VRF outdoor unit gateway (BACnet IP) · BACnet points list

Midea IMMP-BAC(A) BACnet gateway - outdoor unit device BACnet points list

Updated 7 November 2026

Short answer

The IMMP-BAC(A) gateway publishes each VRF outdoor unit as a separate BACnet IP device. The outdoor device is mostly monitoring: operating mode, run and alarm state, compressor frequencies and discharge temperatures, pressures, fan speeds, EXV openings, valve and heater outputs, and the error code.

This page lists 37 BACnet objects for the Midea IMMP-BAC(A) BACnet gateway - outdoor unit device — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Midea’s own free documentation, linked below.

Manufacturer
Midea
Model
IMMP-BAC(A) BACnet gateway - outdoor unit device
Equipment
VRF outdoor unit gateway (BACnet IP)
Equipment type
VRF & split air conditioners
BACnet objects
37 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
IMMP-BAC(A), K05.2-BACNET(A), IMMP-BAC-A
Source document
Manual de Instalación y de Usuario, Sistema de control IMMP-BAC(A) (K05.2-BACNET(A)) · 210427_MI-MU_F-CTR_IMMP-BAC-A-ES · rev. 2021-04
Download CSV 37 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Midea’s current documentation and the live device before use. Not official Midea information. Terms of use.

BMS integration notes: Midea IMMP-BAC(A) BACnet gateway - outdoor unit device

Integration in brief

The outdoor unit device is read-only monitoring. Map BI 1 run state, MI 1 mode, AI 1 ambient temperature and the compressor data, plus BI 2 alarm and AI 8 error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 1Encendido/ apagadoOutdoor unit runningRead
MI 1Estado del modo de funcionamientoOperating modeRead
AI 1Temperatura ambienteOutdoor ambient temperature, °CRead
AI 2Frecuencia del compresor 1Compressor 1 frequency, HzRead
BI 2Indicación de alarmaOutdoor unit alarmRead
AI 8Código de averíaError code (1-260 = A0...UU)Read

Network setup

Watch out for

Midea IMMP-BAC(A) BACnet gateway - outdoor unit device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

37 of 37 shown
Type
AnalogMulti-state
Show
Midea IMMP-BAC(A) BACnet gateway - outdoor unit device BACnet Points List
DescriptionStates
MImin1Estado del modo de funcionamientoOutdoor unit operating modeRead1=apagado, 2=reservado, 3=refrigeración, 4=calefacción, 5=refrigeración forzada, 6=refrigeración principal, 7=calefacción principal, 8=calefacción forzada
BImin1Encendido/ apagadoOn/off statusRead0=APAGADO, 1=ENCENDIDO
BImin2Indicación de alarmaAlarm indicationRead0=Sin error, 1=Error
BI3SV1Valve / heater output stateRead
BI4SV2Valve / heater output stateRead
BI5SV3Valve / heater output stateRead
BI6SV4Valve / heater output stateRead
BI7SV5Valve / heater output stateRead
BI8SV6Valve / heater output stateRead
BI9SV7Valve / heater output stateRead
BI10SV8Valve / heater output stateRead
BI11ST1Valve / heater output stateRead
BI12ST2Valve / heater output stateRead
BI13ST3Valve / heater output stateRead
BI14SV8BValve / heater output stateRead
BI15SV9Valve / heater output stateRead
BI17HEATER 1Valve / heater output stateRead
BI18HEATER 2Valve / heater output stateRead
AImin1Temperatura ambienteAmbient temperature°CRead
AImin2Frecuencia del compresor 1Compressor 1 frequencyHzRead
AI3Frecuencia del compresor 2Compressor 2 frequencyHzRead
AI4Temperatura de descarga del compresor 1Compressor 1 discharge temperature°CRead
AI5Temperatura de descarga del compresor 2Compressor 2 discharge temperature°CRead
AI6Alta presiónHigh pressurebarRead
AI7Baja presiónLow pressurebarRead
AImin8Código de averíaError code (see code table)Read
AI9Velocidad ventilador 1Fan 1 speedRead
AI10Velocidad ventilador 2Fan 2 speedRead
AI11T3T3 temperature°CRead
AI12T3BT3B temperature (reserved)°CRead
AI13VersiónSoftware versionRead
AI14Tipo de unidad exteriorOutdoor unit typeRead
AI15Potencia de unidad exteriorOutdoor unit capacityRead
AI16Apertura de Exv1EXV1 openingRead
AI17Apertura de Exv2EXV2 openingRead
AI18Apertura de Exv3EXV3 openingRead
BV1Parada de emergenciaEmergency stop (reserved)Read0=parada de emergencia APAGADA, 1=parada de emergencia ENCENDIDA
Object ID lookup: Midea IMMP-BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IMMP-BAC(A) BACnet gateway - outdoor unit device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Midea IMMP-BAC(A) BACnet gateway - outdoor unit device

How many BACnet points does the Midea IMMP-BAC(A) BACnet gateway - outdoor unit device have?

This list has 37 BACnet objects: 18 analog inputs, 17 binary inputs, 1 binary value, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Midea IMMP-BAC(A) BACnet gateway - outdoor unit device BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Midea IMMP-BAC(A) BACnet gateway - outdoor unit device BACnet documentation?

The source is Manual de Instalación y de Usuario, Sistema de control IMMP-BAC(A) (K05.2-BACNET(A)) (210427_MI-MU_F-CTR_IMMP-BAC-A-ES), revision 2021-04, published free by Midea at https://www.midea.es/wp-content/uploads/2021/04/210427_MI-MU_F-CTR_IMMP-BAC-A-ES.pdf.

What are the minimum BACnet points to integrate the Midea IMMP-BAC(A) BACnet gateway - outdoor unit device?

Start with BI 1 Encendido/ apagado (Outdoor unit running); MI 1 Estado del modo de funcionamiento (Operating mode); AI 1 Temperatura ambiente (Outdoor ambient temperature, °C); AI 2 Frecuencia del compresor 1 (Compressor 1 frequency, Hz); BI 2 Indicación de alarma (Outdoor unit alarm); AI 8 Código de avería (Error code (1-260 = A0...UU)).

How do I check these points on the real IMMP-BAC(A) BACnet gateway - outdoor unit device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Midea BACnet points lists

Source: Manual de Instalación y de Usuario, Sistema de control IMMP-BAC(A) (K05.2-BACNET(A)) · 210427_MI-MU_F-CTR_IMMP-BAC-A-ES · rev. 2021-04. Object names, instances and units are reproduced as published; descriptions are our own.