- TB3026B / TB3026B-W BACnet FF fixed-function thermostat
Thermostat (fixed-function controller) · BACnet points list
Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet points list
Updated 12 November 2026Unofficial source
The BACnet FF (TB3026B) is a fixed-function thermostat/controller on BACnet MS/TP that runs one of 19 built-in applications (fan coils, heat pumps, unit ventilators and others). This list is the platform's ordered list of named control points: setpoints and limits, displayed and sensed values, occupancy and schedule control, maintenance timers, humidity setpoints and the many screen-control objects. The application in use adds its own AV 0-89 / BV 0-63 points, documented per application in the guide.
This page lists 245 BACnet objects for the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat — 208 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Honeywell’s documentation hosted by Galco, not by Honeywell itself, so treat it as unofficial.
- Manufacturer
- Honeywell
- Model
- TB3026B / TB3026B-W BACnet FF fixed-function thermostat
- Equipment
- Thermostat (fixed-function controller)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 245 (208 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 9999
- Also known as
- TB3026B, TB3026B-W, BACnet FF, Honeywell BACnet Fixed Function thermostat, 31-00098
- Source document
- BACnet FF Installation and Operations Guide · 31-00098-01 (unofficial copy, hosted by Galco)
Reference only, provided as-is: verify against Honeywell’s current documentation and the live device before use. Not official Honeywell information. Terms of use.
BMS integration notes: Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat
Set the MS/TP MAC and device instance in the ISU menu, then write occupancy (BV 40, or let the internal schedule run) and the occupied setpoint AV 90. Read the sensed room temperature, the active heating/cooling setpoints and the occupied status. Application-specific outputs and alarms are in the per-application tables of the guide.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 90 | Setpoint (SP) | Occupied space setpoint | Write |
| AV 95 | Unoccupied Cooling SP | Unoccupied cooling setpoint | Write |
| AV 96 | Unoccupied Heating SP | Unoccupied heating setpoint | Write |
| BV 133 | Enable internal schedule | Internal schedule on/off | Write |
| AV 104 | Sensed Room Temperature | Room temperature (built-in sensor) | Read |
| BV 67 | Occupied/Unoccupied Status | Occupied / unoccupied status | Read |
| AV 99 | Current Cooling SP | Active cooling setpoint | Read |
| AV 100 | Current Heating SP | Active heating setpoint | Read |
Enable & remote start
Occupancy comes from BV 40 (priority array) or the internal schedule (BV 133).
Network setup
- Factory defaults: MS/TP MAC 0 (valid 0-127), device instance 0009999 (valid 0-4194302).
- MS/TP MAC and device instance are set through ISU parameters on the thermostat.
- Application selection is an ISU / setup setting; it decides which AV 0-89 / BV 0-63 points are used.
Watch out for
- Many BVs and AVs above 200 only control the display layout; do not map them for HVAC control.
Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 90 | Setpoint (SP) | Occupied space setpoint | °F/°C | Write | |
| AV | 92 | Setpoint Low Limit | Setpoint low limit | °F/°C | Write | |
| AV | 94 | Heating SP Offset | Heating setpoint offset | °F/°C | Write | |
| AVmin | 96 | Unoccupied Heating SP | Unoccupied heating setpoint | °F/°C | Write | |
| AV | 98 | After Hours Timer | After-hours timer | Write | ||
| AVmin | 100 | Current Heating SP | Active heating setpoint | °F/°C | Read | |
| AV | 102 | Displayed Room Humidity | Room humidity shown on the display | %RH | Read | |
| AVmin | 104 | Sensed Room Temperature | Room temperature from the built-in sensor | °F/°C | Read | |
| AV | 106 | Demand Offset | Demand (standby) offset | Write | ||
| AV | 108 | SP Mode Cooling SP | Cooling setpoint in setpoint mode | °F/°C | Write | |
| AV | 110 | SP Mode Setpoint Model | Setpoint Mode: Chooses the setpoint model, and also selects the layout of... | Write | 0.0=use OFF Format (no setpoints shown), 1.0=use 1-setpoint format (cooling), 2.0=use 1-setpoint format (heating), 3.0=use 2-setpoint format Occupancy Mode: Ignored | |
| AV | 113 | SP Override Mode AV | In setpoint mode: setpoint override state | Write | 1.0=scheduled, 2.0=temporary, 3.0=permanent, 4.0=vacation, 5.0=initial | |
| AV | 115 | Filter Runtime Limit | Filter runtime limit | Hours | Read | |
| AV | 117 | UV Lamp Runtime Limit | UV Lamp runtime limit | Hours | Read | |
| AV | 119 | Humidifier Pad Runtime Limit | Humidifier Pad runtime limit | Hours | Read | |
| AV | 121 | Dehumidifier SP Max | Dehumidifier max | % RH | Write | |
| AV | 123 | Set system to Occupancy mode | Sets system to Occupancy mode | Write | ||
| AV | 125 | Humidity Pad Change Reminder | Enables the humidity pad change reminder | Write | ||
| AV | 127 | Daylight savings | Sets Daylight savings to Off, pre-2007 scheme, or post-2007 scheme | Write | ||
| AV | 129 | Weekday periods ISU value | Schedule periods per weekday (ISU 540) | Write | 2=Two schedule periods per day, 4=Four schedule periods per day | |
| AV | 131 | Vacation days remaining | In setpoint mode: number of days remaining in a vacation override | Days | Write | |
| AV | 133 | ISU mode security PIN | Allows access to ISU mode only by authorized users | Write | ||
| AV | 135 | Humidifier SP Max | Humidifier max | % RH | Write | |
| AV | 137 | Fan Setting Display Format | Selects the format in which fan settings are shown on the display | Write | ||
| AV | 139 | Sensed Humidity Offset | Limited to +/- 5% | %RH | Write | |
| AV | 141 | Sensed Outside Air Humidity Offset | Added to AV-107 to generate OA humidity on the details screens | %RH | Write | |
| AV | 211 | ULHC left character | Custom screen field setting | Write | ||
| AV | 213 | URHC number | Custom screen field setting | Write | ||
| AV | 215 | URHC 1 char | Custom screen field setting | Write | ||
| AV | 217 | URHC maximum | Custom screen field setting | Write | ||
| AV | 219 | LLHC number | Custom screen field setting | Write | ||
| AV | 221 | LLHC 1 char | Custom screen field setting | Write | ||
| AV | 223 | LLHC maximum | Custom screen field setting | Write | ||
| AV | 91 | Setpoint High Limit | Setpoint high limit | °F/°C | Write | |
| AV | 93 | Cooling SP Offset | Cooling setpoint offset | °F/°C | Write | |
| AVmin | 95 | Unoccupied Cooling SP | Unoccupied cooling setpoint | °F/°C | Write | |
| AV | 97 | After Hours Timer Limit | After-hours override limit | h | Write | |
| AVmin | 99 | Current Cooling SP | Active cooling setpoint | °F/°C | Read | |
| AV | 101 | Displayed Room Temperature | Room temperature shown on the display | °F/°C | Read | |
| AV | 103 | Displayed Outside Air Temperature | Outdoor temperature shown | °F/°C | Read | |
| AV | 105 | Sensed Room Humidity | Room humidity from the built-in sensor | %RH | Read | |
| AV | 107 | Displayed Outside Humidity | Outdoor humidity shown | %RH | Read | |
| AV | 109 | SP Mode Heating SP | Heating setpoint in setpoint mode | °F/°C | Write | |
| AV | 111 | SYSTEM Setpoint Model | Provides a compatible output from the SYSTEM control that can be... | Write | 0.0=OFF selected, 1.0=COOL selected, 2.0=HEAT/EM HEAT selected, 3.0=AUTO selected | |
| AV | 114 | Filter Runtime | Current filter runtime hours | Hours | Write | |
| AV | 116 | UV Lamp Runtime | Current UV Lamp runtime hours | Hours | Write | |
| AV | 118 | Humidifier Pad Runtime | Current Humidifier Pad runtime hours | Hours | Write | |
| AV | 120 | Dehumidifier Setpoint | Current dehumidifier setpoint | % RH | Write | |
| AV | 122 | Dehumidifier SP Min | Dehumidifier min | % RH | Write | |
| AV | 124 | Filter Change Reminder | Enables the filter change reminder | Write | ||
| AV | 126 | UV Lamp Change Reminder | Enables the UV lamp change reminder | Write | ||
| AV | 128 | Keypad lock | Locks the keypad | Write | ||
| AV | 130 | Hold until time | In setpoint mode: minute of the day (0-1440) at which a temporary or v | Minutes | Write | |
| AV | 132 | Field service mode security PIN | Allows access to Field Service mode only by authorized users | Write | ||
| AV | 134 | Humidifier Setpoint | Current humidifier setpoint | % RH | Write | |
| AV | 136 | Humidifier SP Min | Humidifier min | % RH | Write | |
| AV | 138 | Sensed Temperature Offset | Limited to +/- 4 degrees F | °F/°C | Write | |
| AV | 140 | Sensed Outside Air Temperature Offset | Limited to +/- 4 degrees F. Added to Sensed Outside Air Temperature... | °F/°C | Write | |
| AV | 210 | UHLH number | Custom screen field setting | Write | ||
| AV | 212 | ULHC right character | Custom screen field setting | Write | ||
| AV | 214 | URHC 10 char | Custom screen field setting | Write | ||
| AV | 216 | URHC minimum | Custom screen field setting | Write | ||
| AV | 218 | URHC delta | Custom screen field setting | Write | ||
| AV | 220 | LLHC 10 char | Custom screen field setting | Write | ||
| AV | 222 | LLHC minimum | Custom screen field setting | Write | ||
| AV | 224 | LLHC delta | Custom screen field setting | Write | ||
| AV | 225 | LLHC 1000 char | Custom screen field setting | Write | ||
| AV | 227 | LRHC number | Custom screen field setting | Write | ||
| AV | 229 | LRHC 1 char | Custom screen field setting | Write | ||
| AV | 231 | LRHC maximum | Custom screen field setting | Write | ||
| BV | 64 | Time Schedule Output | Schedule output (occupied when on) | Read | ||
| BV | 66 | After Hours Timer Status | After-hours timer running | Read | ||
| BV | 68 | Field service Lockout | Field service lockout | Write | ||
| BV | 71 | English (OFF) / Metric (ON) | English (off) or metric (on) | Write | ||
| BV | 73 | Fan stage 2 | Fan stage 2 output status | Read | ||
| BV | 77 | Heating ICON | Display 'heat on' icon | Write | ||
| BV | 79 | Backlight ON | Backlight on | Write | ||
| BV | 81 | Select Hotel Mode | Hotel mode | Write | ||
| BV | 83 | 24Hr Time Format | 24-hour clock | Write | ||
| BV | 100 | Enable OSA Temp | Display the OSA temperature as appropriate | Write | ||
| BV | 102 | Enable System Control | Allow the 'SYSTEM' control to be visible | Write | ||
| BV | 104 | Enable DOW | Allow day of week to be shown is possible | Write | ||
| BV | 106 | Show Wait | Display 'Wait' | Write | ||
| BV | 108 | Show Recovery | Display 'Recovery' | Write | ||
| BV | 110 | Show DEHUMIDIFIER | Display 'DEHUMIDIFIER' | Write | ||
| BV | 112 | Force CHANGE UV LAMP | Force 'CHANGE UV LAMP' to be displayed (can also automatically be... | Write | ||
| BV | 114 | Disable SCHED key | If set, the user is not allowed to view schedules | Write | ||
| BV | 116 | Disable CLOCK key | Allow 'CLOCK' key to be used to set clock (if appropriate) | Write | ||
| BV | 118 | Allow System HEAT | Allow system HEAT | Write | ||
| BV | 120 | Allow System AUTO | Allow system AUTO | Write | ||
| BV | 122 | System HEAT Mode | System HEAT mode | Write | ||
| BV | 124 | System AUTO Mode | System AUTO mode | Write | ||
| BV | 130 | Disable Vacation HOLD key | Allow 'HOLD' key to be used to access the standard Vacation Hold UI (if... | Write | ||
| BVmin | 133 | Enable internal schedule | Internal 7-day scheduling is enabled (subject to other factors) | Write | ||
| BV | 135 | Filter ON | Accumulator ON | Write | ||
| BV | 137 | UV Lamp ON | Accumulator ON | Write | ||
| BV | 139 | Humidifier Pad ON | Accumulator ON | Write | ||
| BV | 141 | Disable schedule edit | Inhibits screen EDIT key | Write | ||
| BV | 143 | Enable humidifier setpoint on detail screens | Enable humidifier setpoint on detail screens (also requires humidity to be... | Write | ||
| AV | 226 | LLHC 100 char | Custom screen field setting | Write | ||
| AV | 228 | LRHC 10 char | Custom screen field setting | Write | ||
| AV | 230 | LRHC minimum | Custom screen field setting | Write | ||
| AV | 232 | LRHC delta | Custom screen field setting | Write | ||
| BV | 65 | User ON/OFF in Occupied Mode | User on/off in occupied mode | Write | ||
| BVmin | 67 | Occupied/Unoccupied Status | Occupied / unoccupied status | Read | ||
| BV | 69 | Swap English/Metric | Swap English / metric display | Write | ||
| BV | 72 | Fan stage 1 | Fan stage 1 output status | Read | ||
| BV | 74 | Fan stage 3 | Fan stage 3 output status | Read | ||
| BV | 78 | Cooling ICON | Display 'cool on' icon | Write | ||
| BV | 80 | Enable Fan Speed Control | Allow the 'FAN' control to be visible to the end user | Write | ||
| BV | 82 | Enable Time Display | Show time | Write | ||
| BV | 84 | Enable Space Humidity | Display space humidity as appropriate | Write | ||
| BV | 101 | Enable OSA Humidity | Display outside humidity as appropriate | Write | ||
| BV | 103 | Hide Fan and System | Hide the FAN and SYSTEM controls in unoccupied mode (regardless of other... | Write | ||
| BV | 105 | Show Unocc Setpoints | Display the unoccupied heating/cooling setpoints in unoccupied mode | Write | ||
| BV | 107 | Show Aux heat on | Display 'Aux heat on' | Write | ||
| BV | 109 | Show FROST | Display 'FROST' | Write | ||
| BV | 111 | Force CHANGE FILTER | Force 'CHANGE FILTER' to be displayed (can also be automatically displayed... | Write | ||
| BV | 113 | Force CHANGE HUMIDIFIER PAD | Force 'CHANGE HUMIDIFIER PAD' to be displayed (can also be displayed due... | Write | ||
| BV | 115 | Disable Permanent HOLD key | Allow 'HOLD' key to be used to access the Permanent Hold UI | Write | ||
| BV | 117 | Allow System OFF | Allow system OFF | Write | ||
| BV | 119 | Allow System COOL | Allow system COOL | Write | ||
| BV | 121 | Allow System EM HEAT | Allow system EM HEAT | Write | ||
| BV | 123 | System COOL Mode | System COOL mode | Write | ||
| BV | 125 | System EM HEAT Mode | System EM HEAT mode | Write | ||
| BV | 131 | Hotel Standby Mode | Set Active by DDC to indicate to the display that DDC is controlling to... | Write | ||
| BV | 134 | Filter Enable | Enable filter timer and automatic 'change filter' warning | Write | ||
| BV | 136 | UV Lamp Enable | Enable UV Lamp timer and automatic 'UV Lamp' warning | Write | ||
| BV | 138 | Humidifier Pad Enable | Enable Humidifier Pad timer and automatic 'Humidifier Pad' warning | Write | ||
| BV | 140 | Enable dehumidifier setpoint on detail screen | Enable dehumidifier setpoint on detail screen (also requires humidity to... | Write | ||
| BV | 142 | Master OFF | No effect | Write | ||
| BV | 144 | Enable AUTO/OFF user selection on humidifier detail screen | Enable AUTO/OFF user selection on humidifier detail screen | Write | ||
| BV | 145 | User humidifier AUTO/OFF selection | User humidifier AUTO/OFF selection | Write | ||
| BV | 147 | User dehumidifier AUTO/OFF selection | User dehumidifier AUTO/OFF selection | Write | ||
| BV | 210 | Custom 1 Enable | Custom screen element / key | Write | ||
| BV | 212 | ULHC enable | Custom screen element / key | Write | ||
| BV | 214 | ULHC lead zero | Custom screen element / key | Write | ||
| BV | 216 | URHC decimal | Custom screen element / key | Write | ||
| BV | 218 | URHC edit | Custom screen element / key | Write | ||
| BV | 220 | LLHC lead zero | Custom screen element / key | Write | ||
| BV | 222 | LRHC enable | Custom screen element / key | Write | ||
| BV | 224 | LRHC lead zero | Custom screen element / key | Write | ||
| BV | 226 | LRHC leading 1 | Custom screen element / key | Write | ||
| BV | 228 | Mon text | Custom screen element / key | Write | ||
| BV | 230 | Wed text | Custom screen element / key | Write | ||
| BV | 232 | Fri text | Custom screen element / key | Write | ||
| BV | 234 | Sun text | Custom screen element / key | Write | ||
| BV | 236 | Tue check | Custom screen element / key | Write | ||
| BV | 238 | Thu check | Custom screen element / key | Write | ||
| BV | 240 | Sat check | Custom screen element / key | Write | ||
| BV | 242 | Ok to pick | Custom screen element / key | Write | ||
| BV | 244 | Change | Custom screen element / key | Write | ||
| BV | 246 | UV Lamp | Custom screen element / key | Write | ||
| BV | 250 | Inside | Custom screen element / key | Write | ||
| BV | 253 | Set to | Custom screen element / key | Write | ||
| BV | 255 | Heat On | Custom screen element / key | Write | ||
| BV | 257 | Cool On | Custom screen element / key | Write | ||
| BV | 259 | Frost | Custom screen element / key | Write | ||
| BV | 261 | Recovery | Custom screen element / key | Write | ||
| BV | 263 | Pm | Custom screen element / key | Write | ||
| BV | 265 | Days | Custom screen element / key | Write | ||
| BV | 268 | Permanent | Custom screen element / key | Write | ||
| BV | 270 | Cancel Period | Custom screen element / key | Write | ||
| BV | 272 | DE | Custom screen element / key | Write | ||
| BV | 274 | LRHC Humidity | Custom screen element / key | Write | ||
| BV | 276 | LRHC Adj Arrows | Custom screen element / key | Write | ||
| BV | 146 | Enable AUTO/OFF user selection on dehumidifier detail screen | Enable AUTO/OFF user selection on dehumidifier detail screen | Write | ||
| BV | 200 | AIn Current Mode | AI 0: current mode select | Write | ||
| BV | 201 | AIn Current Mode | AI 1: current mode select | Write | ||
| BV | 202 | AIn Current Mode | AI 2: current mode select | Write | ||
| BV | 211 | Reset | Custom screen element / key | Write | ||
| BV | 213 | ULHC decimal | Custom screen element / key | Write | ||
| BV | 215 | URHC enable | Custom screen element / key | Write | ||
| BV | 217 | URHC lead zero | Custom screen element / key | Write | ||
| BV | 219 | LLHC enable | Custom screen element / key | Write | ||
| BV | 221 | LLHC edit | Custom screen element / key | Write | ||
| BV | 223 | LRHC decimal | Custom screen element / key | Write | ||
| BV | 225 | LRHC edit | Custom screen element / key | Write | ||
| BV | 227 | Day boxes | Custom screen element / key | Write | ||
| BV | 229 | Tue text | Custom screen element / key | Write | ||
| BV | 231 | Thu text | Custom screen element / key | Write | ||
| BV | 233 | Sat text | Custom screen element / key | Write | ||
| BV | 235 | Mon check | Custom screen element / key | Write | ||
| BV | 237 | Wed check | Custom screen element / key | Write | ||
| BV | 239 | Fri check | Custom screen element / key | Write | ||
| BV | 241 | Sun check | Custom screen element / key | Write | ||
| BV | 243 | Screen locked | Custom screen element / key | Write | ||
| BV | 245 | Filter | Custom screen element / key | Write | ||
| BV | 247 | Hum Pad | Custom screen element / key | Write | ||
| BV | 251 | ULHC % Humidity | Custom screen element / key | Write | ||
| BV | 254 | Aux | Custom screen element / key | Write | ||
| BV | 256 | Wait | Custom screen element / key | Write | ||
| BV | 258 | Heat Adjust | Custom screen element / key | Write | ||
| BV | 260 | Follow | Custom screen element / key | Write | ||
| BV | 262 | URHC Adj Arrows | Custom screen element / key | Write | ||
| BV | 264 | Am | Custom screen element / key | Write | ||
| BV | 266 | LLHC Adj Arrows | Custom screen element / key | Write | ||
| BV | 269 | Hold Until | Custom screen element / key | Write | ||
| BV | 271 | Outside | Custom screen element / key | Write | ||
| BV | 273 | HUMIDIFIER | Custom screen element / key | Write | ||
| BV | 275 | Minutes | Custom screen element / key | Write | ||
| BV | 277 | LLRC % | Custom screen element / key | Write | ||
| BV | 278 | LLRC minus | Custom screen element / key | Write | ||
| BV | 280 | Vent | Custom screen element / key | Write | ||
| BV | 282 | Tue key | Custom screen element / key | Write | ||
| BV | 284 | Thu key | Custom screen element / key | Write | ||
| BV | 286 | Sat key | Custom screen element / key | Write | ||
| BV | 288 | URHC up key | Custom screen element / key | Write | ||
| BV | 290 | LRHC up key | Custom screen element / key | Write | ||
| BV | 292 | LLHC up key | Custom screen element / key | Write | ||
| BV | 294 | RESET key | Custom screen element / key | Write | ||
| BV | 297 | FAN key | Custom screen element / key | Write | ||
| BV | 300 | AOn Current Mode | AO 0: current mode detected | Read | ||
| BV | 301 | AOn Current Mode | AO 1: current mode detected | Read | ||
| MV | 0 | Time Mode | Device's time handling capability: Normal clock operation will | Read | 1=Time Of Day Unknown Mode, 2=Time Of Day Available Mode, 3=Date/Time Available Mode | |
| MV | 2 | Keypad Lock | Keypad access level | Read | 1=full access, 2=setpoints only, 3=locked | |
| MV | 4 | SP Increment | Amount of change in setpoint per arrow press | Read | ||
| MV | 6 | User SYSTEM selection | Display / screen setting | Read | ||
| MV | 8 | Fan OFF text | Display / screen setting | Read | ||
| MV | 10 | Fan stage 2 text | Display / screen setting | Read | ||
| MV | 12 | Schedule Format | This point is a human-friendly version of AV-129, ISU parameter 540 (see... | Read | 1=2 commands per day, 2=4 commands per day | |
| MV | 20 | ULHC mode | Display / screen setting | Read | ||
| MV | 22 | LLHC mode | Display / screen setting | Read | ||
| BV | 279 | Cool Adj | Custom screen element / key | Write | ||
| BV | 281 | Mon key | Custom screen element / key | Write | ||
| BV | 283 | Wed key | Custom screen element / key | Write | ||
| BV | 285 | Fri key | Custom screen element / key | Write | ||
| BV | 287 | Sun key | Custom screen element / key | Write | ||
| BV | 289 | URHC dn key | Custom screen element / key | Write | ||
| BV | 291 | LRHC dn key | Custom screen element / key | Write | ||
| BV | 293 | LLHC dn key | Custom screen element / key | Write | ||
| BV | 295 | CANCEL PERIOD key | Custom screen element / key | Write | ||
| BV | 298 | SYSTEM key | Custom screen element / key | Write | ||
| BV | 400 | AIn Pullup | AI 0: pull-up enable | Write | ||
| BV | 401 | AIn Pullup | AI 1: pull-up enable | Write | ||
| BV | 402 | AIn Pullup | AI 2: pull-up enable | Write | ||
| MV | 1 | Schedule Model | Device's schedule model | Read | 1=Setpoint, 2=Occupancy | |
| MV | 3 | DLS Mode | Mode of Daylight Saving operation | Read | 1=OFF, 2=Auto (pre-2007), 3=Auto (2007 and later) | |
| MV | 5 | Schedule Increment | Amount of change in schedule times per arrow press | Read | ||
| MV | 7 | Fan status | Display / screen setting | Read | ||
| MV | 9 | Fan stage 1 text | Display / screen setting | Read | ||
| MV | 11 | Fan stage 3 text | Display / screen setting | Read | ||
| MV | 13 | SP Override Mode | In setpoint mode: setpoint override state | Read | 1=scheduled, 2=temporary, 3=permanent, 4=vacation | |
| MV | 21 | URHC mode | Display / screen setting | Read | ||
| MV | 23 | LRHC mode | Display / screen setting | Read |
No points match these filters.
Object ID lookup: Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat point IDs by name
AV90Setpoint (SP)AV92Setpoint Low LimitAV94Heating SP OffsetAV96Unoccupied Heating SPAV98After Hours TimerAV100Current Heating SPAV102Displayed Room HumidityAV104Sensed Room TemperatureAV106Demand OffsetAV108SP Mode Cooling SPAV110SP Mode Setpoint ModelAV113SP Override Mode AVAV115Filter Runtime LimitAV117UV Lamp Runtime LimitAV119Humidifier Pad Runtime LimitAV121Dehumidifier SP MaxAV123Set system to Occupancy modeAV125Humidity Pad Change ReminderAV127Daylight savingsAV129Weekday periods ISU valueAV131Vacation days remainingAV133ISU mode security PINAV135Humidifier SP MaxAV137Fan Setting Display FormatAV139Sensed Humidity OffsetAV141Sensed Outside Air Humidity OffsetAV211ULHC left characterAV213URHC numberAV215URHC 1 charAV217URHC maximumAV219LLHC numberAV221LLHC 1 charAV223LLHC maximumAV91Setpoint High LimitAV93Cooling SP OffsetAV95Unoccupied Cooling SPAV97After Hours Timer LimitAV99Current Cooling SPAV101Displayed Room TemperatureAV103Displayed Outside Air TemperatureAV105Sensed Room HumidityAV107Displayed Outside HumidityAV109SP Mode Heating SPAV111SYSTEM Setpoint ModelAV114Filter RuntimeAV116UV Lamp RuntimeAV118Humidifier Pad RuntimeAV120Dehumidifier SetpointAV122Dehumidifier SP MinAV124Filter Change ReminderAV126UV Lamp Change ReminderAV128Keypad lockAV130Hold until timeAV132Field service mode security PINAV134Humidifier SetpointAV136Humidifier SP MinAV138Sensed Temperature OffsetAV140Sensed Outside Air Temperature OffsetAV210UHLH numberAV212ULHC right characterAV214URHC 10 charAV216URHC minimumAV218URHC deltaAV220LLHC 10 charAV222LLHC minimumAV224LLHC deltaAV225LLHC 1000 charAV227LRHC numberAV229LRHC 1 charAV231LRHC maximumBV64Time Schedule OutputBV66After Hours Timer StatusBV68Field service LockoutBV71English (OFF) / Metric (ON)BV73Fan stage 2BV77Heating ICONBV79Backlight ONBV81Select Hotel ModeBV8324Hr Time FormatBV100Enable OSA TempBV102Enable System ControlBV104Enable DOWBV106Show WaitBV108Show RecoveryBV110Show DEHUMIDIFIERBV112Force CHANGE UV LAMPBV114Disable SCHED keyBV116Disable CLOCK keyBV118Allow System HEATBV120Allow System AUTOBV122System HEAT ModeBV124System AUTO ModeBV130Disable Vacation HOLD keyBV133Enable internal scheduleBV135Filter ONBV137UV Lamp ONBV139Humidifier Pad ONBV141Disable schedule editBV143Enable humidifier setpoint on detail screensAV226LLHC 100 charAV228LRHC 10 charAV230LRHC minimumAV232LRHC deltaBV65User ON/OFF in Occupied ModeBV67Occupied/Unoccupied StatusBV69Swap English/MetricBV72Fan stage 1BV74Fan stage 3BV78Cooling ICONBV80Enable Fan Speed ControlBV82Enable Time DisplayBV84Enable Space HumidityBV101Enable OSA HumidityBV103Hide Fan and SystemBV105Show Unocc SetpointsBV107Show Aux heat onBV109Show FROSTBV111Force CHANGE FILTERBV113Force CHANGE HUMIDIFIER PADBV115Disable Permanent HOLD keyBV117Allow System OFFBV119Allow System COOLBV121Allow System EM HEATBV123System COOL ModeBV125System EM HEAT ModeBV131Hotel Standby ModeBV134Filter EnableBV136UV Lamp EnableBV138Humidifier Pad EnableBV140Enable dehumidifier setpoint on detail screenBV142Master OFFBV144Enable AUTO/OFF user selection on humidifier detail screenBV145User humidifier AUTO/OFF selectionBV147User dehumidifier AUTO/OFF selectionBV210Custom 1 EnableBV212ULHC enableBV214ULHC lead zeroBV216URHC decimalBV218URHC editBV220LLHC lead zeroBV222LRHC enableBV224LRHC lead zeroBV226LRHC leading 1BV228Mon textBV230Wed textBV232Fri textBV234Sun textBV236Tue checkBV238Thu checkBV240Sat checkBV242Ok to pickBV244ChangeBV246UV LampBV250InsideBV253Set toBV255Heat OnBV257Cool OnBV259FrostBV261RecoveryBV263PmBV265DaysBV268PermanentBV270Cancel PeriodBV272DEBV274LRHC HumidityBV276LRHC Adj ArrowsBV146Enable AUTO/OFF user selection on dehumidifier detail screenBV200AIn Current ModeBV201AIn Current ModeBV202AIn Current ModeBV211ResetBV213ULHC decimalBV215URHC enableBV217URHC lead zeroBV219LLHC enableBV221LLHC editBV223LRHC decimalBV225LRHC editBV227Day boxesBV229Tue textBV231Thu textBV233Sat textBV235Mon checkBV237Wed checkBV239Fri checkBV241Sun checkBV243Screen lockedBV245FilterBV247Hum PadBV251ULHC % HumidityBV254AuxBV256WaitBV258Heat AdjustBV260FollowBV262URHC Adj ArrowsBV264AmBV266LLHC Adj ArrowsBV269Hold UntilBV271OutsideBV273HUMIDIFIERBV275MinutesBV277LLRC %BV278LLRC minusBV280VentBV282Tue keyBV284Thu keyBV286Sat keyBV288URHC up keyBV290LRHC up keyBV292LLHC up keyBV294RESET keyBV297FAN keyBV300AOn Current ModeBV301AOn Current ModeMV0Time ModeMV2Keypad LockMV4SP IncrementMV6User SYSTEM selectionMV8Fan OFF textMV10Fan stage 2 textMV12Schedule FormatMV20ULHC modeMV22LLHC modeBV279Cool AdjBV281Mon keyBV283Wed keyBV285Fri keyBV287Sun keyBV289URHC dn keyBV291LRHC dn keyBV293LLHC dn keyBV295CANCEL PERIOD keyBV298SYSTEM keyBV400AIn PullupBV401AIn PullupBV402AIn PullupMV1Schedule ModelMV3DLS ModeMV5Schedule IncrementMV7Fan statusMV9Fan stage 1 textMV11Fan stage 3 textMV13SP Override ModeMV21URHC modeMV23LRHC mode
Integration notes
- The appendix gives each object a label in an 'Object Name' column, but its property tables say the Object_Name property reads 'AV-nnn' / 'BV-nnn' / 'MV-nnn' for most objects. The labels are used as names here; a scan may show the AV-nnn form.
- Physical I/O objects (AI 0-2, AO 0-7, BI 0-2, BO 0-5) and the general-use AV 0-89 / BV 0-63 depend on the loaded application (DDC file); they are not listed here except where the guide names them.
- BV 40 (general-use range) is the occupancy command and supports a priority array.
- Access comes from the appendix where it has an access column; otherwise it is inferred (displayed/sensed/current/status points and multistates read-only, others writable).
- Taken from Appendix B (ordered list of control points) with access and descriptions from Appendix A of the guide.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TB3026B / TB3026B-W BACnet FF fixed-function thermostat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat
How many BACnet points does the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat have?
This list has 245 BACnet objects: 74 analog values, 153 binary values, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet points are writable?
208 of the 245 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat BACnet documentation?
Honeywell does not publish it on its own website. This list comes from BACnet FF Installation and Operations Guide (31-00098-01), a copy hosted by Galco at https://docs.galco.com/techdoc/hnwl/31-00098_opm.pdf. Ask Honeywell or its representative for the current revision.
What are the minimum BACnet points to integrate the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat?
Start with AV 90 Setpoint (SP) (Occupied space setpoint); AV 95 Unoccupied Cooling SP (Unoccupied cooling setpoint); AV 96 Unoccupied Heating SP (Unoccupied heating setpoint); BV 133 Enable internal schedule (Internal schedule on/off); AV 104 Sensed Room Temperature (Room temperature (built-in sensor)); BV 67 Occupied/Unoccupied Status (Occupied / unoccupied status); AV 99 Current Cooling SP (Active cooling setpoint); AV 100 Current Heating SP (Active heating setpoint).
How do I enable BMS control of the Honeywell TB3026B / TB3026B-W BACnet FF fixed-function thermostat?
Occupancy comes from BV 40 (priority array) or the internal schedule (BV 133).
How do I check these points on the real TB3026B / TB3026B-W BACnet FF fixed-function thermostat?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Honeywell BACnet points lists
- Thermostat (fan coil, conventional and heat pump)
Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)
Honeywell TC300 and Wi-Fi TC320 commercial touchscreen thermostats for fan coils, conventional units and heat pumps.
Also known as: TC300, TC320, TC300B-G, TC300C-G, TC320B-G, TC320C-G, T300 Series - Thermostat (rooftop, heat pump and fan coil)
Honeywell TC500A Commercial Thermostat
Honeywell TC500A commercial touchscreen thermostat for conventional rooftop units, heat pumps and fan coils, with economizer, DCV and Sylk bus sensors.
Also known as: TC500A, TC500A-N, TC500 - Room air quality sensor
Honeywell TR50 indoor air quality sensor (BACnet MS/TP)
Honeywell TR50 wall-mount indoor air quality sensors (temperature, humidity, CO2, PM2.5 / PM1.0 / PM10, TVOC) on BACnet MS/TP.
Also known as: TR50, TR50-5D, TR50-5N, TR50-3D, TR50-3N, TR50-5D-U, TR50-3D-U, Honeywell TR50 IAQ sensor
Source: BACnet FF Installation and Operations Guide · 31-00098-01. Object names, instances and units are reproduced as published; descriptions are our own.