 "manufacturer": "Nidec Control Techniques",
 "manufacturer_slug": "nidec-control-techniques",
 "model": "SI-BACnet IP option module",
 "model_slug": "si-bacnet-ip",
 "aliases": [
  "SI-BACnet IP",
  "SI-BACnet",
  "82400000022600",
  "Control Techniques BACnet/IP module"
 ],
 "equipment_type": "Variable frequency drive BACnet IP option module",
 "applies_to": "Control Techniques SI-BACnet IP option module (part 82400000022600) fitted to a compatible Control Techniques drive.",
 "summary": "The SI-BACnet IP is a plug-in option that puts a Control Techniques drive on BACnet IP. It exposes the same kinds of objects as the H300 onboard port (I/O, speed reference, run and reset, output values, PID loops, filter timers, energy meter, ten user-configurable AVs) but numbers the Analog Values differently and adds a multistate drive-status object and two network port objects.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "01.00.02.06 (PICS)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names are listed as printed, including the #AI_01-style prefix.",
  "AV numbering differs from the H300 onboard MS/TP list: Speed Ref is AV 1 here and AV 4 on the H300.",
  "Read-only analog objects are printed R*: only COV-related properties are writable.",
  "AV 25-34 map any drive parameter; access follows the mapped parameter (printed R/W).",
  "The PICS also lists Network Port objects #NP_01 and #NP_02; they are not listed as points.",
  "The PICS gives no state texts for MV 1 Drive Status.",
  "The PICS says the module only shows the objects the host drive supports, so some objects may be missing on a given drive."
 ],
 "source": {
  "title": "SI-BACnet IP PICS",
  "doc_number": null,
  "revision_date": "2024-09-14",
  "url": "https://www.bacnetinternational.net/catalog/manu/nidec%20control%20techniques%20ltd./PICS%20si-bacnetip_pics.pdf",
  "unofficial": true,
  "host": "BACnet International"
 },
 "integration": {
  "summary": "Command BV 3 Drive Run Fwrd and AV 1 Speed Ref, reset trips with BV 6, and read output frequency, current, power, BV 4 Drive Healthy, MV 1 Drive Status and AV 15 Last Trip.",
  "minimum_points": [
   {
    "ref": "BV 3",
    "name": "#BV_03 Drive Run Fwrd",
    "why": "Run forward command"
   },
   {
    "ref": "AV 1",
    "name": "#AV_01 Speed Ref",
    "why": "Speed reference, Hz"
   },
   {
    "ref": "BV 6",
    "name": "#BV_06 Drive Reset",
    "why": "Trip reset (write active)"
   },
   {
    "ref": "BI 7",
    "name": "#BI_07 Drive Binary IP7",
    "why": "Drive enable input state"
   },
   {
    "ref": "AV 10",
    "name": "#AV_10 Output Frequency",
    "why": "Output frequency, Hz"
   },
   {
    "ref": "AV 9",
    "name": "#AV_09 Output Current",
    "why": "Motor current, A"
   },
   {
    "ref": "AV 11",
    "name": "#AV_11 Output Power",
    "why": "Output power, kW"
   },
   {
    "ref": "BV 4",
    "name": "#BV_04 Drive Healthy",
    "why": "Drive healthy (no trip)"
   },
   {
    "ref": "MV 1",
    "name": "#MSV_01 Drive Status",
    "why": "Drive health and trip state"
   },
   {
    "ref": "AV 15",
    "name": "#AV_15 Last Trip",
    "why": "Last trip code"
   }
  ],
  "setup": [
   "Network Port objects: only foreign-device (BBMD registration) properties are writable."
  ],
  "gotchas": [
   "BV 6 Drive Reset can only be written active from inactive; BV 2 can only be written inactive."
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "#AI_01 Drive Analog IP1",
   "description": "Analog input 1 on drive",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "#AI_02 Drive Analog IP2",
   "description": "Analog input 2 on drive",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "#AO_01 Drive Analog OP1",
   "description": "Analog output 1 on drive",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "#AO_02 Drive Analog OP2",
   "description": "Analog output 2 on drive",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "#AV_01 Speed Ref",
   "description": "Frequency/speed reference",
   "units": "Hz",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "#AV_02 PID1 Dig Ref",
   "description": "PID 1 digital reference",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "#AV_03 PID1 Dig Fback",
   "description": "PID 1 digital feedback",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "#AV_04 PID2 Dig Ref",
   "description": "PID 2 digital reference",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "#AV_05 PID2 Dig Fback",
   "description": "PID 2 digital feedback",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "#AV_06 Max Speed Ref",
   "description": "Maximum reference clamp",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "#AV_07 User Trip Param",
   "description": "User trip",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "#AV_08 Filtr Change(dt)",
   "description": "Time between filter changes",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "#AV_09 Output Current",
   "description": "Motor output current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "#AV_10 Output Frequency",
   "description": "Drive output frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "#AV_11 Output Power",
   "description": "Drive output power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "#AV_12 Output Torque",
   "description": "Output torque, % of full load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "#AV_13 Output Speed",
   "description": "Motor speed",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "#AV_14 Drive Status Wd",
   "description": "Drive status word",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "#AV_15 Last Trip",
   "description": "Last drive trip code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "#AV_16 Nxt Filtr ChTime",
   "description": "Time until next filter change",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "#AV_17 Enrgy Meter(MWh)",
   "description": "Energy meter, MWh part",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "#AV_18 Enrgy Meter(kWh)",
   "description": "Energy meter, kWh part",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "#AV_19 PID1 Ref",
   "description": "PID 1 total reference",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "#AV_20 PID1 Fback",
   "description": "PID 1 total feedback",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "#AV_21 PID1 Output",
   "description": "PID 1 output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "#AV_22 PID2 Ref",
   "description": "PID 2 total reference",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "#AV_23 PID2 Fback",
   "description": "PID 2 total feedback",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "#AV_24 PID2 Output",
   "description": "PID 2 output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "#AV_25 User Configurable",
   "description": "User-selectable drive parameter 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "#AV_26 User Configurable",
   "description": "User-selectable drive parameter 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "#AV_27 User Configurable",
   "description": "User-selectable drive parameter 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "#AV_28 User Configurable",
   "description": "User-selectable drive parameter 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "#AV_29 User Configurable",
   "description": "User-selectable drive parameter 5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "#AV_30 User Configurable",
   "description": "User-selectable drive parameter 6",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "#AV_31 User Configurable",
   "description": "User-selectable drive parameter 7",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "#AV_32 User Configurable",
   "description": "User-selectable drive parameter 8",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "#AV_33 User Configurable",
   "description": "User-selectable drive parameter 9",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "#AV_34 User Configurable",
   "description": "User-selectable drive parameter 10",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "#BI_01 Drive Binary IP1",
   "description": "Digital input 1 on drive (bi-directional)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "#BI_02 Drive Binary IP2",
   "description": "Digital input 2 on drive (bi-directional)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "#BI_03 Drive Binary IP3",
   "description": "Digital input 3 on drive (bi-directional)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "#BI_04 Drive Binary IP4",
   "description": "Digital input 4 on drive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "#BI_05 Drive Binary IP5",
   "description": "Digital input 5 on drive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "#BI_06 Drive Binary IP6",
   "description": "Digital input 6 on drive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "#BI_07 Drive Binary IP7",
   "description": "Drive enable input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "#BO_01 Drive Binary OP1",
   "description": "Digital output 1 (bi-directional)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "#BO_02 Drive Binary OP2",
   "description": "Digital output 2 (bi-directional)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "#BO_03 Drive Binary OP3",
   "description": "Digital output 3 (bi-directional)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "#BO_04 Drive Binary OP4",
   "description": "24 V output",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "#BO_05 Drive Binary Rl1",
   "description": "Drive relay 1",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "#BO_06 Drive Binary Rl2",
   "description": "Drive relay 2",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "#BV_01 Reset Enrgy Metr",
   "description": "Reset the energy meter",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "#BV_02 Filtr Change Rqd",
   "description": "Filter change due; can only be written inactive",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "#BV_03 Drive Run Fwrd",
   "description": "Run forward command",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "#BV_04 Drive Healthy",
   "description": "Drive healthy status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "#BV_05 Drive Warning",
   "description": "Drive warning",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "#BV_06 Drive Reset",
   "description": "Drive reset; can only be written active from inactive",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "#MSV_01 Drive Status",
   "description": "Drive health and trip state",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/nidec-control-techniques/si-bacnet-ip",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}