VRF BACnet gateway (V8 outdoor unit device) · BACnet points list

Midea GW3-BAC gateway - V8 VRF outdoor unit device BACnet points list

Updated 11 November 2026

Short answer

The Midea GW3-BAC gateway serves V8 VRF systems on BACnet IP and creates one virtual BACnet device per outdoor unit. Each outdoor-unit device has 42 objects: on/off and fault status, mode, fan speeds and status, outdoor temperature, compressor frequencies, status, discharge temperatures and currents, high and low pressure, error code, EXV openings, solenoid valves, auxiliary electric heaters and an emergency-stop command.

This page lists 42 BACnet objects for the Midea GW3-BAC gateway - V8 VRF outdoor unit device — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Midea’s own free documentation, linked below.

Manufacturer
Midea
Model
GW3-BAC gateway - V8 VRF outdoor unit device
Equipment
VRF BACnet gateway (V8 outdoor unit device)
Equipment type
VRF & split air conditioners
BACnet objects
42 (1 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
GW3-BAC, Midea GW3-BAC ODU, Midea V8 outdoor unit BACnet, Midea VRF V8 BACnet IP
Source document
Manual de instalación y del usuario - Pasarela GW3-BAC (Spanish) · rev. 2024-04 (240417)
Download CSV 42 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Midea’s current documentation and the live device before use. Not official Midea information. Terms of use.

BMS integration notes: Midea GW3-BAC gateway - V8 VRF outdoor unit device

Integration in brief

Discover the outdoor unit as its own BACnet IP device (FG = 96-99 in the device ID) and read its status, pressures and temperatures. The only command is BO 1 emergency stop.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Parada de emergenciaEmergency stop; must be released with the same objectWrite
BI 1Estado de encendido/apagadoRun statusRead
AI 1ModoOperating modeRead
AI 4Temperatura ambienteOutdoor ambient temperatureRead
AI 9Alta presiónHigh pressureRead
AI 10Baja presiónLow pressureRead
BI 2Indicación de alarmaUnit faultRead
AI 11Código de averíaEncoded error codeRead

Network setup

Watch out for

Midea GW3-BAC gateway - V8 VRF outdoor unit device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

42 of 42 shown
Type
Analog
Access
Show
Midea GW3-BAC gateway - V8 VRF outdoor unit device BACnet Points List
DescriptionStates
BImin1Estado de encendido/apagadoOn/off statusRead0=Apagado, 1=Encendido
BImin2Indicación de alarmaFault indicationRead0=Sin errores, 1=Error
AImin1ModoOperating modeRead0=Apagado, 2=Refrigeración, 3=Calefacción, 4=Refrigeración forzada, 29=Refrigeración por mezcla, 30=Calefacción por mezcla
AI2Fan1Fan 1 speedRead
AI3Fan2Fan 2 speedRead
BI3Estado del ventilador 1Fan 1 on/offRead0=Apagado, 1=Encendido
BI4Estado del ventilador 2Fan 2 on/offRead0=Apagado, 1=Encendido
AImin4Temperatura ambienteOutdoor ambient temperatureRead
AI5Frec. del compresor 1Compressor 1 frequencyRead
AI6Frec. del compresor 2Compressor 2 frequencyRead
BI5Estado del compresor 1Compressor 1 on/offRead0=Apagado, 1=Encendido
BI6Estado del compresor 2Compressor 2 on/offRead0=Apagado, 1=Encendido
AI7Temperatura de descarga del compresor 1Compressor 1 discharge temperatureRead
AI8Temperatura de descarga del compresor 2Compressor 2 discharge temperatureRead
AImin9Alta presiónHigh pressureRead
AImin10Baja presiónLow pressureRead
AImin11Código de averíaOutdoor unit error codeRead
AI12T3T3 temperatureRead
AI13Temperatura de escapeDischarge superheatRead
AI14Corriente del compresor 1Compressor 1 currentRead
AI15Corriente del compresor 2Compressor 2 currentRead
AI16CVCapacity (HP)Read
AI17EXV1EXV1 openingRead
AI18EXV2EXV2 openingRead
AI19EXV3EXV3 openingRead
AI20EXV4EXV4 openingRead
BI7SV1Solenoid valve SV1Read0=Apagado, 1=Encendido
BI8SV2Solenoid valve SV2Read0=Apagado, 1=Encendido
BI9SV3Solenoid valve SV3Read0=Apagado, 1=Encendido
BI10SV4Solenoid valve SV4Read0=Apagado, 1=Encendido
BI11SV5Solenoid valve SV5Read0=Apagado, 1=Encendido
BI12SV6Solenoid valve SV6Read0=Apagado, 1=Encendido
BI13SV7Solenoid valve SV7Read0=Apagado, 1=Encendido
BI14SV8Solenoid valve SV8Read0=Apagado, 1=Encendido
BI15SV8bSolenoid valve SV8bRead0=Apagado, 1=Encendido
BI16SV9Solenoid valve SV9Read0=Apagado, 1=Encendido
BI17ST1ST1 output statusRead0=Apagado, 1=Encendido
BI18ST2ST2 output statusRead0=Apagado, 1=Encendido
BI19ST3ST3 output statusRead0=Apagado, 1=Encendido
BI20Crank1Auxiliary electric heater 1 statusRead0=Apagado, 1=Encendido
BI21Crank2Auxiliary electric heater 2 statusRead0=Apagado, 1=Encendido
BOmin1Parada de emergenciaEmergency stop commandWrite0=Parada de emergencia inactiva, 1=Parada de emergencia activa
Object ID lookup: Midea GW3-BAC V8 VRF Outdoor Unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GW3-BAC gateway - V8 VRF outdoor unit device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Midea GW3-BAC gateway - V8 VRF outdoor unit device

How many BACnet points does the Midea GW3-BAC gateway - V8 VRF outdoor unit device have?

This list has 42 BACnet objects: 20 analog inputs, 21 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Midea GW3-BAC gateway - V8 VRF outdoor unit device BACnet points are writable?

1 of the 42 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Midea GW3-BAC gateway - V8 VRF outdoor unit device BACnet documentation?

The source is Manual de instalación y del usuario - Pasarela GW3-BAC (Spanish), revision 2024-04 (240417), published free by Midea at https://www.midea.es/wp-content/uploads/2024/04/240417_MI-MU_M_CTR_GW3-BAC-ES.pdf.

What are the minimum BACnet points to integrate the Midea GW3-BAC gateway - V8 VRF outdoor unit device?

Start with BO 1 Parada de emergencia (Emergency stop; must be released with the same object); BI 1 Estado de encendido/apagado (Run status); AI 1 Modo (Operating mode); AI 4 Temperatura ambiente (Outdoor ambient temperature); AI 9 Alta presión (High pressure); AI 10 Baja presión (Low pressure); BI 2 Indicación de alarma (Unit fault); AI 11 Código de avería (Encoded error code).

How do I check these points on the real GW3-BAC gateway - V8 VRF outdoor unit device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Midea BACnet points lists

Source: Manual de instalación y del usuario - Pasarela GW3-BAC (Spanish) · rev. 2024-04 (240417). Object names, instances and units are reproduced as published; descriptions are our own.