- TR50 indoor air quality sensor (BACnet MS/TP)
Room air quality sensor · BACnet points list
Honeywell TR50 indoor air quality sensor (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The TR50 is a wall-mount indoor air quality sensor that reports temperature, humidity, CO2, particulates, TVOC and an air quality score on BACnet MS/TP (it also speaks Modbus and Sylk). Readings are Analog Inputs; alarm limits, deadbands, delays, offsets and display settings are writable Analog, Multistate and Binary Values, and each measurement has an out-of-range multistate. Which objects appear depends on the SKU (3-sensor models lack PM and TVOC).
This page lists 69 BACnet objects for the Honeywell TR50 indoor air quality sensor (BACnet MS/TP) — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Honeywell’s documentation hosted by Stromquist & Company, not by Honeywell itself, so treat it as unofficial.
- Manufacturer
- Honeywell
- Model
- TR50 indoor air quality sensor (BACnet MS/TP)
- Equipment
- Room air quality sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 69 (58 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Same as the MS/TP MAC address
- Also known as
- TR50, TR50-5D, TR50-5N, TR50-3D, TR50-3N, TR50-5D-U, TR50-3D-U, Honeywell TR50 IAQ sensor
- Source document
- TR50 User Guide, section 4.4.5 BACnet Points (unofficial copy, hosted by Stromquist & Company)
Reference only, provided as-is: verify against Honeywell’s current documentation and the live device before use. Not official Honeywell information. Terms of use.
BMS integration notes: Honeywell TR50 indoor air quality sensor (BACnet MS/TP)
Set the MS/TP MAC on the DIP switches, let the sensor auto-detect the baud rate, discover it and give it a unique device instance. Then read the sensor AIs and the out-of-range multistates; adjust alarm limits only if the sensor's own alarms are used.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | SS_AI_SensorReading_Temp | Space temperature | Read |
| AI 2 | SS_AI_SensorReading_Humi | Space relative humidity, % | Read |
| AI 3 | SS_AI_SensorReading_CO2 | CO2, ppm | Read |
| AI 4 | SS_AI_SensorReading_PM2.5 | PM2.5, ug/m3 | Read |
| AI 5 | SS_AI_SensorReading_TVOC | TVOC, ppb or ug/m3 | Read |
| AI 6 | SS_AI_AIR_QUALITY_SCORE | Air quality score, 0-100 | Read |
| MV 3 | SS_MV_OutOfRange_CO2 | CO2 state: normal, over high, over high-high | Write |
Network setup
- MS/TP MAC by DIP switch; default MAC range 1-30, Max Master 35.
- Device instance defaults to the MAC address; set a unique instance after discovery.
- Auto baud for the first 4 minutes after power-up (9600-115200); falls back to the last found rate, else 38400.
Watch out for
- Allow at least 3 minutes between two CO2 offset writes (cfgCO2SensorOffset).
- The out-of-range multistates (MV 1-5) are listed as R/W but report the alarm state; treat them as status.
Honeywell TR50 indoor air quality sensor (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | SS_AI_SensorReading_Temp | Temperature reading | °F or °C | Read | |
| AImin | 2 | SS_AI_SensorReading_Humi | Relative humidity | % | Read | |
| AImin | 3 | SS_AI_SensorReading_CO2 | CO2 | ppm | Read | |
| AImin | 4 | SS_AI_SensorReading_PM2.5 | PM2.5 | ug/m3 | Read | |
| AImin | 5 | SS_AI_SensorReading_TVOC | TVOC | ppb or ug/m3 | Read | |
| AImin | 6 | SS_AI_AIR_QUALITY_SCORE | Air quality score 0-100 | Read | ||
| AI | 7 | SS_AI_SensorReading_PM1.0 | PM1.0 | ug/m3 | Read | |
| AI | 8 | SS_AI_SensorReading_PM10 | PM10 | ug/m3 | Read | |
| AV | 1 | CfgAlarmTempLowLimit | Alarm temperature low limit (default 65(°F) 18(°C)) | °F or °C | Write | |
| AV | 2 | CfgAlarmTempHighLimit | Alarm temperature high limit (default 86(°F) 30(°C)) | °F or °C | Write | |
| AV | 3 | CfgAlarmTempDeadband | Alarm temperature deadband (default 1(°F) 1(°C)) | °F or °C | Write | |
| AV | 4 | CfgAlarmTempTimeDelay | Alarm temperature time delay (default 60(s)) | s | Write | |
| MV | 1 | SS_MV_OutofRange_Temp | Out-of-range state, temperature (default 1) | Write | 1=Normal, 2=Off normal | |
| AV | 281 | CfgTempSensorOffset | Temperature sensor offset (default 0) | °F or °C | Write | |
| MV | 21 | CfgAlarmTempLimitEnable | Alarm temperature limit enable (default 4) | Write | 1=Temp Low Limit And High Limit Disable, 2=Temp Low Limit Enable, 3=Temp High Limit Enable, 4=Temp Low Limit And High Limit Enable | |
| MV | 101 | cfgDisplayUnitTemp | Display unit temperature (default 1) | Write | 1=Degrees Fahrenheit (°F), 2=Degrees Celsius (°C) | |
| AV | 51 | CfgAlarmHumiLowLimit | Alarm humidity low limit (default 10(%)) | % | Write | |
| AV | 52 | CfgAlarmHumiHighLimit | Alarm humidity high limit (default 80(%)) | % | Write | |
| AV | 53 | CfgAlarmHumiDeadband | Alarm humidity deadband (default 2) | Write | ||
| AV | 54 | CfgAlarmHumiTimeDelay | Alarm humidity time delay (default 60(s)) | s | Write | |
| MV | 2 | SS_MV_OutofRange_Humi | Out-of-range state, humidity (default 1) | Write | 1=Normal, 2=Off normal | |
| MV | 22 | cfgAlarmHumiLimitEnable | Alarm humidity limit enable (default 4) | Write | 1=Humidity Low Limit And High Limit Disable, 2=Humidity Low Limit Enable, 3=Humidity High Limit Enable, 4=Humidity Low Limit And High Limit Enable | |
| AV | 282 | cfgHumiSensorOffset | Humidity sensor offset (default 0) | Write | ||
| AV | 101 | CfgAlarmCO2HighLimit | Alarm CO2 high limit (default 1000(ppm)) | ppm | Write | |
| AV | 102 | CfgAlarmCO2HighHighLimit | Alarm CO2 high-high limit (default 1400(ppm)) | ppm | Write | |
| AV | 103 | CfgAlarmCO2Deadband | Alarm CO2 deadband (default 100) | Write | ||
| AV | 104 | CfgAlarmCO2TimeDelay | Alarm CO2 time delay (default 60(s)) | s | Write | |
| AV | 283 | cfgCO2SensorOffset | CO2 sensor offset (default 0) | Write | ||
| MVmin | 3 | SS_MV_OutOfRange_CO2 | Out-of-range state, CO2 (default 1) | Write | 1=Normal, 2=Over high limit, 3=Over highhigh limit | |
| MV | 23 | CfgAlarmCO2LimitEnable | Alarm CO2 limit enable (default 4) | Write | 1=CO2 High Limit And High High Limit Disable, 2=CO2 High Limit Enable, 3=CO2 High High Limit Enable, 4=CO2 High Limit And High High Limit Enable | |
| AV | 151 | CfgAlarmPM2.5HighLimit | Alarm PM2.5 high limit (default 35(ug/m3)) | ug/m3 | Write | |
| AV | 152 | cfgAlarmPM2.5HighHighLimit | Alarm PM2.5 high-high limit (default 55(ug/m3)) | ug/m3 | Write | |
| AV | 153 | CfgAlarmPM2.5Deadband | Alarm PM2.5 deadband (default 5) | Write | ||
| AV | 154 | CfgAlarmPM2.5TimeDelay | Alarm PM2.5 time delay (default 60(s)) | s | Write | |
| AV | 284 | CfgPM2.5SensorOffset | PM2.5 sensor offset (default 0) | Write | ||
| MV | 4 | SS_MV_OutOfRange_PM2.5 | Out-of-range state, PM2.5 (default 1) | Write | 1=Normal, 2=Over high limit, 3=Over highhigh limit | |
| MV | 24 | CfgAlarmPM2.5LimitEnable | Alarm PM2.5 limit enable (default 4) | Write | 1=PM2.5 High Limit And High High Limit Disable, 2=PM2.5 High Limit Enable, 3=PM2.5 High High Limit Enable, 4=PM2.5 High Limit And High High Limit Enable | |
| AV | 287 | CfgPM1.0SensorOffset | PM1.0 sensor offset (default 0) | Write | ||
| AV | 288 | CfgPM10SensorOffset | PM10 sensor offset (default 0) | Write | ||
| AV | 201 | CfgAlarmTVOCHighLimit | Alarm TVOC high limit (default 250(ppb) 500(ug/m3)) | ppb or ug/m3 | Write | |
| AV | 202 | CfgAlarmTVOCHighHighLimit | Alarm TVOC high-high limit (default 350(ppb) 700(ug/m3)) | ppb or ug/m3 | Write | |
| AV | 203 | CfgAlarmTVOCDeadband | Alarm TVOC deadband (default 20(ppb) 40(ug/m3)) | ppb or ug/m3 | Write | |
| AV | 204 | CfgAlarmTVOCTimeDelay | Alarm TVOC time delay (default 60(s)) | s | Write | |
| AV | 285 | CfgTVOCSensorOffset | TVOC sensor offset (default 0) | Write | ||
| MV | 5 | SS_MV_OutOfRange_TVOC | Out-of-range state, TVOC (default 1) | Write | 1=Normal, 2=Over high limit, 3=Over highhigh limit | |
| MV | 25 | CfgAlarmTVOCLimitEnable | Alarm TVOC limit enable (default 4) | Write | 1=TVOC High Limit And High High Limit Disable, 2=TVOC High Limit Enable, 3=TVOC High High Limit Enable, 4=TVOC High Limit And High High Limit Enable | |
| MV | 102 | cfgDisplayUnitTVOC | Display unit TVOC (default 1) | Write | 1=Parts Per Billion, 2=Micrograms Per Cubic Meter | |
| MV | 6 | SS_MV_AQI_level | Air quality level (default 1) | Read | 1=Good, 2=Moderate, 3=Unhealthy | |
| AV | 251 | cfgAQIUnhealthyScore | AQI Unhealthy Score (default 40) | Write | ||
| AV | 252 | cfgAQIModerateScore | AQI Moderate Score (default 80) | Write | ||
| AV | 253 | CfgAlarmAQIDeadband | Alarm AQI deadband (default 2) | Write | ||
| AV | 254 | CfgAlarmAQITimeDelay | Alarm AQI time delay (default 60(s)) | s | Write | |
| MV | 26 | CfgAlarmAQILimitEnable | Alarm AQI limit enable (default 4) | Write | 1=AQI Moderate Limit And Unhealthy Limit Disable, 2=AQI Moderate Limit Enable, 3=AQI Unhealthy Limit Enable, 4=AQI Moderate And Unhealthy Limit Enable | |
| AV | 301 | cfgLedRingBrightness | Led Ring Brightness (default 50) | Write | ||
| AV | 302 | CfgLedRingDimBrightness | Led Ring Dim Brightness (default 10) | Write | ||
| AV | 321 | CfgLcdBrightness | Lcd Brightness (default 80) | Write | ||
| AV | 322 | CfgLcdDimBrightness | Lcd Dim Brightness (default 40) | Write | ||
| AV | 341 | CfgLcdAutoCycleTime | Lcd Auto Cycle Time (default 5(s)) | s | Write | |
| AV | 361 | cfgLedRingLcdTimeoutTime | Led Ring Lcd Timeout Time (default 0(s)) | s | Write | |
| AV | 362 | cfgLedRingLcdDimTime | Led Ring Lcd Dim Time (default 10(s)) | s | Write | |
| AV | 381 | CfgIsParaDisplayed | Bit mask of values shown on the LCD (default TR50-5D: 63 TR50-3D: 15) | Write | ||
| BV | 21 | cfgLedRingLcdEnable | Led Ring Lcd Enable (default 1) | Write | 0=Off, 1=On | |
| MV | 61 | CfgLedRingColorOption | Led Ring Color Option (default 1) | Write | 1=Color mode, 2=Neutral mode | |
| MV | 81 | CfgLcdParameterSwitch | Lcd Parameter Switch (default 1) | Write | TR50-5D: 1=Auto cycling (default), 2=Manual + AQI (as the static page), 3=Manual + Temperature (as the static page), 4=Manual + Humidity (as the static page), 5=Manual + CO2 (as the static page), 6=Manual + PM2.5 (as the static page), 7=Manual + TVOC (as the static page), 8=Manual + no static page; TR50-3D: 1=Auto cycling (default), 2=Manual + AQI (as the static page), 3=Manual + Temperature (as the static page), 4=Manual + Humidity (as the static page), 5=Manual + CO2 (as the static page), 6=Manual + no static page | |
| MV | 41 | CfgAlarmIndicatorEnable | Alarm Indicator Enable (default 4) | Write | 1=Disable, 2=cfgOutOfRangeAlarm IndicatorEnable, 3=cfgSensorFailureAlarm IndicatorEnable, 4=cfgOutOfRangeAlarm IndicatorEnable && cfgSensorFailureAlarm IndicatorEnable | |
| AV | 500 | MstpHeaderCrcErrCount | MS/TP header CRC error count | Read | ||
| AV | 501 | MstpDataCrcErrCount | MS/TP data CRC error count | Read | ||
| BV | 41 | CfgIsMstpBadCrcClear | Clear the CRC error counters (default 1) | Write | 0=Uncleared, 1=Cleared | |
| BV | 1 | cfgIsAlarmLocalDetectionEnable | Local alarm detection on/off (default 1) | Write | 0=Disable, 1=Enable |
No points match these filters.
Object ID lookup: Honeywell TR50 indoor air quality sensor point IDs by name
AI1SS_AI_SensorReading_TempAI2SS_AI_SensorReading_HumiAI3SS_AI_SensorReading_CO2AI4SS_AI_SensorReading_PM2.5AI5SS_AI_SensorReading_TVOCAI6SS_AI_AIR_QUALITY_SCOREAI7SS_AI_SensorReading_PM1.0AI8SS_AI_SensorReading_PM10AV1CfgAlarmTempLowLimitAV2CfgAlarmTempHighLimitAV3CfgAlarmTempDeadbandAV4CfgAlarmTempTimeDelayMV1SS_MV_OutofRange_TempAV281CfgTempSensorOffsetMV21CfgAlarmTempLimitEnableMV101cfgDisplayUnitTempAV51CfgAlarmHumiLowLimitAV52CfgAlarmHumiHighLimitAV53CfgAlarmHumiDeadbandAV54CfgAlarmHumiTimeDelayMV2SS_MV_OutofRange_HumiMV22cfgAlarmHumiLimitEnableAV282cfgHumiSensorOffsetAV101CfgAlarmCO2HighLimitAV102CfgAlarmCO2HighHighLimitAV103CfgAlarmCO2DeadbandAV104CfgAlarmCO2TimeDelayAV283cfgCO2SensorOffsetMV3SS_MV_OutOfRange_CO2MV23CfgAlarmCO2LimitEnableAV151CfgAlarmPM2.5HighLimitAV152cfgAlarmPM2.5HighHighLimitAV153CfgAlarmPM2.5DeadbandAV154CfgAlarmPM2.5TimeDelayAV284CfgPM2.5SensorOffsetMV4SS_MV_OutOfRange_PM2.5MV24CfgAlarmPM2.5LimitEnableAV287CfgPM1.0SensorOffsetAV288CfgPM10SensorOffsetAV201CfgAlarmTVOCHighLimitAV202CfgAlarmTVOCHighHighLimitAV203CfgAlarmTVOCDeadbandAV204CfgAlarmTVOCTimeDelayAV285CfgTVOCSensorOffsetMV5SS_MV_OutOfRange_TVOCMV25CfgAlarmTVOCLimitEnableMV102cfgDisplayUnitTVOCMV6SS_MV_AQI_levelAV251cfgAQIUnhealthyScoreAV252cfgAQIModerateScoreAV253CfgAlarmAQIDeadbandAV254CfgAlarmAQITimeDelayMV26CfgAlarmAQILimitEnableAV301cfgLedRingBrightnessAV302CfgLedRingDimBrightnessAV321CfgLcdBrightnessAV322CfgLcdDimBrightnessAV341CfgLcdAutoCycleTimeAV361cfgLedRingLcdTimeoutTimeAV362cfgLedRingLcdDimTimeAV381CfgIsParaDisplayedBV21cfgLedRingLcdEnableMV61CfgLedRingColorOptionMV81CfgLcdParameterSwitchMV41CfgAlarmIndicatorEnableAV500MstpHeaderCrcErrCountAV501MstpDataCrcErrCountBV41CfgIsMstpBadCrcClearBV1cfgIsAlarmLocalDetectionEnable
Integration notes
- Objects created depend on the SKU: the 5-parameter models (TR50-5x) have PM2.5 and TVOC; the 3-parameter models do not.
- The guide prints CO2 names with the 2 as a subscript (e.g. 'CO 2'); names here join them (SS_AI_SensorReading_CO2). Name capitalisation (cfg / Cfg) is as printed.
- Defaults are given in the descriptions. Temperature-type settings follow the display unit (MV 101).
- CfgIsParaDisplayed (AV 381) is a bit mask of what the LCD shows; the bit meanings differ between TR50-5D and TR50-3D.
- The BTL PICS (Dec 2022) lists the same instances with ranges but no names.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TR50 indoor air quality sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Honeywell TR50 indoor air quality sensor (BACnet MS/TP)
How many BACnet points does the Honeywell TR50 indoor air quality sensor (BACnet MS/TP) have?
This list has 69 BACnet objects: 8 analog inputs, 41 analog values, 3 binary values, 17 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Honeywell TR50 indoor air quality sensor (BACnet MS/TP) BACnet points are writable?
58 of the 69 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Honeywell TR50 indoor air quality sensor (BACnet MS/TP) BACnet documentation?
Honeywell does not publish it on its own website. This list comes from TR50 User Guide, section 4.4.5 BACnet Points, a copy hosted by Stromquist & Company at https://lit.stromquist.com/docs/honeywell/tr50user.pdf. Ask Honeywell or its representative for the current revision.
What are the minimum BACnet points to integrate the Honeywell TR50 indoor air quality sensor (BACnet MS/TP)?
Start with AI 1 SS_AI_SensorReading_Temp (Space temperature); AI 2 SS_AI_SensorReading_Humi (Space relative humidity, %); AI 3 SS_AI_SensorReading_CO2 (CO2, ppm); AI 4 SS_AI_SensorReading_PM2.5 (PM2.5, ug/m3); AI 5 SS_AI_SensorReading_TVOC (TVOC, ppb or ug/m3); AI 6 SS_AI_AIR_QUALITY_SCORE (Air quality score, 0-100); MV 3 SS_MV_OutOfRange_CO2 (CO2 state: normal, over high, over high-high).
How do I check these points on the real TR50 indoor air quality sensor (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Honeywell BACnet points lists
- Thermostat (fixed-function controller)
Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat
Honeywell TB3026B and TB3026B-W BACnet FF wall-mount fixed-function thermostats, all 19 built-in applications (platform objects).
Also known as: TB3026B, TB3026B-W, BACnet FF, Honeywell BACnet Fixed Function thermostat, 31-00098 - Thermostat (fan coil, conventional and heat pump)
Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)
Honeywell TC300 and Wi-Fi TC320 commercial touchscreen thermostats for fan coils, conventional units and heat pumps.
Also known as: TC300, TC320, TC300B-G, TC300C-G, TC320B-G, TC320C-G, T300 Series - Thermostat (rooftop, heat pump and fan coil)
Honeywell TC500A Commercial Thermostat
Honeywell TC500A commercial touchscreen thermostat for conventional rooftop units, heat pumps and fan coils, with economizer, DCV and Sylk bus sensors.
Also known as: TC500A, TC500A-N, TC500
Source: TR50 User Guide, section 4.4.5 BACnet Points. Object names, instances and units are reproduced as published; descriptions are our own.