Variable frequency drive (HVAC) · BACnet points list

Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The HVAC Drive H300 has BACnet MS/TP on board. Its fixed object list covers drive analog and digital I/O, a commandable speed reference and run-forward command, reset, output current, torque, frequency, speed and power, status word and last trip, two PID loops, filter-change timers, an energy meter and ten user-selectable AVs that map any drive parameter.

This page lists 57 BACnet objects for the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Nidec Control Techniques’s documentation hosted by BACnet International, not by Nidec Control Techniques itself, so treat it as unofficial.

Manufacturer
Nidec Control Techniques
Model
HVAC Drive H300 (onboard BACnet MS/TP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
57 (30 writable)
Transport
BACnet MS/TP
Firmware
V01.05.01.10, V01.05.02.02, V02.00.02.02 (PICS)
Also known as
H300, HVAC Drive H300, Control Techniques H300, Nidec H300, H300 BACnet
Source document
H300 PICS BACnet V1 R15 · rev. 2023-11-14 (unofficial copy, hosted by BACnet International)
Download CSV 57 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Nidec Control Techniques’s current documentation and the live device before use. Not official Nidec Control Techniques information. Terms of use.

BMS integration notes: Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP)

Integration in brief

Command BV 3 Drive Run Fwrd and AV 4 Speed Ref, reset trips with BV 6, and read output frequency, current, power, BV 4 Drive Healthy and AV 13 Last Trip.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 3#BV_03 Drive Run FwrdRun forward commandCommand
AV 4#AV_04 Speed RefSpeed reference, HzCommand
BV 6#BV_06 Drive ResetTrip reset (write active)Write
BI 7#BI_07 Drive Binary IP7Drive enable input stateRead
AV 8#AV_08 Output FrequencyOutput frequency, HzRead
AV 6#AV_06 Output CurrentMotor current, ARead
AV 10#AV_10 Output PowerOutput power, kWRead
BV 4#BV_04 Drive HealthyDrive healthy (no trip)Read
BV 5#BV_05 Drive WarningDrive warning activeRead
AV 13#AV_13 Last TripLast trip codeRead

Network setup

Watch out for

Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

57 of 57 shown
Type
Access
Show
Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet Points List
DescriptionStates
AI1#AI_01 Drive Analog IP1Analog input 1 on drive%Read
AI2#AI_02 Drive Analog IP2Analog input 2 on drive%Read
AO1#AO_01 Drive Analog OP1Analog output 1 on drive%Command
AO2#AO_02 Drive Analog OP2Analog output 2 on drive%Command
AVmin4#AV_04 Speed RefFrequency/speed referenceHzCommand
AV5#AV_05 Max Speed RefMaximum reference clampHzWrite
AVmin6#AV_06 Output CurrentMotor output currentARead
AV7#AV_07 Output TorqueOutput torque, % of full load%Read
AVmin8#AV_08 Output FrequencyDrive output frequencyHzRead
AV9#AV_09 Output SpeedMotor speedrpmRead
AVmin10#AV_10 Output PowerDrive output powerkWRead
AV11#AV_11 Drive Status WdDrive status wordRead
AV12#AV_12 User Trip ParamUser tripWrite
AVmin13#AV_13 Last TripLast drive trip codeRead
AV14#AV_14 Filtr Change(dt)Time between filter changeshWrite
AV15#AV_15 Nxt Filtr ChTimeTime until next filter changehRead
AV16#AV_16 Enrgy Meter(MWh)Energy meter, MWh partMWhRead
AV17#AV_17 Enrgy Meter(kWh)Energy meter, kWh partkWhRead
AV18#AV_18 PID1 Dig RefPID 1 digital reference%Command
AV19#AV_19 PID1 Dig FbackPID 1 digital feedback%Command
AV20#AV_20 PID1 RefPID 1 total reference%Read
AV21#AV_21 PID1 FbackPID 1 total feedback%Read
AV22#AV_22 PID1 OutputPID 1 output%Read
AV23#AV_23 PID2 Dig RefPID 2 digital reference%Command
AV24#AV_24 PID2 Dig FbackPID 2 digital feedback%Command
AV25#AV_25 PID2 RefPID 2 total reference%Read
AV26#AV_26 PID2 FbackPID 2 total feedback%Read
AV27#AV_27 PID2 OutputPID 2 output%Read
AV28#AV_28 User Sel 29.010User-selectable parameter 1 (set in Pr 29.010)Write
AV29#AV_29 User Sel 29.011User-selectable parameter 2 (set in Pr 29.011)Write
AV30#AV_30 User Sel 29.012User-selectable parameter 3 (set in Pr 29.012)Write
AV31#AV_31 User Sel 29.013User-selectable parameter 4 (set in Pr 29.013)Write
AV32#AV_32 User Sel 29.014User-selectable parameter 5 (set in Pr 29.014)Write
AV33#AV_33 User Sel 29.015User-selectable parameter 6 (set in Pr 29.015)Write
AV34#AV_34 User Sel 29.016User-selectable parameter 7 (set in Pr 29.016)Write
AV35#AV_35 User Sel 29.017User-selectable parameter 8 (set in Pr 29.017)Write
AV36#AV_36 User Sel 29.018User-selectable parameter 9 (set in Pr 29.018)Write
AV37#AV_37 User Sel 29.019User-selectable parameter 10 (set in Pr 29.019)Write
BI1#BI_01 Drive Binary IP1Digital input 1 on drive (bi-directional)Read
BI2#BI_02 Drive Binary IP2Digital input 2 on drive (bi-directional)Read
BI3#BI_03 Drive Binary IP3Digital input 3 on drive (bi-directional)Read
BI4#BI_04 Drive Binary IP4Digital input 4 on driveRead
BI5#BI_05 Drive Binary IP5Digital input 5 on driveRead
BI6#BI_06 Drive Binary IP6Digital input 6 on driveRead
BImin7#BI_07 Drive Binary IP7Drive enable inputRead
BO1#BO_01 Drive Binary OP1Digital output 1 (bi-directional)Command
BO2#BO_02 Drive Binary OP2Digital output 2 (bi-directional)Command
BO3#BO_03 Drive Binary OP3Digital output 3 (bi-directional)Command
BO4#BO_04 Drive Binary OP424 V outputCommand
BO5#BO_05 Drive Binary Rl1Drive relay 1Command
BO6#BO_06 Drive Binary Rl2Drive relay 2Command
BV1#BV_01 Reset Enrgy MetrReset the energy meterWrite
BV2#BV_02 Filtr Change RqdFilter change due; can only be written inactiveWrite
BVmin3#BV_03 Drive Run FwrdRun forward commandCommand
BVmin4#BV_04 Drive HealthyDrive healthy statusRead
BVmin5#BV_05 Drive WarningDrive warningRead
BVmin6#BV_06 Drive ResetDrive reset; can only be written active from inactiveWrite
Object ID lookup: Nidec Control Techniques HVAC Drive H300 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HVAC Drive H300 (onboard BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP)

How many BACnet points does the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) have?

This list has 57 BACnet objects: 2 analog inputs, 2 analog outputs, 34 analog values, 7 binary inputs, 6 binary outputs, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet points are writable?

30 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP) BACnet documentation?

Nidec Control Techniques does not publish it on its own website. This list comes from H300 PICS BACnet V1 R15, revision 2023-11-14, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/nidec%20control%20techniques%20ltd./H300_PICS_BACNET_V1_R15.pdf. Ask Nidec Control Techniques or its representative for the current revision.

What are the minimum BACnet points to integrate the Nidec Control Techniques HVAC Drive H300 (onboard BACnet MS/TP)?

Start with BV 3 #BV_03 Drive Run Fwrd (Run forward command); AV 4 #AV_04 Speed Ref (Speed reference, Hz); BV 6 #BV_06 Drive Reset (Trip reset (write active)); BI 7 #BI_07 Drive Binary IP7 (Drive enable input state); AV 8 #AV_08 Output Frequency (Output frequency, Hz); AV 6 #AV_06 Output Current (Motor current, A); AV 10 #AV_10 Output Power (Output power, kW); BV 4 #BV_04 Drive Healthy (Drive healthy (no trip)); BV 5 #BV_05 Drive Warning (Drive warning active); AV 13 #AV_13 Last Trip (Last trip code).

How do I check these points on the real HVAC Drive H300 (onboard BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Nidec Control Techniques BACnet points lists

Source: H300 PICS BACnet V1 R15 · rev. 2023-11-14. Object names, instances and units are reproduced as published; descriptions are our own.