd | Filter change due; can only be written inactive | Write | ||
| BVmin | 3 | #BV_03 Drive Run Fwrd | Run forward command | Command | ||
| BVmin | 4 | #BV_04 Drive Healthy | Drive healthy status | Read | ||
| BV | 5 | #BV_05 Drive Warning | Drive warning | Read | ||
| BVmin | 6 | #BV_06 Drive Reset | Drive reset; can only be written active from inactive | Write | ||
| MVmin | 1 | #MSV_01 Drive Status | Drive health and trip state | Read |
No points match these filters.
Object ID lookup: Nidec Control Techniques SI-BACnet IP option module point IDs by name
AI1#AI_01 Drive Analog IP1AI2#AI_02 Drive Analog IP2AO1#AO_01 Drive Analog OP1AO2#AO_02 Drive Analog OP2AV1#AV_01 Speed RefAV2#AV_02 PID1 Dig RefAV3#AV_03 PID1 Dig FbackAV4#AV_04 PID2 Dig RefAV5#AV_05 PID2 Dig FbackAV6#AV_06 Max Speed RefAV7#AV_07 User Trip ParamAV8#AV_08 Filtr Change(dt)AV9#AV_09 Output CurrentAV10#AV_10 Output FrequencyAV11#AV_11 Output PowerAV12#AV_12 Output TorqueAV13#AV_13 Output SpeedAV14#AV_14 Drive Status WdAV15#AV_15 Last TripAV16#AV_16 Nxt Filtr ChTimeAV17#AV_17 Enrgy Meter(MWh)AV18#AV_18 Enrgy Meter(kWh)AV19#AV_19 PID1 RefAV20#AV_20 PID1 FbackAV21#AV_21 PID1 OutputAV22#AV_22 PID2 RefAV23#AV_23 PID2 FbackAV24#AV_24 PID2 OutputAV25#AV_25 User ConfigurableAV26#AV_26 User ConfigurableAV27#AV_27 User ConfigurableAV28#AV_28 User ConfigurableAV29#AV_29 User ConfigurableAV30#AV_30 User ConfigurableAV31#AV_31 User ConfigurableAV32#AV_32 User ConfigurableAV33#AV_33 User ConfigurableAV34#AV_34 User ConfigurableBI1#BI_01 Drive Binary IP1BI2#BI_02 Drive Binary IP2BI3#BI_03 Drive Binary IP3BI4#BI_04 Drive Binary IP4BI5#BI_05 Drive Binary IP5BI6#BI_06 Drive Binary IP6BI7#BI_07 Drive Binary IP7BO1#BO_01 Drive Binary OP1BO2#BO_02 Drive Binary OP2BO3#BO_03 Drive Binary OP3BO4#BO_04 Drive Binary OP4BO5#BO_05 Drive Binary Rl1BO6#BO_06 Drive Binary Rl2BV1#BV_01 Reset Enrgy MetrBV2#BV_02 Filtr Change RqdBV3#BV_03 Drive Run FwrdBV4#BV_04 Drive HealthyBV5#BV_05 Drive WarningBV6#BV_06 Drive ResetMV1#MSV_01 Drive Status
Integration notes
- Object names are listed as printed, including the #AI_01-style prefix.
- AV numbering differs from the H300 onboard MS/TP list: Speed Ref is AV 1 here and AV 4 on the H300.
- Read-only analog objects are printed R*: only COV-related properties are writable.
- AV 25-34 map any drive parameter; access follows the mapped parameter (printed R/W).
- The PICS also lists Network Port objects #NP_01 and #NP_02; they are not listed as points.
- The PICS gives no state texts for MV 1 Drive Status.
- The PICS says the module only shows the objects the host drive supports, so some objects may be missing on a given drive.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SI-BACnet IP option module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Nidec Control Techniques SI-BACnet IP option module
How many BACnet points does the Nidec Control Techniques SI-BACnet IP option module have?
This list has 58 BACnet objects: 2 analog inputs, 2 analog outputs, 34 analog values, 7 binary inputs, 6 binary outputs, 6 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Nidec Control Techniques SI-BACnet IP option module BACnet points are writable?
30 of the 58 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Nidec Control Techniques SI-BACnet IP option module BACnet documentation?
Nidec Control Techniques does not publish it on its own website. This list comes from SI-BACnet IP PICS, revision 2024-09-14, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/nidec%20control%20techniques%20ltd./PICS%20si-bacnetip_pics.pdf. Ask Nidec Control Techniques or its representative for the current revision.
What are the minimum BACnet points to integrate the Nidec Control Techniques SI-BACnet IP option module?
Start with BV 3 #BV_03 Drive Run Fwrd (Run forward command); AV 1 #AV_01 Speed Ref (Speed reference, Hz); BV 6 #BV_06 Drive Reset (Trip reset (write active)); BI 7 #BI_07 Drive Binary IP7 (Drive enable input state); AV 10 #AV_10 Output Frequency (Output frequency, Hz); AV 9 #AV_09 Output Current (Motor current, A); AV 11 #AV_11 Output Power (Output power, kW); BV 4 #BV_04 Drive Healthy (Drive healthy (no trip)); MV 1 #MSV_01 Drive Status (Drive health and trip state); AV 15 #AV_15 Last Trip (Last trip code).
How do I check these points on the real SI-BACnet IP option module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Nidec Control Techniques BACnet points lists
Source: SI-BACnet IP PICS · rev. 2024-09-14. Object names, instances and units are reproduced as published; descriptions are our own.