Thermostat (fixed-function controller) · BACnet points list

Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The BACnet FF (TB3026B) is a fixed-function thermostat/controller on BACnet MS/TP that runs one of 19 built-in applications (fan coils, heat pumps, unit ventilators and others). This list is the platform's ordered list of named control points: setpoints and limits, displayed and sensed values, occupancy and schedule control, maintenance timers, humidity setpoints and the many screen-control objects. The application in use adds its own AV 0-89 / BV 0-63 points, documented per application in the guide.

This page lists 245 BACnet objects for the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat — 208 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Honeywell’s documentation hosted by Galco, not by Honeywell itself, so treat it as unofficial.

Manufacturer
Honeywell
Model
TB3026B / TB3026B-W BACnet FF fixed-function thermostat
Equipment
Thermostat (fixed-function controller)
Equipment type
Thermostats, sensors & meters
BACnet objects
245 (208 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
9999
Also known as
TB3026B, TB3026B-W, BACnet FF, Honeywell BACnet Fixed Function thermostat, 31-00098
Source document
BACnet FF Installation and Operations Guide · 31-00098-01 (unofficial copy, hosted by Galco)
Download CSV 245 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Honeywell’s current documentation and the live device before use. Not official Honeywell information. Terms of use.

BMS integration notes: Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat

Integration in brief

Set the MS/TP MAC and device instance in the ISU menu, then write occupancy (BV 40, or let the internal schedule run) and the occupied setpoint AV 90. Read the sensed room temperature, the active heating/cooling setpoints and the occupied status. Application-specific outputs and alarms are in the per-application tables of the guide.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 90Setpoint (SP)Occupied space setpointWrite
AV 95Unoccupied Cooling SPUnoccupied cooling setpointWrite
AV 96Unoccupied Heating SPUnoccupied heating setpointWrite
BV 133Enable internal scheduleInternal schedule on/offWrite
AV 104Sensed Room TemperatureRoom temperature (built-in sensor)Read
BV 67Occupied/Unoccupied StatusOccupied / unoccupied statusRead
AV 99Current Cooling SPActive cooling setpointRead
AV 100Current Heating SPActive heating setpointRead

Enable & remote start

Occupancy comes from BV 40 (priority array) or the internal schedule (BV 133).

Network setup

Watch out for

Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

245 of 245 shown
Type
AnalogBinaryMulti-state
Access
Show
Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet Points List
DescriptionStates
AVmin90Setpoint (SP)Occupied space setpoint°F/°CWrite
AV92Setpoint Low LimitSetpoint low limit°F/°CWrite
AV94Heating SP OffsetHeating setpoint offset°F/°CWrite
AVmin96Unoccupied Heating SPUnoccupied heating setpoint°F/°CWrite
AV98After Hours TimerAfter-hours timerWrite
AVmin100Current Heating SPActive heating setpoint°F/°CRead
AV102Displayed Room HumidityRoom humidity shown on the display%RHRead
AVmin104Sensed Room TemperatureRoom temperature from the built-in sensor°F/°CRead
AV106Demand OffsetDemand (standby) offsetWrite
AV108SP Mode Cooling SPCooling setpoint in setpoint mode°F/°CWrite
AV110SP Mode Setpoint ModelSetpoint Mode: Chooses the setpoint model, and also selects the layout of...Write0.0=use OFF Format (no setpoints shown), 1.0=use 1-setpoint format (cooling), 2.0=use 1-setpoint format (heating), 3.0=use 2-setpoint format Occupancy Mode: Ignored
AV113SP Override Mode AVIn setpoint mode: setpoint override stateWrite1.0=scheduled, 2.0=temporary, 3.0=permanent, 4.0=vacation, 5.0=initial
AV115Filter Runtime LimitFilter runtime limitHoursRead
AV117UV Lamp Runtime LimitUV Lamp runtime limitHoursRead
AV119Humidifier Pad Runtime LimitHumidifier Pad runtime limitHoursRead
AV121Dehumidifier SP MaxDehumidifier max% RHWrite
AV123Set system to Occupancy modeSets system to Occupancy modeWrite
AV125Humidity Pad Change ReminderEnables the humidity pad change reminderWrite
AV127Daylight savingsSets Daylight savings to Off, pre-2007 scheme, or post-2007 schemeWrite
AV129Weekday periods ISU valueSchedule periods per weekday (ISU 540)Write2=Two schedule periods per day, 4=Four schedule periods per day
AV131Vacation days remainingIn setpoint mode: number of days remaining in a vacation overrideDaysWrite
AV133ISU mode security PINAllows access to ISU mode only by authorized usersWrite
AV135Humidifier SP MaxHumidifier max% RHWrite
AV137Fan Setting Display FormatSelects the format in which fan settings are shown on the displayWrite
AV139Sensed Humidity OffsetLimited to +/- 5%%RHWrite
AV141Sensed Outside Air Humidity OffsetAdded to AV-107 to generate OA humidity on the details screens%RHWrite
AV211ULHC left characterCustom screen field settingWrite
AV213URHC numberCustom screen field settingWrite
AV215URHC 1 charCustom screen field settingWrite
AV217URHC maximumCustom screen field settingWrite
AV219LLHC numberCustom screen field settingWrite
AV221LLHC 1 charCustom screen field settingWrite
AV223LLHC maximumCustom screen field settingWrite
AV91Setpoint High LimitSetpoint high limit°F/°CWrite
AV93Cooling SP OffsetCooling setpoint offset°F/°CWrite
AVmin95Unoccupied Cooling SPUnoccupied cooling setpoint°F/°CWrite
AV97After Hours Timer LimitAfter-hours override limithWrite
AVmin99Current Cooling SPActive cooling setpoint°F/°CRead
AV101Displayed Room TemperatureRoom temperature shown on the display°F/°CRead
AV103Displayed Outside Air TemperatureOutdoor temperature shown°F/°CRead
AV105Sensed Room HumidityRoom humidity from the built-in sensor%RHRead
AV107Displayed Outside HumidityOutdoor humidity shown%RHRead
AV109SP Mode Heating SPHeating setpoint in setpoint mode°F/°CWrite
AV111SYSTEM Setpoint ModelProvides a compatible output from the SYSTEM control that can be...Write0.0=OFF selected, 1.0=COOL selected, 2.0=HEAT/EM HEAT selected, 3.0=AUTO selected
AV114Filter RuntimeCurrent filter runtime hoursHoursWrite
AV116UV Lamp RuntimeCurrent UV Lamp runtime hoursHoursWrite
AV118Humidifier Pad RuntimeCurrent Humidifier Pad runtime hoursHoursWrite
AV120Dehumidifier SetpointCurrent dehumidifier setpoint% RHWrite
AV122Dehumidifier SP MinDehumidifier min% RHWrite
AV124Filter Change ReminderEnables the filter change reminderWrite
AV126UV Lamp Change ReminderEnables the UV lamp change reminderWrite
AV128Keypad lockLocks the keypadWrite
AV130Hold until timeIn setpoint mode: minute of the day (0-1440) at which a temporary or vMinutesWrite
AV132Field service mode security PINAllows access to Field Service mode only by authorized usersWrite
AV134Humidifier SetpointCurrent humidifier setpoint% RHWrite
AV136Humidifier SP MinHumidifier min% RHWrite
AV138Sensed Temperature OffsetLimited to +/- 4 degrees F°F/°CWrite
AV140Sensed Outside Air Temperature OffsetLimited to +/- 4 degrees F. Added to Sensed Outside Air Temperature...°F/°CWrite
AV210UHLH numberCustom screen field settingWrite
AV212ULHC right characterCustom screen field settingWrite
AV214URHC 10 charCustom screen field settingWrite
AV216URHC minimumCustom screen field settingWrite
AV218URHC deltaCustom screen field settingWrite
AV220LLHC 10 charCustom screen field settingWrite
AV222LLHC minimumCustom screen field settingWrite
AV224LLHC deltaCustom screen field settingWrite
AV225LLHC 1000 charCustom screen field settingWrite
AV227LRHC numberCustom screen field settingWrite
AV229LRHC 1 charCustom screen field settingWrite
AV231LRHC maximumCustom screen field settingWrite
BV64Time Schedule OutputSchedule output (occupied when on)Read
BV66After Hours Timer StatusAfter-hours timer runningRead
BV68Field service LockoutField service lockoutWrite
BV71English (OFF) / Metric (ON)English (off) or metric (on)Write
BV73Fan stage 2Fan stage 2 output statusRead
BV77Heating ICONDisplay 'heat on' iconWrite
BV79Backlight ONBacklight onWrite
BV81Select Hotel ModeHotel modeWrite
BV8324Hr Time Format24-hour clockWrite
BV100Enable OSA TempDisplay the OSA temperature as appropriateWrite
BV102Enable System ControlAllow the 'SYSTEM' control to be visibleWrite
BV104Enable DOWAllow day of week to be shown is possibleWrite
BV106Show WaitDisplay 'Wait'Write
BV108Show RecoveryDisplay 'Recovery'Write
BV110Show DEHUMIDIFIERDisplay 'DEHUMIDIFIER'Write
BV112Force CHANGE UV LAMPForce 'CHANGE UV LAMP' to be displayed (can also automatically be...Write
BV114Disable SCHED keyIf set, the user is not allowed to view schedulesWrite
BV116Disable CLOCK keyAllow 'CLOCK' key to be used to set clock (if appropriate)Write
BV118Allow System HEATAllow system HEATWrite
BV120Allow System AUTOAllow system AUTOWrite
BV122System HEAT ModeSystem HEAT modeWrite
BV124System AUTO ModeSystem AUTO modeWrite
BV130Disable Vacation HOLD keyAllow 'HOLD' key to be used to access the standard Vacation Hold UI (if...Write
BVmin133Enable internal scheduleInternal 7-day scheduling is enabled (subject to other factors)Write
BV135Filter ONAccumulator ONWrite
BV137UV Lamp ONAccumulator ONWrite
BV139Humidifier Pad ONAccumulator ONWrite
BV141Disable schedule editInhibits screen EDIT keyWrite
BV143Enable humidifier setpoint on detail screensEnable humidifier setpoint on detail screens (also requires humidity to be...Write
AV226LLHC 100 charCustom screen field settingWrite
AV228LRHC 10 charCustom screen field settingWrite
AV230LRHC minimumCustom screen field settingWrite
AV232LRHC deltaCustom screen field settingWrite
BV65User ON/OFF in Occupied ModeUser on/off in occupied modeWrite
BVmin67Occupied/Unoccupied StatusOccupied / unoccupied statusRead
BV69Swap English/MetricSwap English / metric displayWrite
BV72Fan stage 1Fan stage 1 output statusRead
BV74Fan stage 3Fan stage 3 output statusRead
BV78Cooling ICONDisplay 'cool on' iconWrite
BV80Enable Fan Speed ControlAllow the 'FAN' control to be visible to the end userWrite
BV82Enable Time DisplayShow timeWrite
BV84Enable Space HumidityDisplay space humidity as appropriateWrite
BV101Enable OSA HumidityDisplay outside humidity as appropriateWrite
BV103Hide Fan and SystemHide the FAN and SYSTEM controls in unoccupied mode (regardless of other...Write
BV105Show Unocc SetpointsDisplay the unoccupied heating/cooling setpoints in unoccupied modeWrite
BV107Show Aux heat onDisplay 'Aux heat on'Write
BV109Show FROSTDisplay 'FROST'Write
BV111Force CHANGE FILTERForce 'CHANGE FILTER' to be displayed (can also be automatically displayed...Write
BV113Force CHANGE HUMIDIFIER PADForce 'CHANGE HUMIDIFIER PAD' to be displayed (can also be displayed due...Write
BV115Disable Permanent HOLD keyAllow 'HOLD' key to be used to access the Permanent Hold UIWrite
BV117Allow System OFFAllow system OFFWrite
BV119Allow System COOLAllow system COOLWrite
BV121Allow System EM HEATAllow system EM HEATWrite
BV123System COOL ModeSystem COOL modeWrite
BV125System EM HEAT ModeSystem EM HEAT modeWrite
BV131Hotel Standby ModeSet Active by DDC to indicate to the display that DDC is controlling to...Write
BV134Filter EnableEnable filter timer and automatic 'change filter' warningWrite
BV136UV Lamp EnableEnable UV Lamp timer and automatic 'UV Lamp' warningWrite
BV138Humidifier Pad EnableEnable Humidifier Pad timer and automatic 'Humidifier Pad' warningWrite
BV140Enable dehumidifier setpoint on detail screenEnable dehumidifier setpoint on detail screen (also requires humidity to...Write
BV142Master OFFNo effectWrite
BV144Enable AUTO/OFF user selection on humidifier detail screenEnable AUTO/OFF user selection on humidifier detail screenWrite
BV145User humidifier AUTO/OFF selectionUser humidifier AUTO/OFF selectionWrite
BV147User dehumidifier AUTO/OFF selectionUser dehumidifier AUTO/OFF selectionWrite
BV210Custom 1 EnableCustom screen element / keyWrite
BV212ULHC enableCustom screen element / keyWrite
BV214ULHC lead zeroCustom screen element / keyWrite
BV216URHC decimalCustom screen element / keyWrite
BV218URHC editCustom screen element / keyWrite
BV220LLHC lead zeroCustom screen element / keyWrite
BV222LRHC enableCustom screen element / keyWrite
BV224LRHC lead zeroCustom screen element / keyWrite
BV226LRHC leading 1Custom screen element / keyWrite
BV228Mon textCustom screen element / keyWrite
BV230Wed textCustom screen element / keyWrite
BV232Fri textCustom screen element / keyWrite
BV234Sun textCustom screen element / keyWrite
BV236Tue checkCustom screen element / keyWrite
BV238Thu checkCustom screen element / keyWrite
BV240Sat checkCustom screen element / keyWrite
BV242Ok to pickCustom screen element / keyWrite
BV244ChangeCustom screen element / keyWrite
BV246UV LampCustom screen element / keyWrite
BV250InsideCustom screen element / keyWrite
BV253Set toCustom screen element / keyWrite
BV255Heat OnCustom screen element / keyWrite
BV257Cool OnCustom screen element / keyWrite
BV259FrostCustom screen element / keyWrite
BV261RecoveryCustom screen element / keyWrite
BV263PmCustom screen element / keyWrite
BV265DaysCustom screen element / keyWrite
BV268PermanentCustom screen element / keyWrite
BV270Cancel PeriodCustom screen element / keyWrite
BV272DECustom screen element / keyWrite
BV274LRHC HumidityCustom screen element / keyWrite
BV276LRHC Adj ArrowsCustom screen element / keyWrite
BV146Enable AUTO/OFF user selection on dehumidifier detail screenEnable AUTO/OFF user selection on dehumidifier detail screenWrite
BV200AIn Current ModeAI 0: current mode selectWrite
BV201AIn Current ModeAI 1: current mode selectWrite
BV202AIn Current ModeAI 2: current mode selectWrite
BV211ResetCustom screen element / keyWrite
BV213ULHC decimalCustom screen element / keyWrite
BV215URHC enableCustom screen element / keyWrite
BV217URHC lead zeroCustom screen element / keyWrite
BV219LLHC enableCustom screen element / keyWrite
BV221LLHC editCustom screen element / keyWrite
BV223LRHC decimalCustom screen element / keyWrite
BV225LRHC editCustom screen element / keyWrite
BV227Day boxesCustom screen element / keyWrite
BV229Tue textCustom screen element / keyWrite
BV231Thu textCustom screen element / keyWrite
BV233Sat textCustom screen element / keyWrite
BV235Mon checkCustom screen element / keyWrite
BV237Wed checkCustom screen element / keyWrite
BV239Fri checkCustom screen element / keyWrite
BV241Sun checkCustom screen element / keyWrite
BV243Screen lockedCustom screen element / keyWrite
BV245FilterCustom screen element / keyWrite
BV247Hum PadCustom screen element / keyWrite
BV251ULHC % HumidityCustom screen element / keyWrite
BV254AuxCustom screen element / keyWrite
BV256WaitCustom screen element / keyWrite
BV258Heat AdjustCustom screen element / keyWrite
BV260FollowCustom screen element / keyWrite
BV262URHC Adj ArrowsCustom screen element / keyWrite
BV264AmCustom screen element / keyWrite
BV266LLHC Adj ArrowsCustom screen element / keyWrite
BV269Hold UntilCustom screen element / keyWrite
BV271OutsideCustom screen element / keyWrite
BV273HUMIDIFIERCustom screen element / keyWrite
BV275MinutesCustom screen element / keyWrite
BV277LLRC %Custom screen element / keyWrite
BV278LLRC minusCustom screen element / keyWrite
BV280VentCustom screen element / keyWrite
BV282Tue keyCustom screen element / keyWrite
BV284Thu keyCustom screen element / keyWrite
BV286Sat keyCustom screen element / keyWrite
BV288URHC up keyCustom screen element / keyWrite
BV290LRHC up keyCustom screen element / keyWrite
BV292LLHC up keyCustom screen element / keyWrite
BV294RESET keyCustom screen element / keyWrite
BV297FAN keyCustom screen element / keyWrite
BV300AOn Current ModeAO 0: current mode detectedRead
BV301AOn Current ModeAO 1: current mode detectedRead
MV0Time ModeDevice's time handling capability: Normal clock operation willRead1=Time Of Day Unknown Mode, 2=Time Of Day Available Mode, 3=Date/Time Available Mode
MV2Keypad LockKeypad access levelRead1=full access, 2=setpoints only, 3=locked
MV4SP IncrementAmount of change in setpoint per arrow pressRead
MV6User SYSTEM selectionDisplay / screen settingRead
MV8Fan OFF textDisplay / screen settingRead
MV10Fan stage 2 textDisplay / screen settingRead
MV12Schedule FormatThis point is a human-friendly version of AV-129, ISU parameter 540 (see...Read1=2 commands per day, 2=4 commands per day
MV20ULHC modeDisplay / screen settingRead
MV22LLHC modeDisplay / screen settingRead
BV279Cool AdjCustom screen element / keyWrite
BV281Mon keyCustom screen element / keyWrite
BV283Wed keyCustom screen element / keyWrite
BV285Fri keyCustom screen element / keyWrite
BV287Sun keyCustom screen element / keyWrite
BV289URHC dn keyCustom screen element / keyWrite
BV291LRHC dn keyCustom screen element / keyWrite
BV293LLHC dn keyCustom screen element / keyWrite
BV295CANCEL PERIOD keyCustom screen element / keyWrite
BV298SYSTEM keyCustom screen element / keyWrite
BV400AIn PullupAI 0: pull-up enableWrite
BV401AIn PullupAI 1: pull-up enableWrite
BV402AIn PullupAI 2: pull-up enableWrite
MV1Schedule ModelDevice's schedule modelRead1=Setpoint, 2=Occupancy
MV3DLS ModeMode of Daylight Saving operationRead1=OFF, 2=Auto (pre-2007), 3=Auto (2007 and later)
MV5Schedule IncrementAmount of change in schedule times per arrow pressRead
MV7Fan statusDisplay / screen settingRead
MV9Fan stage 1 textDisplay / screen settingRead
MV11Fan stage 3 textDisplay / screen settingRead
MV13SP Override ModeIn setpoint mode: setpoint override stateRead1=scheduled, 2=temporary, 3=permanent, 4=vacation
MV21URHC modeDisplay / screen settingRead
MV23LRHC modeDisplay / screen settingRead
Object ID lookup: Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TB3026B / TB3026B-W BACnet FF fixed-function thermostat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat

How many BACnet points does the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat have?

This list has 245 BACnet objects: 74 analog values, 153 binary values, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet points are writable?

208 of the 245 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet documentation?

Honeywell does not publish it on its own website. This list comes from BACnet FF Installation and Operations Guide (31-00098-01), a copy hosted by Galco at https://docs.galco.com/techdoc/hnwl/31-00098_opm.pdf. Ask Honeywell or its representative for the current revision.

What are the minimum BACnet points to integrate the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat?

Start with AV 90 Setpoint (SP) (Occupied space setpoint); AV 95 Unoccupied Cooling SP (Unoccupied cooling setpoint); AV 96 Unoccupied Heating SP (Unoccupied heating setpoint); BV 133 Enable internal schedule (Internal schedule on/off); AV 104 Sensed Room Temperature (Room temperature (built-in sensor)); BV 67 Occupied/Unoccupied Status (Occupied / unoccupied status); AV 99 Current Cooling SP (Active cooling setpoint); AV 100 Current Heating SP (Active heating setpoint).

How do I enable BMS control of the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat?

Occupancy comes from BV 40 (priority array) or the internal schedule (BV 133).

How do I check these points on the real TB3026B / TB3026B-W BACnet FF fixed-function thermostat?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Honeywell BACnet points lists