Variable frequency drive (HVAC) · BACnet points list
Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The HVAC Drive H300 has BACnet MS/TP on board. Its fixed object list covers drive analog and digital I/O, a commandable speed reference and run-forward command, reset, output current, torque, frequency, speed and power, status word and last trip, two PID loops, filter-change timers, an energy meter and ten user-selectable AVs that map any drive parameter.
This page lists 57 BACnet objects for the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Nidec Control Techniques’s documentation hosted by BACnet International, not by Nidec Control Techniques itself, so treat it as unofficial.
- Manufacturer
- Nidec Control Techniques
- Model
- HVAC Drive H300 (onboard BACnet MS/TP)
- Equipment
- Variable frequency drive (HVAC)
- Equipment type
- VFDs & pumps
- BACnet objects
- 57 (30 writable)
- Transport
- BACnet MS/TP
- Firmware
- V01.05.01.10, V01.05.02.02, V02.00.02.02 (PICS)
- Also known as
- H300, HVAC Drive H300, Control Techniques H300, Nidec H300, H300 BACnet
- Source document
- H300 PICS BACnet V1 R15 · rev. 2023-11-14 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against Nidec Control Techniques’s current documentation and the live device before use. Not official Nidec Control Techniques information. Terms of use.
BMS integration notes: Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP)
Command BV 3 Drive Run Fwrd and AV 4 Speed Ref, reset trips with BV 6, and read output frequency, current, power, BV 4 Drive Healthy and AV 13 Last Trip.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 3 | #BV_03 Drive Run Fwrd | Run forward command | Command |
| AV 4 | #AV_04 Speed Ref | Speed reference, Hz | Command |
| BV 6 | #BV_06 Drive Reset | Trip reset (write active) | Write |
| BI 7 | #BI_07 Drive Binary IP7 | Drive enable input state | Read |
| AV 8 | #AV_08 Output Frequency | Output frequency, Hz | Read |
| AV 6 | #AV_06 Output Current | Motor current, A | Read |
| AV 10 | #AV_10 Output Power | Output power, kW | Read |
| BV 4 | #BV_04 Drive Healthy | Drive healthy (no trip) | Read |
| BV 5 | #BV_05 Drive Warning | Drive warning active | Read |
| AV 13 | #AV_13 Last Trip | Last trip code | Read |
Network setup
- The onboard EIA-485 port is selectable between Modbus RTU and BACnet MS/TP; MS/TP master at 9600, 19200 or 38400 baud.
Watch out for
- BV 6 Drive Reset can only be written active from inactive; BV 2 can only be written inactive.
Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | #AI_01 Drive Analog IP1 | Analog input 1 on drive | % | Read | |
| AI | 2 | #AI_02 Drive Analog IP2 | Analog input 2 on drive | % | Read | |
| AO | 1 | #AO_01 Drive Analog OP1 | Analog output 1 on drive | % | Command | |
| AO | 2 | #AO_02 Drive Analog OP2 | Analog output 2 on drive | % | Command | |
| AVmin | 4 | #AV_04 Speed Ref | Frequency/speed reference | Hz | Command | |
| AV | 5 | #AV_05 Max Speed Ref | Maximum reference clamp | Hz | Write | |
| AVmin | 6 | #AV_06 Output Current | Motor output current | A | Read | |
| AV | 7 | #AV_07 Output Torque | Output torque, % of full load | % | Read | |
| AVmin | 8 | #AV_08 Output Frequency | Drive output frequency | Hz | Read | |
| AV | 9 | #AV_09 Output Speed | Motor speed | rpm | Read | |
| AVmin | 10 | #AV_10 Output Power | Drive output power | kW | Read | |
| AV | 11 | #AV_11 Drive Status Wd | Drive status word | Read | ||
| AV | 12 | #AV_12 User Trip Param | User trip | Write | ||
| AVmin | 13 | #AV_13 Last Trip | Last drive trip code | Read | ||
| AV | 14 | #AV_14 Filtr Change(dt) | Time between filter changes | h | Write | |
| AV | 15 | #AV_15 Nxt Filtr ChTime | Time until next filter change | h | Read | |
| AV | 16 | #AV_16 Enrgy Meter(MWh) | Energy meter, MWh part | MWh | Read | |
| AV | 17 | #AV_17 Enrgy Meter(kWh) | Energy meter, kWh part | kWh | Read | |
| AV | 18 | #AV_18 PID1 Dig Ref | PID 1 digital reference | % | Command | |
| AV | 19 | #AV_19 PID1 Dig Fback | PID 1 digital feedback | % | Command | |
| AV | 20 | #AV_20 PID1 Ref | PID 1 total reference | % | Read | |
| AV | 21 | #AV_21 PID1 Fback | PID 1 total feedback | % | Read | |
| AV | 22 | #AV_22 PID1 Output | PID 1 output | % | Read | |
| AV | 23 | #AV_23 PID2 Dig Ref | PID 2 digital reference | % | Command | |
| AV | 24 | #AV_24 PID2 Dig Fback | PID 2 digital feedback | % | Command | |
| AV | 25 | #AV_25 PID2 Ref | PID 2 total reference | % | Read | |
| AV | 26 | #AV_26 PID2 Fback | PID 2 total feedback | % | Read | |
| AV | 27 | #AV_27 PID2 Output | PID 2 output | % | Read | |
| AV | 28 | #AV_28 User Sel 29.010 | User-selectable parameter 1 (set in Pr 29.010) | Write | ||
| AV | 29 | #AV_29 User Sel 29.011 | User-selectable parameter 2 (set in Pr 29.011) | Write | ||
| AV | 30 | #AV_30 User Sel 29.012 | User-selectable parameter 3 (set in Pr 29.012) | Write | ||
| AV | 31 | #AV_31 User Sel 29.013 | User-selectable parameter 4 (set in Pr 29.013) | Write | ||
| AV | 32 | #AV_32 User Sel 29.014 | User-selectable parameter 5 (set in Pr 29.014) | Write | ||
| AV | 33 | #AV_33 User Sel 29.015 | User-selectable parameter 6 (set in Pr 29.015) | Write | ||
| AV | 34 | #AV_34 User Sel 29.016 | User-selectable parameter 7 (set in Pr 29.016) | Write | ||
| AV | 35 | #AV_35 User Sel 29.017 | User-selectable parameter 8 (set in Pr 29.017) | Write | ||
| AV | 36 | #AV_36 User Sel 29.018 | User-selectable parameter 9 (set in Pr 29.018) | Write | ||
| AV | 37 | #AV_37 User Sel 29.019 | User-selectable parameter 10 (set in Pr 29.019) | Write | ||
| BI | 1 | #BI_01 Drive Binary IP1 | Digital input 1 on drive (bi-directional) | Read | ||
| BI | 2 | #BI_02 Drive Binary IP2 | Digital input 2 on drive (bi-directional) | Read | ||
| BI | 3 | #BI_03 Drive Binary IP3 | Digital input 3 on drive (bi-directional) | Read | ||
| BI | 4 | #BI_04 Drive Binary IP4 | Digital input 4 on drive | Read | ||
| BI | 5 | #BI_05 Drive Binary IP5 | Digital input 5 on drive | Read | ||
| BI | 6 | #BI_06 Drive Binary IP6 | Digital input 6 on drive | Read | ||
| BImin | 7 | #BI_07 Drive Binary IP7 | Drive enable input | Read | ||
| BO | 1 | #BO_01 Drive Binary OP1 | Digital output 1 (bi-directional) | Command | ||
| BO | 2 | #BO_02 Drive Binary OP2 | Digital output 2 (bi-directional) | Command | ||
| BO | 3 | #BO_03 Drive Binary OP3 | Digital output 3 (bi-directional) | Command | ||
| BO | 4 | #BO_04 Drive Binary OP4 | 24 V output | Command | ||
| BO | 5 | #BO_05 Drive Binary Rl1 | Drive relay 1 | Command | ||
| BO | 6 | #BO_06 Drive Binary Rl2 | Drive relay 2 | Command | ||
| BV | 1 | #BV_01 Reset Enrgy Metr | Reset the energy meter | Write | ||
| BV | 2 | #BV_02 Filtr Change Rqd | Filter change due; can only be written inactive | Write | ||
| BVmin | 3 | #BV_03 Drive Run Fwrd | Run forward command | Command | ||
| BVmin | 4 | #BV_04 Drive Healthy | Drive healthy status | Read | ||
| BVmin | 5 | #BV_05 Drive Warning | Drive warning | Read | ||
| BVmin | 6 | #BV_06 Drive Reset | Drive reset; can only be written active from inactive | Write |
No points match these filters.
Object ID lookup: Nidec Control Techniques HVAC Drive H300 point IDs by name
AI1#AI_01 Drive Analog IP1AI2#AI_02 Drive Analog IP2AO1#AO_01 Drive Analog OP1AO2#AO_02 Drive Analog OP2AV4#AV_04 Speed RefAV5#AV_05 Max Speed RefAV6#AV_06 Output CurrentAV7#AV_07 Output TorqueAV8#AV_08 Output FrequencyAV9#AV_09 Output SpeedAV10#AV_10 Output PowerAV11#AV_11 Drive Status WdAV12#AV_12 User Trip ParamAV13#AV_13 Last TripAV14#AV_14 Filtr Change(dt)AV15#AV_15 Nxt Filtr ChTimeAV16#AV_16 Enrgy Meter(MWh)AV17#AV_17 Enrgy Meter(kWh)AV18#AV_18 PID1 Dig RefAV19#AV_19 PID1 Dig FbackAV20#AV_20 PID1 RefAV21#AV_21 PID1 FbackAV22#AV_22 PID1 OutputAV23#AV_23 PID2 Dig RefAV24#AV_24 PID2 Dig FbackAV25#AV_25 PID2 RefAV26#AV_26 PID2 FbackAV27#AV_27 PID2 OutputAV28#AV_28 User Sel 29.010AV29#AV_29 User Sel 29.011AV30#AV_30 User Sel 29.012AV31#AV_31 User Sel 29.013AV32#AV_32 User Sel 29.014AV33#AV_33 User Sel 29.015AV34#AV_34 User Sel 29.016AV35#AV_35 User Sel 29.017AV36#AV_36 User Sel 29.018AV37#AV_37 User Sel 29.019BI1#BI_01 Drive Binary IP1BI2#BI_02 Drive Binary IP2BI3#BI_03 Drive Binary IP3BI4#BI_04 Drive Binary IP4BI5#BI_05 Drive Binary IP5BI6#BI_06 Drive Binary IP6BI7#BI_07 Drive Binary IP7BO1#BO_01 Drive Binary OP1BO2#BO_02 Drive Binary OP2BO3#BO_03 Drive Binary OP3BO4#BO_04 Drive Binary OP4BO5#BO_05 Drive Binary Rl1BO6#BO_06 Drive Binary Rl2BV1#BV_01 Reset Enrgy MetrBV2#BV_02 Filtr Change RqdBV3#BV_03 Drive Run FwrdBV4#BV_04 Drive HealthyBV5#BV_05 Drive WarningBV6#BV_06 Drive Reset
Integration notes
- Object names are listed as printed, including the #AI_01-style prefix.
- AV 28-37 map drive parameters chosen in Pr 29.010-29.019; their access follows the mapped parameter (printed R/W).
- Binary I/O 1-3 are bi-directional; each can be an input or an output at a time.
- The PICS prints the BV descriptions copied from the BO rows; BV descriptions here follow the object names.
- The SI-BACnet IP option module uses a different AV numbering (see that list).
- Object instantiation is static; objects cannot be created or deleted.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HVAC Drive H300 (onboard BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP)
How many BACnet points does the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) have?
This list has 57 BACnet objects: 2 analog inputs, 2 analog outputs, 34 analog values, 7 binary inputs, 6 binary outputs, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet points are writable?
30 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet documentation?
Nidec Control Techniques does not publish it on its own website. This list comes from H300 PICS BACnet V1 R15, revision 2023-11-14, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/nidec%20control%20techniques%20ltd./H300_PICS_BACNET_V1_R15.pdf. Ask Nidec Control Techniques or its representative for the current revision.
What are the minimum BACnet points to integrate the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP)?
Start with BV 3 #BV_03 Drive Run Fwrd (Run forward command); AV 4 #AV_04 Speed Ref (Speed reference, Hz); BV 6 #BV_06 Drive Reset (Trip reset (write active)); BI 7 #BI_07 Drive Binary IP7 (Drive enable input state); AV 8 #AV_08 Output Frequency (Output frequency, Hz); AV 6 #AV_06 Output Current (Motor current, A); AV 10 #AV_10 Output Power (Output power, kW); BV 4 #BV_04 Drive Healthy (Drive healthy (no trip)); BV 5 #BV_05 Drive Warning (Drive warning active); AV 13 #AV_13 Last Trip (Last trip code).
How do I check these points on the real HVAC Drive H300 (onboard BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Nidec Control Techniques BACnet points lists
Source: H300 PICS BACnet V1 R15 · rev. 2023-11-14. Object names, instances and units are reproduced as published; descriptions are our own.