VRF hydronic module (air to water heat pump) gateway (BACnet IP) · BACnet points list

Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device BACnet points list

Updated 7 November 2026

Short answer

For a high-temperature hydronic module the IMMP-BAC(A) gateway publishes a separate BACnet IP device with heating and hot water on/off commands, their setpoints and locks, and water temperatures, pressures, compressor frequency and the error code.

This page lists 25 BACnet objects for the Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Midea’s own free documentation, linked below.

Manufacturer
Midea
Model
IMMP-BAC(A) BACnet gateway - HTHM hydronic module device
Equipment
VRF hydronic module (air to water heat pump) gateway (BACnet IP)
Equipment type
Heat pumps
BACnet objects
25 (8 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
IMMP-BAC(A), K05.2-BACNET(A), IMMP-BAC-A
Source document
Manual de Instalación y de Usuario, Sistema de control IMMP-BAC(A) (K05.2-BACNET(A)) · 210427_MI-MU_F-CTR_IMMP-BAC-A-ES · rev. 2021-04
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Midea’s current documentation and the live device before use. Not official Midea information. Terms of use.

BMS integration notes: Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device

Integration in brief

Map BV 90 and BV 91 to switch space heating and hot water, AV 51 and AV 50 for their setpoints, and read MI 56 mode, the water temperatures and AV 63 error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 90Encendido/apagado de la calefacciónSpace heating on/offWrite
BV 91Encendido/apagado del calentamiento del aguaDomestic hot water on/offWrite
AV 51Ajuste de temperatura de la calefacciónHeating water setpoint, 25-80 °CWrite
AV 50Ajuste de la temperatura de calentamiento del aguaHot water setpoint, 25-80 °CWrite
MI 56Modo actualMode: 1=Off 4=Heating 6=Hot waterRead
AV 61Temperatura de salida del aguaWater outlet temperature, °CRead
AV 62Temperatura del acumulador de aguaHot water tank temperature, °CRead
AV 63Código de errorError code (1-260 = A0...UU)Read

Network setup

Watch out for

Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

25 of 25 shown
Type
AnalogBinary
Access
Show
Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device BACnet Points List
DescriptionStates
AVmin50Ajuste de la temperatura de calentamiento del aguaDomestic hot water setpoint, 25-80 °C°CWrite
AVmin51Ajuste de temperatura de la calefacciónHeating water setpoint, 25-80 °C°CWrite
AV52Bloqueo de la temperatura de la calefacciónHeating setpoint limit (0 = unlocked)°CWrite
AV53Bloqueo de la temperatura de calentamiento del aguaHot water setpoint limit (0 = unlocked)°CWrite
AV60Temperatura de entrada del aguaWater inlet temperature°CRead
AVmin61Temperatura de salida del aguaWater outlet temperature°CRead
AVmin62Temperatura del acumulador de aguaWater tank temperature°CRead
AVmin63Código de errorError code (see code table)Read
AV64TfTf temperature°CRead
AV65T2AT2A temperature°CRead
AV66T7T7 temperature°CRead
AV67T7CT7C temperature°CRead
AV68PePe pressurebarRead
AV69PcPc pressurebarRead
AV70EXV 1EXV 1 openingRead
AV71EXV 2EXV 2 openingRead
AV72NecesidadHTHM demandRead
AV73PotenciaCapacityRead
AV75Frecuencia del compresorCompressor frequencyHzRead
AV76Versión del softwareSoftware versionRead
MV78Bloqueo de la calefacciónHeating lockWrite1=Bloqueo ENCENDIDO, 2=Bloqueo APAGADO, 3=Desbloqueado
MV79Bloqueo de calentamiento del aguaHot water lockWrite1=Bloqueo ENCENDIDO, 2=Bloqueo APAGADO, 3=Desbloqueado
MImin56Modo actualCurrent modeRead1=Apagado, 4=Calefacción, 6=Calentamiento del agua
BVmin90Encendido/apagado de la calefacciónHeating on/off commandWrite0=APAGADO, 1=ENCENDIDO
BVmin91Encendido/apagado del calentamiento del aguaHot water on/off commandWrite0=APAGADO, 1=ENCENDIDO
Object ID lookup: Midea IMMP-BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IMMP-BAC(A) BACnet gateway - HTHM hydronic module device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device

How many BACnet points does the Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device have?

This list has 25 BACnet objects: 20 analog values, 2 binary values, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device BACnet points are writable?

8 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device BACnet documentation?

The source is Manual de Instalación y de Usuario, Sistema de control IMMP-BAC(A) (K05.2-BACNET(A)) (210427_MI-MU_F-CTR_IMMP-BAC-A-ES), revision 2021-04, published free by Midea at https://www.midea.es/wp-content/uploads/2021/04/210427_MI-MU_F-CTR_IMMP-BAC-A-ES.pdf.

What are the minimum BACnet points to integrate the Midea IMMP-BAC(A) BACnet gateway - HTHM hydronic module device?

Start with BV 90 Encendido/apagado de la calefacción (Space heating on/off); BV 91 Encendido/apagado del calentamiento del agua (Domestic hot water on/off); AV 51 Ajuste de temperatura de la calefacción (Heating water setpoint, 25-80 °C); AV 50 Ajuste de la temperatura de calentamiento del agua (Hot water setpoint, 25-80 °C); MI 56 Modo actual (Mode: 1=Off 4=Heating 6=Hot water); AV 61 Temperatura de salida del agua (Water outlet temperature, °C); AV 62 Temperatura del acumulador de agua (Hot water tank temperature, °C); AV 63 Código de error (Error code (1-260 = A0...UU)).

How do I check these points on the real IMMP-BAC(A) BACnet gateway - HTHM hydronic module device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Midea BACnet points lists

Source: Manual de Instalación y de Usuario, Sistema de control IMMP-BAC(A) (K05.2-BACNET(A)) · 210427_MI-MU_F-CTR_IMMP-BAC-A-ES · rev. 2021-04. Object names, instances and units are reproduced as published; descriptions are our own.