 "manufacturer": "Nidec Control Techniques",
 "manufacturer_slug": "nidec-control-techniques",
 "model": "HVAC Drive H300 (onboard BACnet MS/TP)",
 "model_slug": "hvac-drive-h300",
 "aliases": [
  "H300",
  "HVAC Drive H300",
  "Control Techniques H300",
  "Nidec H300",
  "H300 BACnet"
 ],
 "equipment_type": "Variable frequency drive (HVAC)",
 "applies_to": "Control Techniques HVAC Drive H300 using its onboard BACnet MS/TP port.",
 "summary": "The HVAC Drive H300 has BACnet MS/TP on board. Its fixed object list covers drive analog and digital I/O, a commandable speed reference and run-forward command, reset, output current, torque, frequency, speed and power, status word and last trip, two PID loops, filter-change timers, an energy meter and ten user-selectable AVs that map any drive parameter.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "V01.05.01.10, V01.05.02.02, V02.00.02.02 (PICS)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names are listed as printed, including the #AI_01-style prefix.",
  "AV 28-37 map drive parameters chosen in Pr 29.010-29.019; their access follows the mapped parameter (printed R/W).",
  "Binary I/O 1-3 are bi-directional; each can be an input or an output at a time.",
  "The PICS prints the BV descriptions copied from the BO rows; BV descriptions here follow the object names.",
  "The SI-BACnet IP option module uses a different AV numbering (see that list).",
  "Object instantiation is static; objects cannot be created or deleted."
 ],
 "source": {
  "title": "H300 PICS BACnet V1 R15",
  "doc_number": null,
  "revision_date": "2023-11-14",
  "url": "https://www.bacnetinternational.net/catalog/manu/nidec%20control%20techniques%20ltd./H300_PICS_BACNET_V1_R15.pdf",
  "unofficial": true,
  "host": "BACnet International"
 },
 "integration": {
  "summary": "Command BV 3 Drive Run Fwrd and AV 4 Speed Ref, reset trips with BV 6, and read output frequency, current, power, BV 4 Drive Healthy and AV 13 Last Trip.",
  "minimum_points": [
   {
    "ref": "BV 3",
    "name": "#BV_03 Drive Run Fwrd",
    "why": "Run forward command"
   },
   {
    "ref": "AV 4",
    "name": "#AV_04 Speed Ref",
    "why": "Speed reference, Hz"
   },
   {
    "ref": "BV 6",
    "name": "#BV_06 Drive Reset",
    "why": "Trip reset (write active)"
   },
   {
    "ref": "BI 7",
    "name": "#BI_07 Drive Binary IP7",
    "why": "Drive enable input state"
   },
   {
    "ref": "AV 8",
    "name": "#AV_08 Output Frequency",
    "why": "Output frequency, Hz"
   },
   {
    "ref": "AV 6",
    "name": "#AV_06 Output Current",
    "why": "Motor current, A"
   },
   {
    "ref": "AV 10",
    "name": "#AV_10 Output Power",
    "why": "Output power, kW"
   },
   {
    "ref": "BV 4",
    "name": "#BV_04 Drive Healthy",
    "why": "Drive healthy (no trip)"
   },
   {
    "ref": "BV 5",
    "name": "#BV_05 Drive Warning",
    "why": "Drive warning active"
   },
   {
    "ref": "AV 13",
    "name": "#AV_13 Last Trip",
    "why": "Last trip code"
   }
  ],
  "gotchas": [
   "BV 6 Drive Reset can only be written active from inactive; BV 2 can only be written inactive."
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The onboard EIA-485 port is selectable between Modbus RTU and BACnet MS/TP; MS/TP master at 9600, 19200 or 38400 baud."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "#AI_01 Drive Analog IP1",
   "description": "Analog input 1 on drive",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "#AI_02 Drive Analog IP2",
   "description": "Analog input 2 on drive",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "#AO_01 Drive Analog OP1",
   "description": "Analog output 1 on drive",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "#AO_02 Drive Analog OP2",
   "description": "Analog output 2 on drive",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "#AV_04 Speed Ref",
   "description": "Frequency/speed reference",
   "units": "Hz",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "#AV_05 Max Speed Ref",
   "description": "Maximum reference clamp",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "#AV_06 Output Current",
   "description": "Motor output current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "#AV_07 Output Torque",
   "description": "Output torque, % of full load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "#AV_08 Output Frequency",
   "description": "Drive output frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "#AV_09 Output Speed",
   "description": "Motor speed",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "#AV_10 Output Power",
   "description": "Drive output power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "#AV_11 Drive Status Wd",
   "description": "Drive status word",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "#AV_12 User Trip Param",
   "description": "User trip",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "#AV_13 Last Trip",
   "description": "Last drive trip code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "#AV_14 Filtr Change(dt)",
   "description": "Time between filter changes",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "#AV_15 Nxt Filtr ChTime",
   "description": "Time until next filter change",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "#AV_16 Enrgy Meter(MWh)",
   "description": "Energy meter, MWh part",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "#AV_17 Enrgy Meter(kWh)",
   "description": "Energy meter, kWh part",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "#AV_18 PID1 Dig Ref",
   "description": "PID 1 digital reference",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "#AV_19 PID1 Dig Fback",
   "description": "PID 1 digital feedback",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "#AV_20 PID1 Ref",
   "description": "PID 1 total reference",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "#AV_21 PID1 Fback",
   "description": "PID 1 total feedback",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "#AV_22 PID1 Output",
   "description": "PID 1 output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "#AV_23 PID2 Dig Ref",
   "description": "PID 2 digital reference",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "#AV_24 PID2 Dig Fback",
   "description": "PID 2 digital feedback",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "#AV_25 PID2 Ref",
   "description": "PID 2 total reference",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "#AV_26 PID2 Fback",
   "description": "PID 2 total feedback",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "#AV_27 PID2 Output",
   "description": "PID 2 output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "#AV_28 User Sel 29.010",
   "description": "User-selectable parameter 1 (set in Pr 29.010)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "#AV_29 User Sel 29.011",
   "description": "User-selectable parameter 2 (set in Pr 29.011)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "#AV_30 User Sel 29.012",
   "description": "User-selectable parameter 3 (set in Pr 29.012)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "#AV_31 User Sel 29.013",
   "description": "User-selectable parameter 4 (set in Pr 29.013)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "#AV_32 User Sel 29.014",
   "description": "User-selectable parameter 5 (set in Pr 29.014)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "#AV_33 User Sel 29.015",
   "description": "User-selectable parameter 6 (set in Pr 29.015)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "#AV_34 User Sel 29.016",
   "description": "User-selectable parameter 7 (set in Pr 29.016)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "#AV_35 User Sel 29.017",
   "description": "User-selectable parameter 8 (set in Pr 29.017)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "#AV_36 User Sel 29.018",
   "description": "User-selectable parameter 9 (set in Pr 29.018)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "#AV_37 User Sel 29.019",
   "description": "User-selectable parameter 10 (set in Pr 29.019)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "#BI_01 Drive Binary IP1",
   "description": "Digital input 1 on drive (bi-directional)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "#BI_02 Drive Binary IP2",
   "description": "Digital input 2 on drive (bi-directional)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "#BI_03 Drive Binary IP3",
   "description": "Digital input 3 on drive (bi-directional)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "#BI_04 Drive Binary IP4",
   "description": "Digital input 4 on drive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "#BI_05 Drive Binary IP5",
   "description": "Digital input 5 on drive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "#BI_06 Drive Binary IP6",
   "description": "Digital input 6 on drive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "#BI_07 Drive Binary IP7",
   "description": "Drive enable input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "#BO_01 Drive Binary OP1",
   "description": "Digital output 1 (bi-directional)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "#BO_02 Drive Binary OP2",
   "description": "Digital output 2 (bi-directional)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "#BO_03 Drive Binary OP3",
   "description": "Digital output 3 (bi-directional)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "#BO_04 Drive Binary OP4",
   "description": "24 V output",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "#BO_05 Drive Binary Rl1",
   "description": "Drive relay 1",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "#BO_06 Drive Binary Rl2",
   "description": "Drive relay 2",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "#BV_01 Reset Enrgy Metr",
   "description": "Reset the energy meter",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "#BV_02 Filtr Change Rqd",
   "description": "Filter change due; can only be written inactive",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "#BV_03 Drive Run Fwrd",
   "description": "Run forward command",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "#BV_04 Drive Healthy",
   "description": "Drive healthy status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "#BV_05 Drive Warning",
   "description": "Drive warning",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "#BV_06 Drive Reset",
   "description": "Drive reset; can only be written active from inactive",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/nidec-control-techniques/hvac-drive-h300",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}