Thermostat (rooftop, heat pump and fan coil) · BACnet points list
Honeywell TC500A Commercial Thermostat BACnet points list
Updated 7 November 2026Unofficial source
The TC500A is a commercial touchscreen thermostat that talks BACnet MS/TP on its RS-485 terminals or BACnet IP over Wi-Fi (one at a time). The guide lists objects for terminal I/O, application configuration (conventional, heat pump, fan coil, economizer), setpoints, network inputs, network outputs, alarms, display points and schedules. Network inputs let a BMS share outdoor air, space values, occupancy and emergency overrides.
This page lists 644 BACnet objects for the Honeywell TC500A Commercial Thermostat — 466 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Honeywell’s documentation hosted by Cochrane Supply, not by Honeywell itself, so treat it as unofficial.
- Manufacturer
- Honeywell
- Model
- TC500A Commercial Thermostat
- Equipment
- Thermostat (rooftop, heat pump and fan coil)
- Equipment type
- Heat pumps
- BACnet objects
- 644 (466 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- TC500A, TC500A-N, TC500
- Source document
- TC500A BACnet Integration Guide · 31-00478-05 · rev. Rev. 02-23 (unofficial copy, hosted by Cochrane Supply)
Reference only, provided as-is: verify against Honeywell’s current documentation and the live device before use. Not official Honeywell information. Terms of use.
BMS integration notes: Honeywell TC500A Commercial Thermostat
Drive mode with MV 3 ni_ApplicationMode and occupancy with BV 158 ni_OccupancySensor, and write the occupied setpoints AV 7 / AV 4. Read effective setpoints AO 3 / AO 4, space temperature AO 18 and fan status BO 19. Outdoor and space values can be shared in through the ni_ inputs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 3 | ni_ApplicationMode | System mode from the network | Write |
| BV 158 | ni_OccupancySensor | Network occupancy: 1 = occupied, 0 = unoccupied | Write |
| AV 7 | Cfg_Setpoints_OccHeatSp | Occupied heating setpoint | Write |
| AV 4 | Cfg_Setpoints_OccCoolSp | Occupied cooling setpoint | Write |
| MV 583 | Cfg_FanCoilManualSpeedSel | Fan coil fan speed: auto, low, medium, high, off | Write |
| AO 18 | no_SpaceTemp | Space temperature in use | Read |
| AO 3 | no_EffHeatSp | Effective heating setpoint | Read |
| AO 4 | no_EffCoolSp | Effective cooling setpoint | Read |
| BO 19 | no_FanStart | Fan start output state | Read |
| BO 102 | no_GenericAlarm | Any alarm active | Read |
Enable & remote start
The BMS steers the thermostat through ni_ network inputs: application mode (MV 3, not kept over a power cycle), occupancy (BV 158), bypass (BV 1), shutdown (BV 4) and smoke (BV 5). The schedule-state, occupancy-state, manual-override and emergency-override multistate inputs (MV 1, 4, 5, 6) clash with network outputs in the guide and are not listed.
Heartbeat & communication loss
Each shared network input has a fail-detect enable and delay (0-3600 s), for example occupancy BV 159 / AV 263, outdoor temperature BV 163 / AV 271, space temperature BV 168 / AV 282. When a bound input stops updating it falls back after the delay.
Sensors & values from the BMS
Network inputs: ni_SpaceTemp AV 104, ni_SpaceRH AV 80, ni_SpaceCO2 AV 81, ni_OutdoorTemp AV 89, ni_OutdoorHum AV 194, outdoor and return enthalpy/dew point AV 339-342. Sylk sensor values can be overridden through AV 238-251.
Network setup
- BACnet MS/TP or BACnet IP over Wi-Fi, not both; switching between them restarts the thermostat.
- MS/TP: Device ID is set on the thermostat; auto MAC addressing is on by default. The baud rate is auto-detected in the first 4 minutes, otherwise 76,800.
- ni_DeviceLock (AV 195) can lock changes to the GUI or to the network.
Watch out for
- Several objects share a type and instance in the guide (see notes); check on the device before mapping them.
- ni_ApplicationMode is not kept after a power cycle; rewrite it after a restart.
Honeywell TC500A Commercial Thermostat BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 8 | ni_UI1 | Universal Input shared to network. | Read | ||
| AI | 9 | ni_UI2 | Universal Input shared to network. | Read | ||
| AI | 10 | ni_UIO1 | Universal Input shared to network. | Read | ||
| AO | 64 | no_UIO1 | Universal Output shared to network. | Write | ||
| AI | 11 | ni_UIO2 | Universal Input shared to network. | Read | ||
| AO | 63 | no_UIO2 | Universal Output shared to network. | Write | ||
| BO | 74 | no_DO1 | Digital Output shared to network. | Write | ||
| BO | 75 | no_DO2 | Digital Output shared to network. | Write | ||
| BO | 76 | no_DO3 | Digital Output shared to network. | Write | ||
| BO | 77 | no_DO4 | Digital Output shared to network. | Write | ||
| BO | 78 | no_DO5 | Digital Output shared to network. | Write | ||
| BO | 79 | no_DO6 | Digital Output shared to network. | Write | ||
| BO | 80 | no_DO7 | Digital Output shared to network. | Write | ||
| BO | 81 | no_DO8 | Digital Output shared to network. | Write | ||
| MV | 24 | Cfg_UI1 | Function assigned to terminal UI1 | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=WtrFlwSts, 11=Space Temp Sensor, 12=FiltPres, 14=FanCurSens | |
| AV | 293 | Cfg_UI1_Ext | Function code for terminal UI1, extended option list | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=WtrFlwSts, 11=Space Temp Sensor, 17=PckEconFault, 18=WindowOpen, 19=Return Air Sensor, 20=Leak Detect/Drain Pan Sensor | |
| MV | 25 | Cfg_UI2 | Function assigned to terminal UI2 | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=WtrFlwSts, 11=Space Temp Sensor, 12=FiltPres, 14=FanCurSens | |
| AV | 294 | Cfg_UI2_Ext | Function code for terminal UI2, extended option list | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=WtrFlwSts, 11=Space Temp Sensor, 17=PckEconFault, 18=WindowOpen, 19=Return Air Sensor, 20=Leak Detect/Drain Pan Sensor | |
| MV | 26 | Cfg_UIO1 | Function assigned to terminal UIO1 | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=Fan Speed Control, 11=WtrFlwSts, 12=Space Temp Sensor | |
| AV | 295 | Cfg_UIO1_Ext | Function code for terminal UIO1, extended option list | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=Fan Speed Control, 11=WtrFlwSts, 12=Space Temp Sensor, 17=PckEconFault, 18=WindowOpen, 19=Return Air Sensor, 20=CO2Output, 21=Purge Output, 22=Cooling Control, 23=Leak Detect/Drain Pan Sensor | |
| MV | 27 | Cfg_UIO2 | Function assigned to terminal UIO2 | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=Heating Control, 11=WtrFlwSts, 12=Space Temp Sensor | |
| AV | 296 | Cfg_UIO2_Ext | Function code for terminal UIO2, extended option list | Write | 1=None, 2=Occupancy Sensor, 3=Dirty Filter, 4=Air Flow Status, 5=Shutdown, 6=Mixed Air Sensor, 7=Outside Air Sensor, 8=Discharge Air Sensor, 9=CO2 Sensor, 10=Heating Control, 11=WtrFlwSts, 12=Space Temp Sensor, 17=PckEconFault, 18=WindowOpen, 19=Return Air Sensor, 20=CO2Output, 21=Purge Output, 22=Cooling Control, 23=Leak Detect/Drain Pan Sensor | |
| MV | 28 | Cfg_DO1 | Function assigned to terminal DO1 | Write | 1=None, 2=Fan Command, 3=RTU/FCU Fan High Speed Command | |
| MV | 29 | Cfg_DO2 | Function assigned to terminal DO2 | Write | 2=Heating Stage1 Command, 3=FCU 2Pipe Single Heating On/Off Valve, 4=FCU 4Pipe Dual Heating On/Off Valve, 5=FCU Heating Floating Open Command | |
| MV | 30 | Cfg_DO3 | Function assigned to terminal DO3 | Write | 1=None, 2=Heating Stage2 Command, 3=Heat Pump Reversing Valve Command, 4=Fan Low Speed Command, 5=Occupancy Status, 6=Dehumidification Command, 7=Humidification Command, 8=FCU Heating Floating Close Command | |
| MV | 31 | Cfg_DO4 | Function assigned to terminal DO4 | Write | 1=None, 2=Heating Stage3 Command, 3=Heat Pump Reversing Valve Command, 4=Fan Low Speed Command, 5=Occupancy Status, 6=Dehumidification Command, 7=Humidification Command, 8=Purge Command, 9=Exhaust Fan1 Command, 10=Exhaust Fan2 Command, 11=FCU Fan Medium Speed Command, 12=Cooling Stage4 Command | |
| MV | 32 | Cfg_DO5 | Function assigned to terminal DO5 | Write | 1=None, 2=Cooling / Compressor Stage1 Command, 3=FCU 2Pipe Single Cooling On/Off Valve, 4=FCU 4Pipe Dual Cooling On/Off Valve, 5=FCU Cooling Floating Open Command | |
| MV | 33 | Cfg_DO6 | Function assigned to terminal DO6 | Write | 1=None, 2=Cooling / Compressor Stage2 Command, 3=Heat Pump Reversing Valve Command, 4=Fan Low Speed Command, 5=Occupancy Status, 6=Dehumidification Command, 7=Humidification Command, 8=FCU Cooling Floating Close Command | |
| MV | 34 | Cfg_DO7 | Function assigned to terminal DO7 | Write | 1=None, 2=Cooling / Compressor Stage3 Command, 3=Econ Min Damper Command, 4=Fan Low Speed Command, 5=Occupancy Status, 6=Dehumidification Command, 7=Humidification Command, 8=Purge Command, 9=Exhaust Fan1 Command, 10=Exhaust Fan2 Command, 11=FCU Fan Medium Speed Command | |
| MV | 35 | Cfg_DO8 | Function assigned to terminal DO8 | Write | 1=None, 2=Econ Min Damper Command, 3=Fan Low Speed Command, 4=Occupancy Status, 5=Dehumidification Command, 6=Humidification Command, 7=Purge Command, 8=Spare, 9=Exhaust Fan1 Command, 10=Exhaust Fan2 Command, 11=FCU Fan Medium Speed Command, 12=Cooling Stage4 Command | |
| BV | 31 | Cfg_OccSensChar | Occupancy sensor input characteristics selection | Write | 0=Direct, 1=Reverse | |
| BV | 32 | Cfg_DirtyFilterChar | Dirty filter input characteristics selection | Write | 0=Direct, 1=Reverse | |
| BV | 33 | Cfg_AirFlwStsChar | Airflow status input characteristics selection | Write | 0=Direct, 1=Reverse | |
| BV | 34 | Cfg_ShutdownChar | Shutdown input characteristics selection | Write | 0=Direct, 1=Reverse | |
| MV | 501 | Cfg_MASensChar1 | Temperature Sensor characteristics selection | Write | 1=NTC10K type II, 2=NTC10K type III, 3=NTC20K | |
| MV | 502 | Cfg_OASensChar1 | Temperature Sensor characteristics selection | Write | 1=NTC10K type II, 2=NTC10K type III, 3=NTC20K | |
| MV | 503 | Cfg_DASensChar1 | Temperature Sensor characteristics selection | Write | 1=NTC10K type II, 2=NTC10K type III, 3=NTC20K | |
| BV | 180 | Cfg_RASensChar | Return air Temperature Sensor characteristics selection | Write | 0=NTC 20 K, 1=NTC 10 K Type II | |
| MV | 504 | Cfg_RASensChar1 | Temperature Sensor characteristics selection | Write | 1=NTC10K type II, 2=NTC10K type III, 3=NTC20K | |
| MV | 372 | CFg_SpcSensChar | Space Temperature Sensor characteristics selection | Write | 1=NTC 10 K Type II, 2=NTC 10 K Type III, 3=NTC 20 K | |
| BV | 155 | Cfg_FiltPresChar | Filter Pressure Characteristics selection | Write | 0=0, 0=-5 InWC 1 | |
| AV | 220 | Cfg_CompCurSensMaxAmps | Comp Current Sensor Maximum Range | Write | ||
| AV | 221 | Cfg_FanCurSensMaxAmps | Fan Current Sensor Maximum Range | Write | ||
| BV | 175 | Cfg_WindowOpenChar | Window open characteristic | Write | 0=Direct, 1=Reverse | |
| BV | 383 | Cfg_WaterFlwStsChar | Proof of Water Flow Sensor characteristic | Write | 0=Direct, 1=Reverse | |
| AV | 223 | no_SylkAddr2Temp | Temperature from the Sylk TR40-family sensor at address 2 | Read | ||
| AV | 224 | no_SylkAddr2Hum | Read | |||
| AV | 225 | no_SylkAddr2CO2 | Read | |||
| AV | 226 | no_SylkAddr3Temp | TR40: Temperature | Read | ||
| AV | 227 | no_SylkAddr4Temp | TR40: Temperature | Read | ||
| AV | 228 | no_SylkAddr5Temp | TR40: Temperature | Read | ||
| AV | 229 | no_SylkAddr6Temp | TR120: Temperature and Humidity | Read | ||
| AV | 230 | no_SylkAddr6Hum | Read | |||
| AV | 231 | no_SylkAddr8Temp | C7400S Outdoor Air Sensor, Temperature and Humidity | Read | ||
| AV | 232 | no_SylkAddr8Hum | Read | |||
| AV | 233 | no_SylkAddr9Temp | C7400S Return Air Sensor, Temperature and Humidity | Read | ||
| AV | 234 | no_SylkAddr9Hum | Read | |||
| AV | 235 | no_SylkAddr10Temp | C7400S Discharge Air Sensor, Temperature and Humidity | Read | ||
| AV | 236 | no_SylkAddr10Hum | Read | |||
| MV | 92 | no_Sylk11Status | Sylk actuator fault code (1 = no error; voltage or stall faults) | Read | ||
| AV | 237 | no_SylkAddr11Temp | C7400S Mixed Air Sensor, Temperature | Read | ||
| AV | 773 | no_SylkAddr12Hum | C7400S Mixed Air Sensor, Humidity | Read | ||
| AI | 16 | InternalTempSens | Temperature from the built-in sensor; writing it affects local control | Read | ||
| AI | 17 | InternalHumSens | Humidity from the built-in sensor; writing it affects local control | Read | ||
| MV | 89 | Cfg_FanMode | Fan Mode of operation config by user & supervisor. | Write | 1=Continuous, 2=Auto, 3=FanCirculate | |
| AV | 39 | Cfg_FanRunOnCoolDelay | Fan run on time after all cooling stages and economizer stage turns off. | Write | ||
| AV | 40 | Cfg_FanRunOnHeatDelay | Fan run on time after all heating stages turns off. | Write | ||
| BV | 10 | Cfg_FanOnHeat | Fan in heat mode: external duct thermostat or thermostat output | Write | 0=Disable, 1=Enable | |
| AV | 253 | Cfg_FanCirculate_FanOnTimePercent | Fan run time per hour in circulate mode, percent | % | Write | |
| MV | 15 | Cfg_FanSpeed_CmprCoolSingle | Fan speed selection for Compressor/ Cooling single stage mode. | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| MV | 16 | Cfg_FanSpeed_CmprCoolMulti | Fan speed selection for Cooling/ Compressor Multiple Stages. | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| MV | 17 | Cfg_FanSpeed_HeatSingle | Fan speed selection for Heating/Aux Heat Single Stage. | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| MV | 90 | Cfg_FanSpeed_PurgeMode | Fan speed selection for Purge mode. | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| AV | 83 | Cfg_FanMinSpeed_ModHeat | Not used; kept for backward compatibility | % | Write | |
| AV | 84 | Cfg_FanMaxSpeed_ModHeat | Not used; kept for backward compatibility | % | Write | |
| AV | 64 | Cfg_FanSpeed_Speed1 | Fan speed 1 | % | Write | |
| AV | 65 | Cfg_FanSpeed_Speed2 | Fan speed 2 | % | Write | |
| AV | 66 | Cfg_FanSpeed_Speed3 | Fan speed 3 | % | Write | |
| AV | 67 | Cfg_FanSpeed_Speed4 | Fan speed 4 | % | Write | |
| AV | 68 | Cfg_FanSpeed_Speed5 | Fan speed 5 | % | Write | |
| AV | 69 | Cfg_FanSpeed_Speed6 | Fan speed 6 | % | Write | |
| MV | 367 | Cfg_FanSpeed_EconomizerMode | Fan speed selection for Econ mode. | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| MV | 370 | Cfg_MultipleFanSpeed_ModHeat | Fan speed used for modulating heat | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| MV | 371 | Cfg_MultipleFanSpeed_ModCool | Fan speed used for modulating cool | Write | 1=Speed1, 2=Speed2, 3=Speed3, 4=Speed4, 5=Speed5, 6=Speed6 | |
| AV | 1468 | Cfg_VarSpeedFan_CoolMinSpeed | Minimum Fan speed Setpoint for New Variable Speed Fan during Conventional Cooling Mode. | % | Write | |
| AV | 1469 | Cfg_VarSpeedFan_CoolMaxSpeed | Minimum Fan speed Setpoint for New Variable Speed Fan during Conventional Cooling Mode. | % | Write | |
| AV | 1473 | Cfg_VarSpeedFan_HeatMinSpeed | Minimum Fan speed Setpoint for New Variable Speed Fan during Conventional Heating Mode. | % | Write | |
| AV | 1474 | Cfg_VarSpeedFan_HeatMaxSpeed | Maximum Fan speed Setpoint for New Variable Speed Fan during Conventional Cooling Mode. | % | Write | |
| AV | 1472 | Cfg_VarSpeedFan_PurgeSpeed | Purget speed Setpoint for New Variable Speed Fan | % | Write | |
| AV | 1470 | Cfg_VarSpeedFan_VentSpeed | Vent speed Setpoint for New Variable Speed Fan | % | Write | |
| MV | 373 | Cfg_VarSpeedFanType | Variable Fan Speed Type characteristics selection | Write | 0=1, 2=-10V 2 | |
| AV | 1483 | Cfg_Econ_EXH1Sp | Exhaust Fan1 Damper Pos Setpoint for Single Fan Speed | % | Write | |
| AV | 1484 | Cfg_Econ_EXH2Sp | Exhaust Fan2 Damper Pos Setpoint for Single Fan Speed | % | Write | |
| AV | 1485 | Cfg_Econ_EXH1SpL | Exhaust Fan1 Damper Pos Setpoint for Multiple Fan Speed Low and Two Speed Low | % | Write | |
| AV | 1486 | Cfg_Econ_EXH1SpH | Exhaust Fan1 Damper Pos Setpoint for Multiple Fan Speed High and Two Speed High | % | Write | |
| AV | 1487 | Cfg_Econ_EXH2SpM | Exhaust Fan1 Damper Pos Setpoint for Variable Fan Speed Medium | % | Write | |
| AV | 1488 | Cfg_Econ_EXH2SpL | Exhaust Fan2 Damper Pos Setpoint for Multiple Fan Speed Low and Two Speed Low | % | Write | |
| AV | 1489 | Cfg_Econ_EXH2SpH | Exhaust Fan2 Damper Pos Setpoint for Multiple Fan Speed High and Two Speed High | % | Write | |
| AV | 1490 | Cfg_Econ_EXH2SpM | Exhaust Fan2 Damper Pos Setpoint for Multiple Fan Speed Medium | % | Write | |
| MV | 575 | Cfg_FanCoilType | Fan coil type: 2-pipe single coil or 4-pipe dual coil | Write | 2=1, 4=Pipe 2, 4=Pipe Dual 3 | |
| MV | 576 | Cfg_FanCoilHtgType | Fan Coil (FCU) Heating Type selection | Write | 1=None, 2=OnOff, 3=Mod, 4=Floating | |
| MV | 577 | Cfg_FanCoilClgType | Fan Coil (FCU) Cooling Type selection | Write | 1=None, 2=OnOff, 3=Mod, 4=Floating | |
| MV | 578 | Cfg_FanCoilHtgDriveType | Fan Coil (FCU) Heating Valve Drive Type for Floating Actuator 1=DirectCW 2=ReverseCCW | Write | 1=Direct, 2=Reverse | |
| MV | 579 | Cfg_FanCoilClgDriveType | Fan Coil (FCU) Cooling Valve Drive Type for Floating Actuator 1=DirectCW 2=ReverseCCW | Write | 1=Direct, 2=Reverse | |
| AV | 1721 | Cfg_FanCoilHtgDriveTime | Fan Coil (FCU) Heating Valve Drive Time for Floating Actuator | Write | ||
| AV | 1722 | Cfg_FanCoilClgDriveTime | Fan Coil (FCU) Cooling Valve Drive Time for Floating Actuator | Write | ||
| MV | 580 | Cfg_FanCoilTwoPipeSingleCoil | Fan Coil (FCU) Two Pipe Single Valve Type selection | Write | 1=Heating Only, 2=Cooling Only | |
| AV | 1723 | Cfg_FanCoilSupTempHtgSp | Fan Coil (FCU) SupplyTemp heating Sp | °F | Write | |
| AV | 1731 | Cfg_FanCoilSupTempHtgOffsetSp | Fan Coil (FCU) SupplyTemp heating Offset Sp | °F | Write | |
| AV | 1724 | Cfg_FanCoilSupTempClgSp | Fan Coil (FCU) SupplyTemp Cooling Sp | °F | Write | |
| AV | 1732 | Cfg_FanCoilSupTempClgOffsetSp | Fan Coil (FCU) SupplyTemp Cooling Offset Sp | °F | Write | |
| MV | 581 | Cfg_FanCoilTwoSpeedType | Fan Coil (FCU) Two Speed Type Selection (Low/High) | Write | 1=Multiple outputs at a time, 2=Single output at a time | |
| MV | 582 | Cfg_FanCoilThreeSpeedtype | Fan Coil (FCU) Three Speed Type Selection (Low/Med/ High) | Write | 1=Serial, 2=Parallel | |
| MVmin | 583 | Cfg_FanCoilManualSpeedSel | Fan Coil (FCU) Manual Speed Type Selection | Write | 1=Auto, 2=Low, 3=Medium, 4=High, 5=Off | |
| BV | 454 | Cfg_FanCoilDATSpEnSwitch | Fan Coil (FCU) Discharge Air Setpoint Control Enable Switch | Write | 0=Off, 1=On | |
| BV | 462 | Cfg_FanCoilClgFloatingSyncEn | Nightly resync of the floating cooling valve | Write | 0=SyncOff, 1=SyncOn | |
| BV | 453 | Cfg_FanCoilHtgFloatingSyncEn | Nightly resync of the floating heating valve | Write | 0=SyncOff, 1=SyncOn | |
| AV | 1733 | Cfg_FanCoilDATCtr_CoolTr | Fan Coil (FCU) SupplyTemp Cooling PID Control Proportional Band Sp | °F | Write | |
| AV | 1734 | Cfg_FanCoilDATCtr_CoolIt | Fan Coil (FCU) SupplyTemp Cooling PID Control Integral Time Sp | Write | ||
| AV | 1735 | Cfg_FanCoilDATCtr_CoolDr | Fan Coil (FCU) SupplyTemp Cooling PID Control Derivative Time Sp | Write | ||
| AV | 1736 | Cfg_FanCoilDATCtr_HeatTr | Fan Coil (FCU) SupplyTemp Heating PID Control Proportional Band Sp | °F | Write | |
| AV | 1737 | Cfg_FanCoilDATCtr_HeatIt | Fan Coil (FCU) SupplyTemp Heating PID Control Integral Time Sp | Write | ||
| AV | 1738 | Cfg_FanCoilDATCtr_HeatDr | Fan Coil (FCU) SupplyTemp Heating PID Control Derivative Time Sp | Write | ||
| MV | 585 | Cfg_FanCoilTwoSpeedVentMode | Fan Coil (FCU) Two Speed Type Vent Mode Selection | Write | 1=Low, 2=High | |
| MV | 586 | Cfg_FanCoilThreeSpeedVentMode | Fan Coil (FCU) Three Speed Type Vent Mode Selection | Write | 1=Low, 2=Medium, 3=High | |
| BV | 455 | Cfg_FanCoilDrainPanSrChar | FCU CHWV Leak Detector/ Drain Pan Sensor characteristics | Write | 0=DIRECT, 1=REVERSE | |
| BV | 458 | Cfg_FanCoilOnOffHtgVlvChar | FCU 2Pipe Single/4Pipe Dual Heating Valve characteristics | Write | 0=DIRECT, 1=REVERSE | |
| BV | 459 | Cfg_FanCoilOnOffClgVlvChar | FCU 2Pipe Single/4Pipe Dual Cooling Valve characteristics | Write | 0=DIRECT, 1=REVERSE | |
| MV | 366 | Cfg_Equip_CoolType | Conventional Cool equipment type | Write | 1=1, 2=Stage 2, 3=Stages 3 | |
| AV | 41 | Cfg_Cool_Tr | Cooling Throttling Range | Δ°F | Write | |
| AV | 42 | Cfg_Cool_It | Cooling Integral Time 0 = disable (i.e. proportional only) | Write | ||
| AV | 43 | Cfg_Cool_Dt | Cooling Derivative Time | Write | ||
| AV | 44 | Cfg_Cool_CPH | Cooling System Response | Write | ||
| AV | 45 | Cfg_Cool_MinOnTime | Cooling Stage Minimum on Time | Write | ||
| AV | 82 | Cfg_Cool_MinOffTime | Cooling Stage Minimum Off Time | Write | ||
| AV | 46 | Cfg_Cool_CoolLockoutSp | Outside Air Cooling Lockout Setpoint | Write | ||
| AV | 47 | Cfg_Cool_DischLoLimSp | Discharge Air Temperature Low Limit Setpoint | Write | ||
| AV | 1461 | Cfg_Cool_ModClEnMinOut | Minimum output voltage when modulating cool is enabled | Write | ||
| BV | 377 | Cfg_Mod_StgCl1En | Use stage 1 as cool enable when configured for modulating cool | Write | 0=Disable, 1=Enable | |
| AV | 1476 | Cfg_ModCoolMin_Output | Minimum voltage on cooling output (Zero) | Write | ||
| AV | 1478 | Cfg_ModCoolMax_Output | Maximum voltage on cooling output | Write | ||
| BV | 385 | Cfg_ModCoolInitialAtFullOp | Enable to initialize modulating cooling call at full output for 60 seconds | Write | 0=Disable, 1=Enable | |
| MV | 374 | Cfg_ModCoolFullOpCycleTime | Interval for driving modulating cooling to full output for 60 s | Write | 30=None 2, 60=Min 3, 90=Min 4, 120=Min 5 | |
| BV | 381 | Cfg_ModCoolAction | Modulating Cool Polarity selection- Applicable only for Multiple fan Speed Selection | Write | 0=Direct, 1=Reverse | |
| MV | 21 | Cfg_Equip_HeatType | Conventional Heat equipment type | Write | 1=None, 2=Staged, 3=Modulating | |
| AV | 54 | Cfg_Heat_Tr | Heating Throttling Range. | Δ°F | Write | |
| AV | 55 | Cfg_Heat_It | Heating Integral Time 0 = disable (i.e. proportional only). | Write | ||
| AV | 56 | Cfg_Heat_Dt | Heating Derivative Time. | Write | ||
| AV | 57 | Cfg_Heat_CPH | Heating System Response. | Write | ||
| AV | 58 | Cfg_Heat_MinOnTime | Heating Stage Minimum on Time. | Write | ||
| AV | 59 | Cfg_Heat_MinOffTime | Heating Stage Minimum Off Time | Write | ||
| AV | 60 | Cfg_Heat_HeatLockoutSp | Outside Air Heating Lockout Setpoint | Write | ||
| AV | 61 | Cfg_Heat_DischHiLimSp | Discharge Air Temperature High Limit Setpoint | °F | Write | |
| AV | 96 | Cfg_Heat_ModHtEnMinOut | Minimum output voltage when modulating heat is enabled | Write | ||
| BV | 35 | Cfg_Mod_StgHt1En | Use stage 1 as heat enable when configured for modulating heat | Write | 0=Disable, 1=Enable | |
| MV | 87 | Cfg_Heat_FuelType | Heating fuel type; sets the default cycles per hour | Write | 1=Standard Efficiency Gas, 2=High Efficiency Gas, 3=Oil, 4=Electric | |
| AV | 1475 | Cfg_ModHeatMin_Output | Minimum voltage on heating output (zero) | Write | ||
| AV | 1477 | Cfg_ModHeatMax_Output | Maximum voltage on heating output | Write | ||
| BV | 380 | Cfg_ModHeatAction | Modulating Heat Polarity selection Applicable only for Multiple fan Speed Selection | Write | 0=Direct, 1=Reverse | |
| AV | 48 | Cfg_Dehum_SpaceRHHighLimit | Space Relative Humidity (RH) High Limit setpoint. | %RH | Write | |
| BV | 12 | Cfg_Dehum_MinOnTimeOpEn | Minimum on Time Operation Enable | Write | 0=Disable, 1=Enable | |
| AV | 49 | Cfg_Dehum_MinOnTime | Dehumidify Extended Cooling Minimum on Time | Write | ||
| AV | 98 | Cfg_Dehum_MinOnDelay | Dehumidification Minimum ON time | Write | ||
| AV | 62 | Cfg_Hum_SpaceRHLowLimit | Space Relative Humidity (RH) Low Limit setpoint. | %RH | Write | |
| AV | 99 | Cfg_Hum_MinOnDelay | Humidification Minimum ON time. | Write | ||
| BV | 13 | Cfg_HeatPmp_CngOvrRelayType | Heat Pump Change Over Relay - Energize on Cooling (O) - Energize on Heating (B) | Write | 0=EnergOnCool, 1=EnergOnHeat | |
| AV | 50 | Cfg_HeatPmp_AuxHeatLockoutSp | Auxiliary OAT High Heat Lockout | °F | Write | |
| AV | 51 | Cfg_HeatPmp_CompLockoutSp | Heat Pump Compressor OAT Low Lockout | °F | Write | |
| AV | 52 | Cfg_HeatPmp_AuxHeatDroop | Auxiliary Heating Droop | °F | Write | |
| AV | 53 | Cfg_HeatPmp_AuxHeatRampFactor | Auxiliary Heating Recovery Ramp Factor. | Write | ||
| BV | 14 | Cfg_HeatPmp_ComfortMode | Decides the Auxiliary and compressor Heating operation | Write | 0=Saving, 1=Comfort | |
| AV | 215 | Cfg_HeatPmp_UpStgTmr | Up stage timer value. | Write | ||
| BV | 179 | Cfg_CO2_SensorType | External Economizer CO2 Sensor Input Voltage Range | Write | 0=0, 2=-10 Vdc 1 | |
| AV | 349 | Cfg_CO2_SensorZero | External Economizer CO2 Sensor Zero Selection @min. sensor voltage output. | ppm | Write | |
| AV | 350 | Cfg_CO2_SensorSpan | External Economizer CO2 Sensor Span | ppm | Write | |
| BV | 181 | Cfg_CO2Output | External Economizer CO2 Output Type | Write | 0=0, 2=-10 Vdc 1 | |
| MV | 84 | Cfg_Econ_FreeCoolSelect | Internal Economizer Free Cooling Criteria Selection | Write | 1=Fixed Drybulb, 2=Differential Drybulb, 3=Fixed Enthalpy, 4=Differential Enthalpy | |
| AV | 196 | Cfg_Econ_DrybulbSp | Dry-bulb setpoint below which free cooling is allowed | °F | Write | |
| MV | 94 | Cfg_Econ_EnthCurveSel | Choice of enthalpy curve for free cooling available when using Fixed Enthalpy 3 | Write | ||
| AV | 320 | Cfg_Econ_MinDamperPos | Minimal Damper Position of Single Fan Speed (1-Speed fan), when DCV is enabled. | % | Write | |
| AV | 321 | Cfg_Econ_MinDamperPosLow | Minimal Damper Position of Fan Low Speed (2-Speed fan), when DCV is enabled. | % | Write | |
| AV | 322 | Cfg_Econ_MinDamperPosMed | Minimal Damper Position of Fan Medium Speed (Multi- Speed fan), when DCV is enabled. | % | Write | |
| MV | 96 | Cfg_Econ_ShutdownDamperPos | 1=Close, 2=Open Damper Position in Shutdown mode | Write | ||
| MV | 95 | Cfg_Econ_FreezeProtDamperPos | 1=Close, 2=Min Damper Position in Freeze Protection mode | Write | ||
| AV | 201 | Cfg_Econ_MaTempSetPt | Mixed air temperature setpoint | °F | Write | |
| AV | 204 | Cfg_Econ_MaLoTempSetPt | Mixed air low limit for Freeze Protection | °F | Write | |
| AV | 327 | Cfg_Econ_MechCoolingDelay | Delay from full economizer to first mechanical cooling stage | Write | ||
| AV | 1466 | Cfg_MaTThresholdValue | MAT Threshold Value for FDD Enhancement logic | °F | Write | |
| AV | 1467 | Cfg_DmprDelayTime | Damper Time Delay to detect Mechanically Disconnect of Actuator | Write | ||
| AV | 222 | Cfg_Filt_HiLimit | High Limit Alarm Point. | Write | ||
| BV | 36 | Cfg_Stdby_OccSts | Standby occupancy status | Write | 0=Unoccupied, 1=Occupied | |
| MV | 9 | Cfg_Control_MainSensor | Temperature/ Humidity sensor selection. | Write | 1=Local Temp/ Hum, 2=Remote Temp/ Hum, 3=Multi Temp/ Hum | |
| AV | 14 | Cfg_Control_PowerupDelay | Initial delay to start control after power cycle. | Write | ||
| MV | 10 | Cfg_Control_SmokeMode | When Smoke Monitor state is on, the unit operates as configured through smoke mode | Write | 1=No Override, 2=Shutdown, 3=Pressurize, 4=Depressurize | |
| MV | 130 | Cfg_ZoneMultiSens_Control | Main control sensor configuration | Write | 1=Avg, 2=Min, 3=Max, 4=Smart | |
| AV | 33 | Cfg_ZoneMultiSens_Sens1_Wt | Averaging weight of the on-board temperature sensor | Write | ||
| AV | 34 | Cfg_ZoneMultiSens_Sens2_Wt | Averaging weight of Sylk temperature sensor at address 2 | Write | ||
| AV | 35 | Cfg_ZoneMultiSens_Sens3_Wt | Averaging weight of Sylk temperature sensor at address 3 | Write | ||
| AV | 36 | Cfg_ZoneMultiSens_Sens4_Wt | Averaging weight of Sylk temperature sensor at address 4 | Write | ||
| AV | 37 | Cfg_ZoneMultiSens_Sens5_Wt | Averaging weight of Sylk temperature sensor at address 5 | Write | ||
| AV | 219 | Cfg_ZoneMultiSens_Sens6_Wt | Averaging weight of Sylk temperature sensor at address 6 | Write | ||
| MV | 77 | Cfg_ZoneMultiHumSens_Control | Humidity sensor configuration. | Write | 1=Avg, 2=Min, 3=Max, 4=Smart | |
| AV | 181 | Cfg_ZoneMultiSens_HumSens1_Wt | Averaging weight of the on-board humidity sensor (0 = excluded) | Write | ||
| AV | 180 | Cfg_ZoneMultiSens_HumSens2_Wt | Averaging weight of Sylk humidity sensor at address 2 | Write | ||
| AV | 218 | Cfg_ZoneMultiSens_HumSens6_Wt | Averaging weight of Sylk humidity sensor at address 6 | Write | ||
| AVmin | 4 | Cfg_Setpoints_OccCoolSp | Occupied Cooling Setpoint | °F | Write | |
| AV | 5 | Cfg_Setpoints_StbyCoolSp | Standby Cooling Setpoint | °F | Write | |
| AV | 6 | Cfg_Setpoints_UnOccCoolSp | Unoccupied Cooling Setpoint | °F | Write | |
| AVmin | 7 | Cfg_Setpoints_OccHeatSp | Occupied Heating Setpoint | °F | Write | |
| AV | 8 | Cfg_Setpoints_StbyHeatSp | Standby Heating Setpoint | °F | Write | |
| AV | 9 | Cfg_Setpoints_UnOccHeatSp | Unoccupied Heating Setpoint | °F | Write | |
| AV | 18 | Cfg_Recovery_MaxCoolRampRate | Maximum Cooling Setpoint Ramp | Δ°F | Write | |
| AV | 16 | Cfg_Recovery_MinCoolRampRate | Minimum Cooling Setpoint Ramp | Δ°F | Write | |
| AV | 17 | Cfg_Recovery_MaxCoolRampTemp | Outdoor air temperature at the maximum cool setpoint ramp. | Write | ||
| AV | 15 | Cfg_Recovery_MinCoolRampTemp | Outdoor air temperature at the minimum cool setpoint ramp. | Write | ||
| AV | 22 | Cfg_Recovery_MaxHeatRampRate | Maximum Cooling Setpoint Ramp | Δ°F | Write | |
| AV | 20 | Cfg_Recovery_MinHeatRampRate | Minimum Cooling Setpoint Ramp | Δ°F | Write | |
| AV | 21 | Cfg_Recovery_MaxHeatRampTemp | Outdoor air temperature at the maximum heat setpoint ramp. | Write | ||
| AV | 19 | Cfg_Recovery_MinHeatRampTemp | Outdoor air temperature at the minimum heat setpoint ramp. | Write | ||
| AV | 38 | Cfg_DemandLimCtl_TempDiffSp | Demand limit temperature differential Setpoint | °F | Write | |
| BV | 157 | Cfg_Thermostat_SystemChangeOver | Auto changeover allowed (Auto) or not (Manual) on the system switch | Write | 0=Auto, 1=Manual | |
| MV | 36 | Cfg_Thermostat_SystemConfig | To limit available user configurable options | Write | 1=off/heat, 2=off/cool, 3=off/cool/ heat, 4=off/Auto/ cool/heat, 5=off/Auto/ cool/heat/ Em heat | |
| AV | 10 | Cfg_Thermostat_BypOverrideTime | Thermostat Bypass Override Time | Write | ||
| AV | 12 | Cfg_Thermostat_MinCoolSp | Minimum Cool Setpoint of Thermostat | °F | Write | |
| AV | 13 | Cfg_Thermostat_MaxHeatSp | Maximum Heat Setpoint of Thermostat | °F | Write | |
| AV | 101 | Cfg_Thermostat_Deadband | Temperature differential between heat and cool setpoint | Write | ||
| AV | 257 | Cfg_Thermostat_HtAdjStPt | Temporary heat setpoint adjustment from User or from the supervisor | Δ°F | Write | |
| AV | 256 | Cfg_Thermostat_ClAdjStPt | Temporary cool setpoint adjustment from User or from the supervisor | Δ°F | Write | |
| AV | 102 | Cfg_Thermostat_TempOffSpLimit | This point is used to limit the range of user adjustable setpoint | Δ°F | Write | |
| AV | 23 | Cfg_LocalSensCalOffset_Temp | Local internal Temperature sensor calibration offset | Write | ||
| AV | 103 | Cfg_LocalSensCalOffset_Hum | Local internal humidity sensor calibration offset | %RH | Write | |
| AV | 24 | Cfg_SylkCalOffset_SylkBus2Temp | Temperature calibration offset for the Sylk sensor at address 2 | Write | ||
| AV | 25 | Cfg_SylkCalOffset_SylkBus2RH | TR40_2 Humidity calibration offset | %RH | Write | |
| AV | 100 | Cfg_SylkCalOffset_SylkBus2CO2 | TR40_2 CO2 calibration offset | ppm | Write | |
| AV | 26 | Cfg_SylkCalOffset_SylkBus3Temp | TR40_3 Temperature calibration offset | Write | ||
| AV | 27 | Cfg_SylkCalOffset_SylkBus4Temp | TR40_4 Temperature calibration offset | Write | ||
| AV | 28 | Cfg_SylkCalOffset_SylkBus5Temp | TR40_5 Temperature calibration offset | Write | ||
| AV | 216 | Cfg_SylkCalOffset_SylkBus6Temp | TR120_6 Temperature calibration offset | Write | ||
| AV | 217 | Cfg_SylkCalOffset_SylkBus6RH | TR120_6 Humidity calibration offset | %RH | Write | |
| AV | 29 | Cfg_SylkCalOffset_SylkBus8Temp | C7400S Outdoor Air Temperature calibration offset | Write | ||
| AV | 30 | Cfg_SylkCalOffset_SylkBus8RH | C7400S Outdoor Air Humidity calibration offset | %RH | Write | |
| AV | 137 | Cfg_SylkCalOffset_SylkBus9Temp | C7400S Return Air Temperature calibration offset | Write | ||
| AV | 214 | Cfg_SylkCalOffset_SylkBus9RH | C7400S Return Air Humidity calibration offset | %RH | Write | |
| AV | 31 | Cfg_SylkCalOffset_SylkBus10Temp | C7400S Discharge Air Temperature calibration offset | Write | ||
| AV | 32 | Cfg_SylkCalOffset_SylkBus10RH | C7400S Discharge Air Humidity calibration offset | %RH | Write | |
| AV | 138 | Cfg_SylkCalOffset_SylkBus12Temp | C7400S Mixed Air Temperature calibration offset | Write | ||
| AV | 771 | Cfg_SylkCalOffset_SylkBus12RH | C7400S Mixed Air Humidity calibration offset | %RH | Write | |
| AV | 185 | Cfg_UISensCalOffset_DATemp | Universal Input Discharge Air Temperature calibration offset | Write | ||
| AV | 186 | Cfg_UISensCalOffset_OATemp | Universal Input Outdoor Air Temperature calibration offset | Write | ||
| AV | 187 | Cfg_UISensCalOffset_MATemp | Universal Input Mixed Air Temperature calibration offset. | Write | ||
| AV | 427 | Cfg_UISensCalOffset_RATemp | Universal Input Return Air Temperature calibration offset | Write | ||
| AV | 1464 | Cfg_UISensCalOffset_SpcTemp | Universal Input Space Temperature calibration offset | °F | Write | |
| AV | 188 | Cfg_UISensCalOffset_CO2Lvl | Universal Input CO2 calibration offset | ppm | Write | |
| MV | 85 | Cfg_Sylk_SylkBus2En | Sylk Bus addr-2 device enable/ disable. Sylk Device Type: TR40THCO2 | Write | 1=Disable, 2=TempOnly, 3=Temp&Hum, 4=Temp, Hum & CO2, 5=Temp & CO2 | |
| MV | 86 | Cfg_Sylk_SylkBus6En | Sylk Bus addr-6 device enable/ disable. Device Type: TR120H/TR75E | Write | 1=Disable, 2=TempOnly, 3=Temp&Hum | |
| BV | 151 | Cfg_Sylk_SylkBus8En | Sylk Bus addr-8 device enable/ disable. Device Type: C7400 | Write | 0=Disable, 1=Enable | |
| BV | 152 | Cfg_Sylk_SylkBus9En | Sylk Bus addr-9 device enable/ disable. Device Type: C7400 | Write | 0=Disable, 1=Enable | |
| BV | 153 | Cfg_Sylk_SylkBus10En | Sylk Bus addr-10 device enable/ disable. Device Type: C7400 | Write | 0=Disable, 1=Enable | |
| BV | 178 | Cfg_Sylk_SylkBus11En | Sylk Bus addr-11 device enable/ disable. Device Type: MS3103J Sylk Actuator | Write | 0=Disable, 1=Enable | |
| BV | 154 | Cfg_Sylk_SylkBus12En | Sylk Bus addr-12 device enable/ disable. Device Type: C7400 | Write | 0=Disable, 1=Enable | |
| AV | 301 | Cfg_SylkBus11TravelTime | Sylk actuator full-stroke travel time | Write | ||
| AV | 331 | Cfg_SylkBus11Testmode | Sylk actuator test mode (30 s travel time) | Write | ||
| MV | 135 | Sylk11_EconFaultAlarm | Sylk Actuator Alarm Output | Write | 1=Normal, 2=StuckOpen, 3=DamperStuckAtMin, 4=BadOrUnPlugged, 5=ActrMechDisc | |
| BV | 246 | Cfg_StagedHeatEn | Delta-T check on/off for staged or auxiliary heat | Write | 0=Disable, 1=Enable | |
| AV | 955 | Cfg_HeatStage1Min | Heating Stage-1 Heating Min Setpoint | Write | ||
| AV | 956 | Cfg_HeatStage1Max | Heating Stage-1 Heating Max Setpoint | Write | ||
| AV | 957 | Cfg_HeatStage1Delay | Heating Stage-1 Alert Delay Setpoint | Write | ||
| AV | 958 | Cfg_HeatStage2Min | Heating Stage-2 Heating Min Setpoint | Write | ||
| AV | 959 | Cfg_HeatStage2Max | Heating Stage-2 Heating Max Setpoint | Write | ||
| AV | 960 | Cfg_HeatStage2Delay | Heating Stage-2 Alert Delay Setpoint | Write | ||
| AV | 961 | Cfg_HeatStage3Min | Heating Stage-3 Heating Min Setpoint | Write | ||
| AV | 962 | Cfg_HeatStage3Max | Heating Stage-3 Heating Max Setpoint | Write | ||
| AV | 963 | Cfg_HeatStage3Delay | Heating Stage-3 Alert Delay Setpoint | Write | ||
| BV | 247 | Cfg_StagedCoolEn | Delta-T check on/off for staged or compressor cooling | Write | 0=Disable, 1=Enable | |
| AV | 964 | Cfg_CoolStage1Min | Cooling Stage-1 Cooling Min Setpoint | Write | ||
| AV | 965 | Cfg_CoolStage1Max | Cooling Stage-1 Cooling Max Setpoint | Write | ||
| AV | 966 | Cfg_CoolStage1Delay | Cooling Stage-1 Alert Delay Setpoint | Write | ||
| AV | 967 | Cfg_CoolStage2Min | Cooling Stage-2 Cooling Min Setpoint | Write | ||
| AV | 968 | Cfg_CoolStage2Max | Cooling Stage-2 Cooling Max Setpoint | Write | ||
| AV | 969 | Cfg_CoolStage2Delay | Cooling Stage-2 Alert Delay Setpoint | Write | ||
| AV | 970 | Cfg_CoolStage3Min | Cooling Stage-3 Cooling Min Setpoint | Write | ||
| AV | 971 | Cfg_CoolStage3Max | Cooling Stage-3 Cooling Max Setpoint | Write | ||
| AV | 972 | Cfg_CoolStage3Delay | Cooling Stage-3 Alert Delay Setpoint | Write | ||
| AV | 1739 | Cfg_CoolStage4Min | Cooling Stage-4 Cooling Min Setpoint | Write | ||
| AV | 1740 | Cfg_CoolStage4Max | Cooling Stage-4 Cooling Max Setpoint | Write | ||
| AV | 1741 | Cfg_CoolStage4Delay | Cooling Stage-4 Alert Delay Setpoint | Write | ||
| BV | 248 | Cfg_ComprHeatEn | Delta-T On/OFF switch for compressor heating stage of Heat Pump. | Write | 0=Disable, 1=Enable | |
| AV | 973 | Cfg_ComprHeatStage1Min | Heating Stage-1 Heating/Cooling Min Setpoint | Write | ||
| AV | 974 | Cfg_ComprHeatStage1Max | Heating Stage-1 Heating/Cooling Max Setpoint | Write | ||
| AV | 975 | Cfg_ComprHeatStage1Delay | Heating/Cooling Stage-1 Alert Delay Setpoint | Write | ||
| AV | 976 | Cfg_ComprHeatStage2Min | Heating/Cooling Stage-2 Heating Min Setpoint | Write | ||
| AV | 977 | Cfg_ComprHeatStage2Max | Heating/Cooling Stage-2 Heating Max Setpoint | Write | ||
| AV | 978 | Cfg_ComprHeatStage2Delay | Heating/Cooling Stage-2 Alert Delay Setpoint | Write | ||
| AV | 979 | Cfg_ComprHeat3Min | Heating/Cooling Stage-3 Heating Min Setpoint | Write | ||
| AV | 980 | Cfg_ComprHeat3Max | Heating/Cooling Stage-3 Heating Max Setpoint | Write | ||
| AV | 981 | Cfg_ComprHeat3Delay | Heating/Cooling Stage-3 Alert Delay Setpoint | Write | ||
| BV | 249 | Cfg_ModHeatEn | Delta-T check on/off for modulating heat | Write | 0=Disable, 1=Enable | |
| AV | 986 | Cfg_ModHeatMin | Modulating Heating Min Setpoint | Write | ||
| AV | 987 | Cfg_ModHeatMax | Modulating Heating Max Setpoint | Write | ||
| AV | 988 | Cfg_ModHeatDelay | Modulating Heating Alert Delay Setpoint | Write | ||
| AV | 989 | Cfg_ModHeatMinOuput | Modulating Heating Min Output percentage to enable Delta T | % | Write | |
| BV | 250 | Cfg_ModulatingCoolEn | Delta-T On/OFF switch for modulating cooling equipment | Write | 0=Disable, 1=Enable | |
| AV | 982 | Cfg_ModCoolMin | Modulating Cooling Min Setpoint | °C | Write | |
| AV | 983 | Cfg_ModCoolMax | Modulating Cooling Max Setpoint | °C | Write | |
| AV | 984 | Cfg_ModCoolDelay | Modulating Cooling Alert Delay Setpoint | Write | ||
| AV | 985 | Cfg_ModCoolMinOuput | Modulating Cooling Min Output percentage to enable Delta T | % | Write | |
| AV | 990 | Cfg_StagedHeatMATempLimitMin | Staged Heating MAT Min Setpoint | Write | ||
| AV | 991 | Cfg_StagedHeatMATempLimitMax | Staged Heating MAT Max Setpoint | Write | ||
| BV | 134 | Cfg_StagedHeatMARHLimitEn | Staged Heating MA RH Enable | Write | ||
| AV | 992 | Cfg_StagedHeatMARHLimitMin | Staged Heating MA RH Min Setpoint | %RH | Write | |
| AV | 993 | Cfg_StagedHeatMARHLimitMax | Staged Heating MA RH Max Setpoint | %RH | Write | |
| AV | 994 | Cfg_StagedHeatOATempLimitMin | Staged Heating OAT Min Setpoint | Write | ||
| AV | 995 | Cfg_StagedHeatOATempLimitMax | Staged Heating OAT Max Setpoint | Write | ||
| AV | 996 | Cfg_StagedHeatOARHLimitMin | Staged Heating OA RH Min Setpoint | %RH | Write | |
| AV | 997 | Cfg_StagedHeatOARHLimitMax | Staged Heating OA RH Max Setpoint | %RH | Write | |
| AV | 998 | Cfg_StagedCoolMATempLimitMin | Staged Cooling MAT Min Setpoint | Write | ||
| AV | 999 | Cfg_StagedCoolMATempLimitMax | Staged Cooling MAT Max Setpoint | Write | ||
| AV | 1000 | Cfg_StagedCoolMARHLimitMin | Staged Cooling MA RH Min Setpoint | %RH | Write | |
| AV | 1001 | Cfg_StagedCoolMARHLimitMax | Staged Cooling MA RH Max Setpoint | %RH | Write | |
| AV | 1002 | Cfg_StagedCoolOATempLimitMin | Staged Cooling OAT Min Setpoint | Write | ||
| AV | 1003 | Cfg_StagedCoolOATempLimitMax | Staged Cooling OAT Max Setpoint | Write | ||
| AV | 1004 | Cfg_StagedCoolOARHLimitMin | Staged Cooling OA RH Min Setpoint | %RH | Write | |
| AV | 1005 | Cfg_StagedCoolOARHLimitMax | Staged Cooling OA RH Max Setpoint | %RH | Write | |
| AV | 1022 | Cfg_CmprHeatMATempLimitMin | CompressorHeat Heating MAT Min Setpoint | Write | ||
| AV | 1023 | Cfg_CmprHeatMATempLimitMax | CompressorHeat Heating MAT Max Setpoint | Write | ||
| BV | 150 | Cfg_CmprHeatMARHLimitEn | CompressorHeat Heating MA RH Enable | Write | ||
| AV | 1024 | Cfg_CmprHeatMARHLimitMin | CompressorHeat Heating MA RH Min Setpoint | %RH | Write | |
| AV | 1025 | Cfg_CmprHeatMARHLimitMax | CompressorHeat Heating MA RH Max Setpoint | %RH | Write | |
| AV | 1026 | Cfg_CmprHeatOATempLimitMin | CompressorHeat Heating OAT Min Setpoint | Write | ||
| AV | 1027 | Cfg_CmprHeatOATempLimitMax | CompressorHeat Heating OAT Max Setpoint | Write | ||
| AV | 1028 | Cfg_CmprHeatOARHLimitMin | CompressorHeat Heating OA RH Min Setpoint | %RH | Write | |
| AV | 1029 | Cfg_CmprHeatOARHLimitMax | CompressorHeat Heating OA RH Max Setpoint | %RH | Write | |
| MV | 141 | Cfg_ModHeatMATempLimitEn | Mod Heating MAT Enable | Write | 1=NoLimits, 2=MinLimit_MaxNoLimit, 3=MinNoLimit_MaxLimit, 4=MinLimit,MaxLimitAll | |
| AV | 1006 | Cfg_ModHeatMATempLimitMin | Mod Heating MAT Min Setpoint | Write | ||
| AV | 1007 | Cfg_ModHeatMATempLimitMax | Mod Heating MAT Max Setpoint | Write | ||
| BV | 142 | Cfg_ModHeatMARHLimitEn | Mod Heating MA RH Enable | Write | ||
| AV | 1008 | Cfg_ModHeatMARHLimitMin | Mod Heating MA RH Min Setpoint | %RH | Write | |
| AV | 1009 | Cfg_ModHeatMARHLimitMax | Mod Heating MA RH Max Setpoint | %RH | Write | |
| BV | 143 | Cfg_ModHeatOATempLimitEn | Mod Heating OAT Enable | Write | ||
| AV | 1010 | Cfg_ModHeatOATempLimitMin | Mod Heating OAT Min Setpoint | Write | ||
| AV | 1011 | Cfg_ModHeatOATempLimitMax | Mod Heating OAT Max Setpoint | Write | ||
| AV | 1012 | Cfg_ModHeatOARHLimitMin | Mod Heating OA RH Min Setpoint | %RH | Write | |
| AV | 1013 | Cfg_ModHeatOARHLimitMax | Mod Heating OA RH Max Setpoint | %RH | Write | |
| BV | 145 | Cfg_ModCoolMATempLimitEn | Mod Cooling MAT Enable | Write | ||
| AV | 1014 | Cfg_ModCoolMATempLimitMin | Mod Cooling MAT Min Setpoint | °C | Write | |
| AV | 1015 | Cfg_ModCoolMATempLimitMax | Mod Cooling MAT Max Setpoint | °C | Write | |
| BV | 146 | Cfg_ModCoolMARHLimitEn | Mod Cooling MA RH Enable | Write | ||
| AV | 1016 | Cfg_ModCoolMARHLimitMin | Mod Cooling MA RH Min Setpoint | %RH | Write | |
| AV | 1017 | Cfg_ModCoolMARHLimitMax | Mod Cooling MA RH Max Setpoint | %RH | Write | |
| AV | 1018 | Cfg_ModCoolOATempLimitMin | Mod Cooling OAT Min Setpoint | °C | Write | |
| AV | 1019 | Cfg_ModCoolOATempLimitMax | Mod Cooling OAT Max Setpoint | °C | Write | |
| AV | 1020 | Cfg_ModCoolOARHLimitMin | Mod Cooling OA RH Min Setpoint | %RH | Write | |
| AV | 1021 | Cfg_ModCoolOARHLimitMax | Mod Cooling OA RH Max Setpoint | %RH | Write | |
| BV | 251 | Cfg_RunWithHum | Delta T Run With Humidification Point | Write | 0=Disable, 1=Enable | |
| BV | 252 | Cfg_RunWithDehum | Delta T Run With De-Humidification Point | Write | 0=Disable, 1=Enable | |
| AV | 1047 | Cfg_DRHiOffset | Configuration of DR setpoint offset for Simple Event with High level | Write | ||
| AV | 1465 | Cfg_DRMoOffset | Configuration of DR setpoint offset for Simple Event with Moderate level | Write | ||
| AV | 1048 | Cfg_DRLoOffset | Configuration of DR setpoint offset for Simple Event with Low level | Write | ||
| MV | 258 | Cfg_DRDefaultOption | Demand response action: setpoint offset or absolute setpoints | Write | 1=Delta, 2=Absolute | |
| AV | 1049 | Cfg_DRDefaultOffset | Configuration of default DR setpoint offset | Write | ||
| AV | 1050 | Cfg_DRDefaultHtSp | Configuration of default DR Heat setpoint | Write | ||
| AV | 1051 | Cfg_DRDefaultClSp | Configuration of default DR Cool setpoint | Write | ||
| AV | 1052 | Cfg_DRMaxClSp | Configuration of Maximum Cool Setpoint allowed during active DR event | Write | ||
| AV | 205 | Cfg_DCV_VentMinPosHigh | Demand control ventilation OA damper minimum position for highest fan speed. | % | Write | |
| AV | 206 | Cfg_DCV_VentMaxPosHigh | Demand control ventilation OA damper maximum position for highest fan speed. | % | Write | |
| AV | 504 | Cfg_DCV_VentMinPosMid | Demand control ventilation OA damper minimum position for medium fan speed. | % | Write | |
| AV | 311 | Cfg_DCV_VentMaxPosMid | Demand control ventilation OA damper maximum position for medium fan speed. | % | Write | |
| AV | 207 | Cfg_DCV_VentMinPosLow | Demand control ventilation OA damper minimum position for lowest fan speed. | % | Write | |
| AV | 208 | Cfg_DCV_VentMaxPosLow | Demand control ventilation OA damper maximum position for lowest fan speed. | % | Write | |
| AV | 209 | Cfg_DCV_CO2SetPt | CO2 threshold with +200 ppm throttling range. | ppm | Write | |
| AV | 213 | Cfg_DCV_CO2Deadband | CO2 dead band from the setpoint.(Display purpose only do not consider for calculation) | Write | ||
| BV | 259 | Cfg_Co2Output_Override | Drive the CO2 output to 10 V during a purge | Write | ||
| BV | 258 | Cfg_PurOutput | Purge Control Output | Write | 0=0, 2=-10V 1 | |
| BV | 172 | Cfg_Purge_CtrlEn | Purge Function enable point | Write | 0=Disable, 1=Enable | |
| AV | 334 | Cfg_Purge_Pos | Purge Mode Damper Position Setpoint. Applicable to economizer version 2.7.5.4. | % | Write | |
| MV | 91 | Cfg_WindowOpnSetng | Window open sensor settings. | Write | 1=Switch to Unoccupied Mode, 2=Turn off HVAC System, 3=Do nothing | |
| AV | 297 | Cfg_WindowOpnDelay | Window open sensor on delay. | Write | ||
| AV | 291 | Cfg_CO2Alarm_LvlHighLim | CO2 level above which the CO2 alarm is raised | ppm | Write | |
| AV | 192 | Cfg_Alarm_SupplyFanAlarmConfig | Keep or stop heating/cooling outputs on a supply fan alarm | Write | ||
| AV | 193 | Cfg_Alarm_TempSensAlarmConfig | Keep or stop heating/cooling outputs on a temperature sensor alarm | Write | ||
| MO | 99 | Gui_Alarm_SylkActuatorFail | Sylk actuator fault code, display only | Write | ||
| MV | 574 | Cfg_AlarmConfig_CHWDrainPanSrAlarm | Bit flags for outputs to shut off on a leak/drain pan alarm | Write | 0=False- Don’t turn off Cool Outputs when Pan Sr alarm is triggered Bit, 1=TurnOffCoolOuputs, 2=PopUpOnHomeScre en, 4=Acknowledged, 8=TurnOffHeatOutputs, 16=TurnOffFanOutputs Bit | |
| AV | 254 | Cfg_SpcAlarm_TempHighLim | Space temperature high alarm limit | °F | Write | |
| AV | 332 | Cfg_DaTAlarm_TempHighLim | Discharge air temperature high alarm limit | °F | Write | |
| AV | 333 | Cfg_DATAlarmTempLowLim | Discharge air temperature low alarm limit | °F | Write | |
| BV | 1 | ni_BypassState | Net Bypass Input to enable Bypass Timer | Write | 0=Disable, 1=Enable | |
| AV | 2 | ni_BypassValue | Bypass Value to enable Bypass Time | Write | ||
| BV | 2 | ni_DemandLimitControlEn | Demand Limit Control (DLC) input to limit the htg/ clg demand. | Write | 0=Normal, 1=DLCEnable | |
| AV | 89 | ni_OutdoorTemp | This point is considered for Network point sharing of Outside Temperature sensor. | °F | Write | |
| AV | 194 | ni_OutdoorHum | This point is considered for Network point sharing of Outside Humidity sensor. | %RH | Write | |
| AV | 339 | ni_OutdoorEnthalpy | This point is considered for Network point sharing of OA Enthalpy | BTU/lb | Write | |
| AV | 340 | ni_OutdoorDewpoint | This point is considered for Network point sharing of OA Dewpoint | °F | Write | |
| AV | 341 | ni_RaEnthalpy | This point is considered for Network point sharing of RA Enthalpy | BTU/lb | Write | |
| AV | 342 | ni_RaDewpoint | This point is considered for Network point sharing of RA Dewpoint | °F | Write | |
| BV | 390 | ni_ServiceExhaustFan1Cmd | Network input to command Exhaust Fan1-4620 | Write | 0=CmdOff, 1=CmdOn | |
| BV | 391 | ni_ServiceExhaustFan2Cmd | Network input to command Exhaust Fan2-4621 | Write | 0=CmdOff, 1=CmdOn | |
| BV | 4 | ni_ShutdownState | This point is considered for Network point sharing Shutdown input from Network. | Write | 0=Normal, 1=Shutdown | |
| BV | 5 | ni_SmokeMonitorstate | Smoke Detector Network Input | Write | 0=Normal, 1=Smoke | |
| AV | 81 | ni_SpaceCO2 | This point is considered for Network point sharing of Space CO2 Value. | ppm | Write | |
| AV | 80 | ni_SpaceRH | This point is considered for Network point sharing of Space RH Value. | %RH | Write | |
| AV | 104 | ni_SpaceTemp | This point is considered for Network point sharing of Space Temperature Value. | °F | Write | |
| BV | 25 | ni_WSHPEnableState | Water source heat pump enable shared from the network | Write | 0=Disable, 1=Enable | |
| AV | 88 | ni_WSHPEnableValue | Water source heat pump water flow value shared from the network | Write | ||
| BVmin | 158 | ni_OccupancySensor | This point is considered for Network point sharing of Network occupancy sensor | Write | 0=Unoccupied, 1=Occupied | |
| MVmin | 3 | ni_ApplicationMode | Application mode from the network; not kept over a power cycle | Write | 1=Auto, 2=Heat, 3=Cool, 4=Emergency Heat, 5=Fan Only, 6=Off | |
| BV | 6 | ni_ServiceModeEn | Service mode for commissioning; shuts down all equipment | Write | 0=No Override, 1=Service | |
| MV | 23 | ni_ServiceFan | Fan type configuration network input when service mode is enabled. | Write | 1=Off, 2=On (Hi), 3=Low, 4=Medium | |
| AV | 85 | ni_ServiceFanSpeed | Fan speed configuration network input when service mode is enabled. | % | Write | |
| BV | 16 | ni_ServiceCompStage1 | Compressor Stage 1 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 17 | ni_ServiceCompStage2 | Compressor Stage 2 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 18 | ni_ServiceCompStage3 | Compressor Stage 3 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 463 | Ni_ServiceCoolStage4 | Conventional Cool Stage 4 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 19 | ni_ServiceHeatStage1 | Heating Stage 1 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 20 | ni_ServiceHeatStage2 | Heating Stage 2 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 21 | ni_ServiceHeatStage3 | Heating Stage 3 configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| AV | 86 | ni_ServiceHeatCtrl | Modulating Heating control configuration network input when service mode is enabled. | % | Write | |
| AV | 1152 | ni_ServiceCoolCtrl | Modulating Cooling control configuration network input when service mode is enabled. | % | Write | |
| BV | 22 | ni_ServiceRevVlvCmd | Reversing valve configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 23 | ni_ServiceSimpleDehCmd | Dehumudification configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 24 | ni_ServiceSimpleHumCmd | Humidification configuration network input when service mode is enabled. | Write | 0=Cmd Off, 1=Cmd On | |
| BV | 141 | ni_ServiceEconomizerCmd | Economizer command when service mode is enabled | Write | 0=Cmd Off, 1=Cmd On | |
| AV | 212 | ni_ServiceOaDmprCtrl | Outside air damper position when service mode is enabled. | % | Write | |
| BV | 220 | ni_ServiceCO2OutputCmd | Co2 Output Command when service mode is enabled | Write | 0=0, 2=-10 Vdc 1 | |
| AV | 859 | ni_ServicePurgeOP2-10V | Purge Enhanced 2-10V Output Command when service mode is enabled | % | Write | |
| AV | 195 | ni_DeviceLock | Locks the thermostat screen against local changes | Write | ||
| AV | 338 | ni_SylkBus11Cmd | Outside air damper position during network shared value | % | Write | |
| BV | 174 | ni_mstpClearErr | Clears the MS/TP header and data CRC error counters | Write | 0=False, 1=True | |
| AV | 238 | ni_SylkAddr2Temp | Network Temp override for sylk addr-2 | Write | ||
| AV | 239 | ni_SylkAddr2Hum | Network Hum override for sylk addr-2 | Write | ||
| AV | 240 | ni_SylkAddr2CO2 | Network CO2 override for sylk addr-2 | Write | ||
| AV | 241 | ni_SylkAddr3Temp | Network Temp override for sylk addr-3 | Write | ||
| AV | 242 | ni_SylkAddr4Temp | Network Temp override for sylk addr-4 | Write | ||
| AV | 243 | ni_SylkAddr5Temp | Network Temp override for sylk addr-5 | Write | ||
| AV | 244 | ni_SylkAddr6Temp | Network Temp override for sylk addr-6 | Write | ||
| AV | 245 | ni_SylkAddr6Hum | Network Hum override for sylk addr-6 | Write | ||
| AV | 248 | ni_SylkAddr9Temp | Network Temp override for sylk addr-9 | Write | ||
| AV | 249 | ni_SylkAddr9Hum | Network Hum override for sylk addr-9 | Write | ||
| AV | 250 | ni_SylkAddr10Temp | Network Temp override for sylk addr-10 | Write | ||
| AV | 251 | ni_SylkAddr10Hum | Network Hum override for sylk addr-10 | Write | ||
| AV | 246 | ni_SylkAddr12Temp | Network Temp override for sylk addr-12 | Write | ||
| AV | 772 | ni_SylkAddr12Hum | Network Hum override for sylk addr-12 | Write | ||
| BV | 159 | Cfg_NetOccSenFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 262 | Cfg_NetOccSenFailFalbck | Network Fail Detection Fall back value | Write | ||
| BV | 160 | Cfg_NetOccSenFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | Write | 0=Unoccupied, 1=Occupied | |
| AV | 263 | Cfg_NetOccSenFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 163 | Cfg_NetOATFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 270 | Cfg_NetOATFailFalbck | Network Fail Detection Fall back value | Write | ||
| AV | 272 | Cfg_NetOATFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | °F | Write | |
| AV | 271 | Cfg_NetOATFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 162 | Cfg_NetOAHumFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 267 | Cfg_NetOAHumFailFalbck | Network Fail Detection Fall back value | Write | ||
| AV | 269 | Cfg_NetOAHumFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | %RH | Write | |
| AV | 268 | Cfg_NetOAHumFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 164 | Cfg_NetShtdwnFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 273 | Cfg_NetShtdwnFailFalbck | Network Fail Detection Fall back value | Write | ||
| BV | 165 | Cfg_NetShtdwnFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | Write | 0=Normal, 1=Shutdown | |
| AV | 274 | Cfg_NetShtdwnFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 166 | Cfg_NetSpceCO2FailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 275 | Cfg_NetSpceCO2FailFalbck | Network Fail Detection Fall back value | Write | ||
| AV | 277 | Cfg_NetSpceCO2FailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | ppm | Write | |
| AV | 276 | Cfg_NetSpceCO2FailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 167 | Cfg_NetSpceRHFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 278 | Cfg_NetSpceRHFailFalbck | Network Fail Detection Fall back value | Write | ||
| AV | 280 | Cfg_NetSpceRHFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | %RH | Write | |
| AV | 279 | Cfg_NetSpceRHFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 168 | Cfg_NetSpceTmpFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 281 | Cfg_NetSpceTmpFailFalbck | Network Fail Detection Fall back value | Write | ||
| AV | 283 | Cfg_NetSpceTmpFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | °F | Write | |
| AV | 282 | Cfg_NetSpceTmpFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 169 | Cfg_NetWSHPEnStFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 284 | Cfg_NetWSHPEnStFailFalbck | Network Fail Detection Fall back value | Write | ||
| BV | 170 | Cfg_NetWSHPEnStFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | Write | 0=Disable, 1=Enable | |
| AV | 285 | Cfg_NetWSHPEnStFailDetDly | Network Fail Detection delay in seconds | Write | ||
| BV | 171 | Cfg_NetWSHPEnValFailDetEn | Network Fail Detection will be enabled only if network point is considered for sharing | Write | 0=Disable, 1=Enable | |
| AV | 286 | Cfg_NetWSHPEnValFailFalbck | Network Fail Detection Fall back value | Write | ||
| AV | 287 | Cfg_NetWSHPEnValFailFxdVal | Applicable only if Network Fail Fall back value is configured to Fixed value (2) | % | Write | |
| AV | 288 | Cfg_NetWSHPEnValFailDetDly | Network Fail Detection delay in seconds | Write | ||
| MV | 2 | no_EffOccSensState | Network Output to show Effective Occupancy sensor state | Read | 1=Occupied, 2=Unoccupied, 3=Unused | |
| BO | 1 | no_BypassState | Timed after-hours occupancy (bypass) active | Read | 0=No Bypass, 1=Bypass | |
| AO | 1 | no_BypassValue | Network Output to show Bypass Value output. 0=No Bypass, 100=Bypass. | Read | ||
| BO | 3 | no_OccupancyState | Network Output to show the System is in occupied/ unoccupied state. | Read | 0=Unoccupied, 1=Occupied | |
| BO | 4 | no_SystemDisable | Network Output to disable the system. | Read | 0=Normal, 1=Disable | |
| BO | 5 | no_ServiceMd | Network Output to enable the Service mode | Read | 0=Disable, 1=Enable | |
| AO | 2 | no_EffDlcShift | Network Output to show Effective Demand Limit Shift. | °F | Read | |
| AOmin | 3 | no_EffHeatSp | Network Output to show Effective Heating Setpoint | Read | ||
| AOmin | 4 | no_EffCoolSp | Network Output to show Effective Cooling Setpoint | Read | ||
| AO | 5 | no_EffSp | Network Output to show Effective Setpoint | Read | ||
| AO | 6 | no_EffAuxHeatSetpoint | Network Output to show Effective auxiliary heat setpoint. | Read | ||
| BO | 7 | no_IsFanOnly | Network Output to enabled/ disabled Fan Only mode. | Read | 0=Normal, 1=Fan Only | |
| BO | 8 | no_DehumActive | Network Output to Active/ Inactive Dehumidification mode. | Read | 0=Inactive, 1=Active | |
| BO | 9 | no_HumActive | Network Output to Active/ Inactive Humidification mode. | Read | 0=Inactive, 1=Active | |
| BO | 10 | no_IsHeatDisable | Network Output to enable/disable the heat mode. | Read | 0=Enable, 1=Disable | |
| BO | 11 | no_IsAuxHeatDisable | Network Output to enable/disable the auxiliary heat mode | Read | 0=Enable, 1=Disable | |
| BO | 12 | no_IsCompHeatDisable | Network Output to enable/disable the compressor heat mode | Read | 0=Enable, 1=Disable | |
| AO | 7 | no_ActiveHeatStages | Network Output to show Active heat Stages | Read | ||
| AO | 8 | no_ActiveAuxHeatStages | Network Output to show Active auxiliary heat stages | Read | ||
| AO | 9 | no_HeatCtrlOut | Network Output to show Modulating Heat Output | % | Read | |
| AO | 10 | no_ActiveCompHeatStages | Network Output to show Active compressor Stages | Read | ||
| BO | 13 | no_DaHilimit | Network Output to show Discharge Air High Limit output | Read | 0=Normal, 1=HiLimit | |
| BO | 14 | no_CompDaHilimit | Network Output to show Compressor Discharge Air High Limit output | Read | 0=Normal, 1=HiLimit | |
| BO | 15 | no_IsCoolDisable | Network Output to enabled/ disabled Cooling. | Read | 0=Enable, 1=Disable | |
| AO | 11 | no_ActiveCoolStages | Network Output to show Active cool Stages | Read | ||
| BO | 16 | no_ReversingVlv | Network Output to close/open Reversing Valve Output. | Read | 0=Close, 1=Open | |
| AO | 131 | no_CoolCtrlOut | Modulating CoolOutput | % | Read | |
| BO | 17 | no_CompDaLolimit | Network Output to limit Compressor Discharge Air Low Limit output | Read | 0=Normal, 1=LoLimit | |
| BO | 18 | no_EconDmprMinCmd | Econ Min Command Auxiliary Output to Econ module. | Read | 0=Disable, 1=Enable | |
| BOmin | 19 | no_FanStart | Network Output to command Fan start | Read | 0=Off, 1=On | |
| AO | 12 | no_FanSpd | Network Output to control Analog Fan speed output | % | Read | |
| BO | 20 | no_FanHiSpd | Network Output to command Fan high speed | Read | 0=Off, 1=On | |
| BO | 21 | no_FanLoSpd | Network Output to command Fan low speed | Read | 0=Off, 1=On | |
| AO | 13 | no_DaTemp | Discharge Air Temp | °F | Read | |
| AO | 15 | no_DaHumidity | Discharge Air Humidity | % | Read | |
| AO | 14 | no_MaTemp | Mixed Air Temp | °F | Read | |
| AO | 57 | no_RaTemp | Return Air Temp | °F | Read | |
| AO | 16 | no_OaTemp | This point is considered for Network point sharing of Outside Air Temp | °F | Read | |
| AO | 17 | no_OaHumidity | This point is considered for Network point sharing of Outside Air Humidity | % | Read | |
| AOmin | 18 | no_SpaceTemp | This point is considered for Network point sharing of Space Temperature | °F | Read | |
| AO | 19 | no_SpaceHumidity | This point is considered for Network point sharing of Space Humidity | % | Read | |
| AO | 20 | no_SpaceCO2 | This point is considered for Network point sharing of Space CO2 | ppm | Read | |
| AO | 66 | no_VOCLevel | This point is considered for Network point sharing of Volatile Organic Compound Level | Read | ||
| BO | 22 | no_EconEn | Network Output to disable/enable Economizer output | Read | 0=Disable, 1=Enable | |
| AO | 22 | no_Fan_RunTimeAccumulate | Outputs the actual run time of Fan. | Read | ||
| AO | 27 | no_HeatStg1_RunTimeAccumulate | Outputs the actual run time of heating stage 1 | Read | ||
| AO | 28 | no_HeatStg2_RunTimeAccumulate | Outputs the actual run time of heating stage 2 | Read | ||
| AO | 29 | no_HeatStg3_RunTimeAccumulate | Outputs the actual run time of heating stage 3 | Read | ||
| AO | 30 | no_HeatCtrl_RunTimeAccumulate | Outputs the actual run time of heating control. | Read | ||
| AO | 132 | no_CoolCtrl_RunTimeAccumulate | Outputs the actual run time of cooling control. | Read | ||
| AO | 31 | no_CompStg1_RunTimeAccumulate | Outputs the actual run time of comp stage 1 | Read | ||
| AO | 32 | no_CompStg2_RunTimeAccumulate | Outputs the actual run time of comp stage 2 | Read | ||
| AO | 58 | no_CompStg3_RunTimeAccumulate | Outputs the actual run time of comp stage 3 | Read | ||
| AO | 252 | no_CoolStg4_RunTimeAccumulate | Outputs the actual run time of Conventional Cool Stage 4 | Read | ||
| AO | 59 | no_ConvHeatTermLdOut | Conventional heating terminal load output | % | Read | |
| AO | 60 | no_AuxHeatTermLdOut | Auxiliary heating terminal load output | % | Read | |
| AO | 61 | no_CompTermLdOut | Compressor terminal load output | % | Read | |
| AO | 85 | no_TermLdOut | Common terminal load output for heating and cooling demand level. | % | Read | |
| AO | 62 | no_EffTUNCOS | Minutes until the next schedule change | Read | ||
| AO | 65 | no_BypassRemTime | Time left before the bypass override ends | Read | ||
| AO | 67 | no_CtrlSpaceTemp | Control Space Temperature output (Only for testing purpose). | °F | Read | |
| BO | 82 | no_RecoveryStatus | This point gives out when the system is in recovery mode. | Read | 0=Normal, 1=Recovery | |
| BO | 83 | no_ModEconEn | Modulating economizer status, display only | Read | 0=Enabled, 1=Disabled | |
| AO | 68 | no_ModEconValue | Modulating economizer value (0 = disabled, 100 = enabled), display only | Read | ||
| BO | 84 | no_DCVEn | Demand control ventilation status, display only | Read | 0=Enabled, 1=Disabled | |
| AO | 69 | no_DCVValue | DCV Value output. 0=DCV disabled, 100= DCV enabled | Read | ||
| BO | 85 | no_MaLoLimActive | Status of mixed air low limit control logic | Read | 0=Inactive, 1=Active | |
| BO | 86 | no_IsFreeCoolAvailable | This point gives the status whether free cooling is available or not. | Read | 0=Not Available, 1=Available | |
| BO | 87 | no_IsEconomizing | This point gives the status whether the control loop is economizing. | Read | 0=False, 1=True | |
| AO | 70 | no_OaDmprPos | This point gives out the outside air damper position based on the control logic | % | Read | |
| AO | 71 | no_CompCurSens | This point gives out the Comp Current Sensor value from the terminal input. | Read | ||
| AO | 72 | no_FanCurSens | This point gives out the Fan Current Sensor value from the terminal input. | Read | ||
| AO | 73 | no_CompDATemp | This point gives out the Comp DA Temperature value from the terminal input. | °F | Read | |
| BO | 94 | no_OccupancySensor | This point is considered for Network point sharing of Occupancy sensor status of terminal | Read | 0=Unoccupied, 1=Occupied | |
| BO | 95 | no_ShutdownState | This point is considered for Network point sharing of shutdown state of terminal | Read | 0=NoOvrd, 1=Shutdown | |
| BO | 96 | no_WSHPEnableState | Water source heat pump enable state from water flow status | Read | 0=Disable, 1=Enable | |
| AO | 97 | no_WSHPEnableValue | Water source heat pump enable value from water flow status | Read | ||
| BO | 98 | no_PurgeState | This point gives current state of Purge Function | Read | 0=Disable, 1=Enable | |
| AO | 77 | no_EffLocalSch | This point is used to display the local schedule current state | Read | ||
| AO | 78 | no_mstpHeaderCrcError | Display mstp header crc error from firmware | Read | ||
| AO | 79 | no_mstpDataCrcErr | Display mstp data crc error from firmware | Read | ||
| AO | 81 | no_Sylk11Pos | This point gives the position feedback from actuator 0-100% | % | Read | |
| AO | 82 | no_Sylk11Cycles | This point shows that how many times the actuator Is cycled from open to close. | Read | ||
| BO | 117 | no_Sylk11Status | Sylk actuator fault code (1 = no error; voltage or stall faults) | Read | ||
| BO | 118 | no_Sylk11Overriden | Sylk actuator overridden externally, display only | Read | 0=False, 1=Override | |
| AO | 84 | no_Sylk11PowerReport | Last commanded actuator move, display only | % | Read | |
| MO | 126 | no_DeltaTConv/Aux/ModHtStg1Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 127 | no_DeltaTConv/Aux/ModHtStg2Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 128 | no_DeltaTConv/Aux/ModHtStg3Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 129 | no_DeltaTCompHt/Cl/ConvClStg1Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 130 | no_DeltaTCompHt/Cl/ConvClStg2Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 131 | no_DeltaTCompHt/Cl/ConvClStg3Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 213 | no_DeltaTCompHt/Cl/ConvClStg4Alarm | Display the network Point to display the Delta T Alarm Enumeration | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| MO | 132 | no_DeltaTModClAlarm(Fut) | Display the network Point to display the Delta T Alarm Enumeration (Future) | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| AO | 130 | no_DeltaTValue | The actual DeltaT value measured by real time (MAT-DAT) | °F | Read | |
| MO | 134 | no_DeltaTAlarmStatus | The actual DeltaT Alarm Status shown in HMI, Supervisor, mobile app. | Read | 1=Green, 2=Orange, 3=Red, 4=DisablebyCtrlValue/ MinDly, 5=SensorNotAvail, 6=DisableByEqAvail/ HMIConfigServ, 7=DisableByMAOALimits | |
| BOmin | 102 | no_GenericAlarm | Any alarm active on the thermostat | Read | 0=False, 1=True | |
| MO | 247 | no_DRStatus | Display user a Network output indicating whether device is in Demand Response mode | Read | 1=Inactive, 2=Active | |
| MO | 185 | no_ModEconStatus | Display the network Point to display the internal Economizer Status. | Read | 1=Inactive, 2=Active, 3=OATUnAvail, 4=OAHUnAvail, 5=RATUnAvail, 6=RAHUnAvail, 7=MATUnAvail | |
| BO | 128 | no_PckEconFault | Display the network Point to display the External Economizer Point | Read | 0=Ok, 1=Faulty | |
| MO | 112 | no_Sylk11CalibrStatus | Display the network Point to display Sylk Actuator calibration Status | Read | 1=UnCalibrated, 2=CalibrIsInProgress, 3=Calibrated | |
| AO | 87 | no_Sylk11CalibrMax | Displays the Actuator MaxPosition after Calibration (0-100%) | % | Read | |
| AO | 88 | no_Sylk11CalibrMin | Displays the Actuator MinPosition after Calibration (0-100%) | % | Read | |
| BO | 501 | no_ExhaustFan1Status | Display the network Point to display the Exhaust Fan1 Command | Read | 0=Off, 1=On | |
| BO | 502 | no_ExhaustFan2Status | Display the network Point to display the Exhaust Fan2 Command | Read | 0=Off, 1=On | |
| BO | 505 | no_HWValveStatus | Display the network Point to display the FCU HW On/Off Valve Status | Read | 0=Off, 1=On | |
| BO | 506 | no_CWValveStatus | Display the network Point to display the FCU CW On/Off Valve Status | Read | 0=Off, 1=On | |
| BO | 64 | AlarmPriority_SupplyFan | Supply Fan Status Mismatch Alarm & Priority | Read | ||
| BO | 65 | AlarmPriority_SpaceFreezeProtect | Space temperature freeze protection alarm & Priority | Read | ||
| BO | 66 | AlarmPriority_WaterFlwPrf | Proof of water flow alarm & Priority | Read | ||
| AI | 12 | Alarm_UI_SpcTemp | UI Space Temperature fault detection point | Read | ||
| AI | 2 | Alarm_InternalHumSens | Internal Humidity Sensor input. | Read | ||
| BO | 68 | AlarmPriority_SpcTempHI_Lolimit | Space Air Temperature High/ low Limit Alarm | Read | ||
| BO | 100 | AlarmPriority_Co2lvlHighlimit | CO2 Level High limit exceed Alarm | Read | ||
| BO | 63 | Alarm_StPtOutOfRangeAlm | Setpoint Configurations Out of Range Alarm | Read | ||
| BI | 3 | Alarm_UI_OccSens | Occupancy Sensor Physical Input | Read | ||
| BO | 69 | AlarmPriority_OccSensFault | Occupancy Sensor Alarm Priority | Read | ||
| BI | 4 | Alarm_UI_DirtyFilter | Dirty Filter Physical Input | Read | ||
| BO | 70 | AlarmPriority_DirtyFiltFault | Dirty Filter Physical Input Alarm Priority | Read | ||
| BI | 5 | Alarm_UI_AirFlwSts | Air Flow Status Physical Input | Read | ||
| BO | 71 | AlarmPriority_AirFlwFault | Air Flow Status Physical Input Alarm Priority | Read | ||
| BI | 6 | Alarm_UI_Shutdown | Shutdown Physical Input | Read | ||
| BO | 72 | AlarmPriority_ShutdownFault | Shutdown Physical Input Alarm Priority | Read | ||
| AI | 4 | Alarm_UI_MATemp | MA Temperature Physical Input | Read | ||
| MO | 9 | AlarmPriority_MATempAlarm_Fault | MA Temperature Physical Input Alarm Priority | Read | ||
| AI | 5 | Alarm_UI_OATemp | OA Temperature Physical Input Alarm | Read | ||
| MO | 10 | AlarmPriority_OATempAlarm_Fault | OA Temperature Physical Input Alarm Priority | Read | ||
| AI | 6 | Alarm_UI_DATemp | Discharge Air Temperature Physical Input | Read | ||
| MO | 11 | AlarmPriority_DATempAlarm_Fault | Discharge Air Temperature Physical Input Alarm Priority | Read | ||
| AI | 18 | Alarm_UI_RATemp | Return Air Temperature Physical Input | Read | ||
| MO | 110 | AlarmPriority_RATempAlarm_Fault | Return Air Temperature Physical Input Alarm Priority | Read | ||
| AI | 7 | Alarm_UI_CO2Lvl | CO2 Level Physical Input | Read | ||
| BI | 7 | Alarm_UI_WtrFlwSts | Water Flow Status Physical Input | Read | ||
| BO | 73 | AlarmPriority_WtrFlwFault | Water Flow Status Physical Input Alarm Priority | Read | ||
| AI | 14 | Alarm_UI_CompDASens | Comp Discharge Air Temperature Physical Input | Read | ||
| BO | 88 | AlarmPriority_DirtyFilter | Dirty Filter Alarm | Read | ||
| MO | 24 | Alarm_SylkCommFail | Sylk communication failure; shows which sensor or many failed | Read | ||
| AI | 15 | Alarm_UI_HeatPumpFreq | Heat pump fault input. | Read | ||
| MO | 23 | AlarmPriority_HeatPumpFreqFault | HeatPumpFreq Physical Input Alarm Priority | Read | ||
| BO | 91 | AlarmPriority_HeatPumpFail | Heatpump failure alarm | Read | ||
| BO | 92 | AlarmPriority_UnknownTime | Unknown Time alarm from Firmware. | Read | ||
| BO | 93 | AlarmPriority_ProximitySensAlarm | Internal proximity sensor alarm from Firmware. | Read | ||
| BO | 99 | AlarmPriority_PckEcon_Fault | Packaged economizer fault Input alarm | Read | ||
| BO | 101 | AlarmPriority_WindowOpen | Alarm occurs when the window is Open | Read | ||
| BO | 121 | AlarmPriority_Econ_FDD_NEWIS | Alarm occurs when Economizer not economizing when it should (NEWIS) | Read | ||
| BO | 123 | AlarmPriority_Econ_FDD_EWISN | Alarm occurs when Economizer economizing when it should not (EWIS) (NEWIS) | Read | ||
| BO | 122 | AlarmPriority_Econ_FDD_DNM | Alarm occurs when Economizer damper not modulating | Read | ||
| BO | 124 | AlarmPriority_Econ_FDD_EOA | Alarm occurs when Economizer bring in excess outdoor air | Read | ||
| BO | 125 | AlarmPriority_EconomizerFailure | Old economizer failure alarm, kept for backward compatibility | Read | ||
| BO | 109 | AlarmPriority_Sylk11ActuatorFail | Sylk actuator failure alarm (voltage or stall) | Read | ||
| BO | 126 | AlarmPriority_CoilFreezeProtAlm | Mixed air below the freeze limit; outdoor damper closes or goes to minimum | Read | ||
| MO | 133 | AlarmPriority_DeltaTAlarmStatus | Delta-T alarm priority: 1 normal, 2 medium, 3 high | Read | ||
| MO | 187 | AlarmPriority_IntEconomizerFailure | Internal economizer damper fault (stuck, unplugged or disconnected) | Read | ||
| AO | 75 | OaTemp_Display | Outdoor temperature, local sensor or internet value, display only | Read | ||
| AO | 76 | OaHum_Display | Outdoor humidity, local sensor or internet value, display only | Read | ||
| CAL | 3 | Calendar1 | Referred to Enum Schedule | Write | ||
| CAL | 4 | Calendar2 | Write | |||
| CAL | 5 | Calendar3 | Write | |||
| CAL | 6 | Calendar4 | Write | |||
| CAL | 7 | Calendar5 | Write | |||
| CAL | 8 | Calendar6 | Write | |||
| CAL | 9 | Calendar7 | Write | |||
| CAL | 10 | Calendar8 | Write | |||
| CAL | 11 | Calendar9 | Write | |||
| CAL | 12 | Calendar10 | Write | |||
| SCH | 2 | EnumSchedule | Main weekly occupancy schedule | Write | ||
| SCH | 3 | PurgeSchedule | Purge Schedule. 0-PurgeOff, 1-PurgeOn. Default is Purge Off for all 5 days. | Write |
No points match these filters.
Object ID lookup: Honeywell TC500A Commercial Thermostat point IDs by name
AI8ni_UI1AI9ni_UI2AI10ni_UIO1AO64no_UIO1AI11ni_UIO2AO63no_UIO2BO74no_DO1BO75no_DO2BO76no_DO3BO77no_DO4BO78no_DO5BO79no_DO6BO80no_DO7BO81no_DO8MV24Cfg_UI1AV293Cfg_UI1_ExtMV25Cfg_UI2AV294Cfg_UI2_ExtMV26Cfg_UIO1AV295Cfg_UIO1_ExtMV27Cfg_UIO2AV296Cfg_UIO2_ExtMV28Cfg_DO1MV29Cfg_DO2MV30Cfg_DO3MV31Cfg_DO4MV32Cfg_DO5MV33Cfg_DO6MV34Cfg_DO7MV35Cfg_DO8BV31Cfg_OccSensCharBV32Cfg_DirtyFilterCharBV33Cfg_AirFlwStsCharBV34Cfg_ShutdownCharMV501Cfg_MASensChar1MV502Cfg_OASensChar1MV503Cfg_DASensChar1BV180Cfg_RASensCharMV504Cfg_RASensChar1MV372CFg_SpcSensCharBV155Cfg_FiltPresCharAV220Cfg_CompCurSensMaxAmpsAV221Cfg_FanCurSensMaxAmpsBV175Cfg_WindowOpenCharBV383Cfg_WaterFlwStsCharAV223no_SylkAddr2TempAV224no_SylkAddr2HumAV225no_SylkAddr2CO2AV226no_SylkAddr3TempAV227no_SylkAddr4TempAV228no_SylkAddr5TempAV229no_SylkAddr6TempAV230no_SylkAddr6HumAV231no_SylkAddr8TempAV232no_SylkAddr8HumAV233no_SylkAddr9TempAV234no_SylkAddr9HumAV235no_SylkAddr10TempAV236no_SylkAddr10HumMV92no_Sylk11StatusAV237no_SylkAddr11TempAV773no_SylkAddr12HumAI16InternalTempSensAI17InternalHumSensMV89Cfg_FanModeAV39Cfg_FanRunOnCoolDelayAV40Cfg_FanRunOnHeatDelayBV10Cfg_FanOnHeatAV253Cfg_FanCirculate_FanOnTimePercentMV15Cfg_FanSpeed_CmprCoolSingleMV16Cfg_FanSpeed_CmprCoolMultiMV17Cfg_FanSpeed_HeatSingleMV90Cfg_FanSpeed_PurgeModeAV83Cfg_FanMinSpeed_ModHeatAV84Cfg_FanMaxSpeed_ModHeatAV64Cfg_FanSpeed_Speed1AV65Cfg_FanSpeed_Speed2AV66Cfg_FanSpeed_Speed3AV67Cfg_FanSpeed_Speed4AV68Cfg_FanSpeed_Speed5AV69Cfg_FanSpeed_Speed6MV367Cfg_FanSpeed_EconomizerModeMV370Cfg_MultipleFanSpeed_ModHeatMV371Cfg_MultipleFanSpeed_ModCoolAV1468Cfg_VarSpeedFan_CoolMinSpeedAV1469Cfg_VarSpeedFan_CoolMaxSpeedAV1473Cfg_VarSpeedFan_HeatMinSpeedAV1474Cfg_VarSpeedFan_HeatMaxSpeedAV1472Cfg_VarSpeedFan_PurgeSpeedAV1470Cfg_VarSpeedFan_VentSpeedMV373Cfg_VarSpeedFanTypeAV1483Cfg_Econ_EXH1SpAV1484Cfg_Econ_EXH2SpAV1485Cfg_Econ_EXH1SpLAV1486Cfg_Econ_EXH1SpHAV1487Cfg_Econ_EXH2SpMAV1488Cfg_Econ_EXH2SpLAV1489Cfg_Econ_EXH2SpHAV1490Cfg_Econ_EXH2SpMMV575Cfg_FanCoilTypeMV576Cfg_FanCoilHtgTypeMV577Cfg_FanCoilClgTypeMV578Cfg_FanCoilHtgDriveTypeMV579Cfg_FanCoilClgDriveTypeAV1721Cfg_FanCoilHtgDriveTimeAV1722Cfg_FanCoilClgDriveTimeMV580Cfg_FanCoilTwoPipeSingleCoilAV1723Cfg_FanCoilSupTempHtgSpAV1731Cfg_FanCoilSupTempHtgOffsetSpAV1724Cfg_FanCoilSupTempClgSpAV1732Cfg_FanCoilSupTempClgOffsetSpMV581Cfg_FanCoilTwoSpeedTypeMV582Cfg_FanCoilThreeSpeedtypeMV583Cfg_FanCoilManualSpeedSelBV454Cfg_FanCoilDATSpEnSwitchBV462Cfg_FanCoilClgFloatingSyncEnBV453Cfg_FanCoilHtgFloatingSyncEnAV1733Cfg_FanCoilDATCtr_CoolTrAV1734Cfg_FanCoilDATCtr_CoolItAV1735Cfg_FanCoilDATCtr_CoolDrAV1736Cfg_FanCoilDATCtr_HeatTrAV1737Cfg_FanCoilDATCtr_HeatItAV1738Cfg_FanCoilDATCtr_HeatDrMV585Cfg_FanCoilTwoSpeedVentModeMV586Cfg_FanCoilThreeSpeedVentModeBV455Cfg_FanCoilDrainPanSrCharBV458Cfg_FanCoilOnOffHtgVlvCharBV459Cfg_FanCoilOnOffClgVlvCharMV366Cfg_Equip_CoolTypeAV41Cfg_Cool_TrAV42Cfg_Cool_ItAV43Cfg_Cool_DtAV44Cfg_Cool_CPHAV45Cfg_Cool_MinOnTimeAV82Cfg_Cool_MinOffTimeAV46Cfg_Cool_CoolLockoutSpAV47Cfg_Cool_DischLoLimSpAV1461Cfg_Cool_ModClEnMinOutBV377Cfg_Mod_StgCl1EnAV1476Cfg_ModCoolMin_OutputAV1478Cfg_ModCoolMax_OutputBV385Cfg_ModCoolInitialAtFullOpMV374Cfg_ModCoolFullOpCycleTimeBV381Cfg_ModCoolActionMV21Cfg_Equip_HeatTypeAV54Cfg_Heat_TrAV55Cfg_Heat_ItAV56Cfg_Heat_DtAV57Cfg_Heat_CPHAV58Cfg_Heat_MinOnTimeAV59Cfg_Heat_MinOffTimeAV60Cfg_Heat_HeatLockoutSpAV61Cfg_Heat_DischHiLimSpAV96Cfg_Heat_ModHtEnMinOutBV35Cfg_Mod_StgHt1EnMV87Cfg_Heat_FuelTypeAV1475Cfg_ModHeatMin_OutputAV1477Cfg_ModHeatMax_OutputBV380Cfg_ModHeatActionAV48Cfg_Dehum_SpaceRHHighLimitBV12Cfg_Dehum_MinOnTimeOpEnAV49Cfg_Dehum_MinOnTimeAV98Cfg_Dehum_MinOnDelayAV62Cfg_Hum_SpaceRHLowLimitAV99Cfg_Hum_MinOnDelayBV13Cfg_HeatPmp_CngOvrRelayTypeAV50Cfg_HeatPmp_AuxHeatLockoutSpAV51Cfg_HeatPmp_CompLockoutSpAV52Cfg_HeatPmp_AuxHeatDroopAV53Cfg_HeatPmp_AuxHeatRampFactorBV14Cfg_HeatPmp_ComfortModeAV215Cfg_HeatPmp_UpStgTmrBV179Cfg_CO2_SensorTypeAV349Cfg_CO2_SensorZeroAV350Cfg_CO2_SensorSpanBV181Cfg_CO2OutputMV84Cfg_Econ_FreeCoolSelectAV196Cfg_Econ_DrybulbSpMV94Cfg_Econ_EnthCurveSelAV320Cfg_Econ_MinDamperPosAV321Cfg_Econ_MinDamperPosLowAV322Cfg_Econ_MinDamperPosMedMV96Cfg_Econ_ShutdownDamperPosMV95Cfg_Econ_FreezeProtDamperPosAV201Cfg_Econ_MaTempSetPtAV204Cfg_Econ_MaLoTempSetPtAV327Cfg_Econ_MechCoolingDelayAV1466Cfg_MaTThresholdValueAV1467Cfg_DmprDelayTimeAV222Cfg_Filt_HiLimitBV36Cfg_Stdby_OccStsMV9Cfg_Control_MainSensorAV14Cfg_Control_PowerupDelayMV10Cfg_Control_SmokeModeMV130Cfg_ZoneMultiSens_ControlAV33Cfg_ZoneMultiSens_Sens1_WtAV34Cfg_ZoneMultiSens_Sens2_WtAV35Cfg_ZoneMultiSens_Sens3_WtAV36Cfg_ZoneMultiSens_Sens4_WtAV37Cfg_ZoneMultiSens_Sens5_WtAV219Cfg_ZoneMultiSens_Sens6_WtMV77Cfg_ZoneMultiHumSens_ControlAV181Cfg_ZoneMultiSens_HumSens1_WtAV180Cfg_ZoneMultiSens_HumSens2_WtAV218Cfg_ZoneMultiSens_HumSens6_WtAV4Cfg_Setpoints_OccCoolSpAV5Cfg_Setpoints_StbyCoolSpAV6Cfg_Setpoints_UnOccCoolSpAV7Cfg_Setpoints_OccHeatSpAV8Cfg_Setpoints_StbyHeatSpAV9Cfg_Setpoints_UnOccHeatSpAV18Cfg_Recovery_MaxCoolRampRateAV16Cfg_Recovery_MinCoolRampRateAV17Cfg_Recovery_MaxCoolRampTempAV15Cfg_Recovery_MinCoolRampTempAV22Cfg_Recovery_MaxHeatRampRateAV20Cfg_Recovery_MinHeatRampRateAV21Cfg_Recovery_MaxHeatRampTempAV19Cfg_Recovery_MinHeatRampTempAV38Cfg_DemandLimCtl_TempDiffSpBV157Cfg_Thermostat_SystemChangeOverMV36Cfg_Thermostat_SystemConfigAV10Cfg_Thermostat_BypOverrideTimeAV12Cfg_Thermostat_MinCoolSpAV13Cfg_Thermostat_MaxHeatSpAV101Cfg_Thermostat_DeadbandAV257Cfg_Thermostat_HtAdjStPtAV256Cfg_Thermostat_ClAdjStPtAV102Cfg_Thermostat_TempOffSpLimitAV23Cfg_LocalSensCalOffset_TempAV103Cfg_LocalSensCalOffset_HumAV24Cfg_SylkCalOffset_SylkBus2TempAV25Cfg_SylkCalOffset_SylkBus2RHAV100Cfg_SylkCalOffset_SylkBus2CO2AV26Cfg_SylkCalOffset_SylkBus3TempAV27Cfg_SylkCalOffset_SylkBus4TempAV28Cfg_SylkCalOffset_SylkBus5TempAV216Cfg_SylkCalOffset_SylkBus6TempAV217Cfg_SylkCalOffset_SylkBus6RHAV29Cfg_SylkCalOffset_SylkBus8TempAV30Cfg_SylkCalOffset_SylkBus8RHAV137Cfg_SylkCalOffset_SylkBus9TempAV214Cfg_SylkCalOffset_SylkBus9RHAV31Cfg_SylkCalOffset_SylkBus10TempAV32Cfg_SylkCalOffset_SylkBus10RHAV138Cfg_SylkCalOffset_SylkBus12TempAV771Cfg_SylkCalOffset_SylkBus12RHAV185Cfg_UISensCalOffset_DATempAV186Cfg_UISensCalOffset_OATempAV187Cfg_UISensCalOffset_MATempAV427Cfg_UISensCalOffset_RATempAV1464Cfg_UISensCalOffset_SpcTempAV188Cfg_UISensCalOffset_CO2LvlMV85Cfg_Sylk_SylkBus2EnMV86Cfg_Sylk_SylkBus6EnBV151Cfg_Sylk_SylkBus8EnBV152Cfg_Sylk_SylkBus9EnBV153Cfg_Sylk_SylkBus10EnBV178Cfg_Sylk_SylkBus11EnBV154Cfg_Sylk_SylkBus12EnAV301Cfg_SylkBus11TravelTimeAV331Cfg_SylkBus11TestmodeMV135Sylk11_EconFaultAlarmBV246Cfg_StagedHeatEnAV955Cfg_HeatStage1MinAV956Cfg_HeatStage1MaxAV957Cfg_HeatStage1DelayAV958Cfg_HeatStage2MinAV959Cfg_HeatStage2MaxAV960Cfg_HeatStage2DelayAV961Cfg_HeatStage3MinAV962Cfg_HeatStage3MaxAV963Cfg_HeatStage3DelayBV247Cfg_StagedCoolEnAV964Cfg_CoolStage1MinAV965Cfg_CoolStage1MaxAV966Cfg_CoolStage1DelayAV967Cfg_CoolStage2MinAV968Cfg_CoolStage2MaxAV969Cfg_CoolStage2DelayAV970Cfg_CoolStage3MinAV971Cfg_CoolStage3MaxAV972Cfg_CoolStage3DelayAV1739Cfg_CoolStage4MinAV1740Cfg_CoolStage4MaxAV1741Cfg_CoolStage4DelayBV248Cfg_ComprHeatEnAV973Cfg_ComprHeatStage1MinAV974Cfg_ComprHeatStage1MaxAV975Cfg_ComprHeatStage1DelayAV976Cfg_ComprHeatStage2MinAV977Cfg_ComprHeatStage2MaxAV978Cfg_ComprHeatStage2DelayAV979Cfg_ComprHeat3MinAV980Cfg_ComprHeat3MaxAV981Cfg_ComprHeat3DelayBV249Cfg_ModHeatEnAV986Cfg_ModHeatMinAV987Cfg_ModHeatMaxAV988Cfg_ModHeatDelayAV989Cfg_ModHeatMinOuputBV250Cfg_ModulatingCoolEnAV982Cfg_ModCoolMinAV983Cfg_ModCoolMaxAV984Cfg_ModCoolDelayAV985Cfg_ModCoolMinOuputAV990Cfg_StagedHeatMATempLimitMinAV991Cfg_StagedHeatMATempLimitMaxBV134Cfg_StagedHeatMARHLimitEnAV992Cfg_StagedHeatMARHLimitMinAV993Cfg_StagedHeatMARHLimitMaxAV994Cfg_StagedHeatOATempLimitMinAV995Cfg_StagedHeatOATempLimitMaxAV996Cfg_StagedHeatOARHLimitMinAV997Cfg_StagedHeatOARHLimitMaxAV998Cfg_StagedCoolMATempLimitMinAV999Cfg_StagedCoolMATempLimitMaxAV1000Cfg_StagedCoolMARHLimitMinAV1001Cfg_StagedCoolMARHLimitMaxAV1002Cfg_StagedCoolOATempLimitMinAV1003Cfg_StagedCoolOATempLimitMaxAV1004Cfg_StagedCoolOARHLimitMinAV1005Cfg_StagedCoolOARHLimitMaxAV1022Cfg_CmprHeatMATempLimitMinAV1023Cfg_CmprHeatMATempLimitMaxBV150Cfg_CmprHeatMARHLimitEnAV1024Cfg_CmprHeatMARHLimitMinAV1025Cfg_CmprHeatMARHLimitMaxAV1026Cfg_CmprHeatOATempLimitMinAV1027Cfg_CmprHeatOATempLimitMaxAV1028Cfg_CmprHeatOARHLimitMinAV1029Cfg_CmprHeatOARHLimitMaxMV141Cfg_ModHeatMATempLimitEnAV1006Cfg_ModHeatMATempLimitMinAV1007Cfg_ModHeatMATempLimitMaxBV142Cfg_ModHeatMARHLimitEnAV1008Cfg_ModHeatMARHLimitMinAV1009Cfg_ModHeatMARHLimitMaxBV143Cfg_ModHeatOATempLimitEnAV1010Cfg_ModHeatOATempLimitMinAV1011Cfg_ModHeatOATempLimitMaxAV1012Cfg_ModHeatOARHLimitMinAV1013Cfg_ModHeatOARHLimitMaxBV145Cfg_ModCoolMATempLimitEnAV1014Cfg_ModCoolMATempLimitMinAV1015Cfg_ModCoolMATempLimitMaxBV146Cfg_ModCoolMARHLimitEnAV1016Cfg_ModCoolMARHLimitMinAV1017Cfg_ModCoolMARHLimitMaxAV1018Cfg_ModCoolOATempLimitMinAV1019Cfg_ModCoolOATempLimitMaxAV1020Cfg_ModCoolOARHLimitMinAV1021Cfg_ModCoolOARHLimitMaxBV251Cfg_RunWithHumBV252Cfg_RunWithDehumAV1047Cfg_DRHiOffsetAV1465Cfg_DRMoOffsetAV1048Cfg_DRLoOffsetMV258Cfg_DRDefaultOptionAV1049Cfg_DRDefaultOffsetAV1050Cfg_DRDefaultHtSpAV1051Cfg_DRDefaultClSpAV1052Cfg_DRMaxClSpAV205Cfg_DCV_VentMinPosHighAV206Cfg_DCV_VentMaxPosHighAV504Cfg_DCV_VentMinPosMidAV311Cfg_DCV_VentMaxPosMidAV207Cfg_DCV_VentMinPosLowAV208Cfg_DCV_VentMaxPosLowAV209Cfg_DCV_CO2SetPtAV213Cfg_DCV_CO2DeadbandBV259Cfg_Co2Output_OverrideBV258Cfg_PurOutputBV172Cfg_Purge_CtrlEnAV334Cfg_Purge_PosMV91Cfg_WindowOpnSetngAV297Cfg_WindowOpnDelayAV291Cfg_CO2Alarm_LvlHighLimAV192Cfg_Alarm_SupplyFanAlarmConfigAV193Cfg_Alarm_TempSensAlarmConfigMO99Gui_Alarm_SylkActuatorFailMV574Cfg_AlarmConfig_CHWDrainPanSrAlarmAV254Cfg_SpcAlarm_TempHighLimAV332Cfg_DaTAlarm_TempHighLimAV333Cfg_DATAlarmTempLowLimBV1ni_BypassStateAV2ni_BypassValueBV2ni_DemandLimitControlEnAV89ni_OutdoorTempAV194ni_OutdoorHumAV339ni_OutdoorEnthalpyAV340ni_OutdoorDewpointAV341ni_RaEnthalpyAV342ni_RaDewpointBV390ni_ServiceExhaustFan1CmdBV391ni_ServiceExhaustFan2CmdBV4ni_ShutdownStateBV5ni_SmokeMonitorstateAV81ni_SpaceCO2AV80ni_SpaceRHAV104ni_SpaceTempBV25ni_WSHPEnableStateAV88ni_WSHPEnableValueBV158ni_OccupancySensorMV3ni_ApplicationModeBV6ni_ServiceModeEnMV23ni_ServiceFanAV85ni_ServiceFanSpeedBV16ni_ServiceCompStage1BV17ni_ServiceCompStage2BV18ni_ServiceCompStage3BV463Ni_ServiceCoolStage4BV19ni_ServiceHeatStage1BV20ni_ServiceHeatStage2BV21ni_ServiceHeatStage3AV86ni_ServiceHeatCtrlAV1152ni_ServiceCoolCtrlBV22ni_ServiceRevVlvCmdBV23ni_ServiceSimpleDehCmdBV24ni_ServiceSimpleHumCmdBV141ni_ServiceEconomizerCmdAV212ni_ServiceOaDmprCtrlBV220ni_ServiceCO2OutputCmdAV859ni_ServicePurgeOP2-10VAV195ni_DeviceLockAV338ni_SylkBus11CmdBV174ni_mstpClearErrAV238ni_SylkAddr2TempAV239ni_SylkAddr2HumAV240ni_SylkAddr2CO2AV241ni_SylkAddr3TempAV242ni_SylkAddr4TempAV243ni_SylkAddr5TempAV244ni_SylkAddr6TempAV245ni_SylkAddr6HumAV248ni_SylkAddr9TempAV249ni_SylkAddr9HumAV250ni_SylkAddr10TempAV251ni_SylkAddr10HumAV246ni_SylkAddr12TempAV772ni_SylkAddr12HumBV159Cfg_NetOccSenFailDetEnAV262Cfg_NetOccSenFailFalbckBV160Cfg_NetOccSenFailFxdValAV263Cfg_NetOccSenFailDetDlyBV163Cfg_NetOATFailDetEnAV270Cfg_NetOATFailFalbckAV272Cfg_NetOATFailFxdValAV271Cfg_NetOATFailDetDlyBV162Cfg_NetOAHumFailDetEnAV267Cfg_NetOAHumFailFalbckAV269Cfg_NetOAHumFailFxdValAV268Cfg_NetOAHumFailDetDlyBV164Cfg_NetShtdwnFailDetEnAV273Cfg_NetShtdwnFailFalbckBV165Cfg_NetShtdwnFailFxdValAV274Cfg_NetShtdwnFailDetDlyBV166Cfg_NetSpceCO2FailDetEnAV275Cfg_NetSpceCO2FailFalbckAV277Cfg_NetSpceCO2FailFxdValAV276Cfg_NetSpceCO2FailDetDlyBV167Cfg_NetSpceRHFailDetEnAV278Cfg_NetSpceRHFailFalbckAV280Cfg_NetSpceRHFailFxdValAV279Cfg_NetSpceRHFailDetDlyBV168Cfg_NetSpceTmpFailDetEnAV281Cfg_NetSpceTmpFailFalbckAV283Cfg_NetSpceTmpFailFxdValAV282Cfg_NetSpceTmpFailDetDlyBV169Cfg_NetWSHPEnStFailDetEnAV284Cfg_NetWSHPEnStFailFalbckBV170Cfg_NetWSHPEnStFailFxdValAV285Cfg_NetWSHPEnStFailDetDlyBV171Cfg_NetWSHPEnValFailDetEnAV286Cfg_NetWSHPEnValFailFalbckAV287Cfg_NetWSHPEnValFailFxdValAV288Cfg_NetWSHPEnValFailDetDlyMV2no_EffOccSensStateBO1no_BypassStateAO1no_BypassValueBO3no_OccupancyStateBO4no_SystemDisableBO5no_ServiceMdAO2no_EffDlcShiftAO3no_EffHeatSpAO4no_EffCoolSpAO5no_EffSpAO6no_EffAuxHeatSetpointBO7no_IsFanOnlyBO8no_DehumActiveBO9no_HumActiveBO10no_IsHeatDisableBO11no_IsAuxHeatDisableBO12no_IsCompHeatDisableAO7no_ActiveHeatStagesAO8no_ActiveAuxHeatStagesAO9no_HeatCtrlOutAO10no_ActiveCompHeatStagesBO13no_DaHilimitBO14no_CompDaHilimitBO15no_IsCoolDisableAO11no_ActiveCoolStagesBO16no_ReversingVlvAO131no_CoolCtrlOutBO17no_CompDaLolimitBO18no_EconDmprMinCmdBO19no_FanStartAO12no_FanSpdBO20no_FanHiSpdBO21no_FanLoSpdAO13no_DaTempAO15no_DaHumidityAO14no_MaTempAO57no_RaTempAO16no_OaTempAO17no_OaHumidityAO18no_SpaceTempAO19no_SpaceHumidityAO20no_SpaceCO2AO66no_VOCLevelBO22no_EconEnAO22no_Fan_RunTimeAccumulateAO27no_HeatStg1_RunTimeAccumulateAO28no_HeatStg2_RunTimeAccumulateAO29no_HeatStg3_RunTimeAccumulateAO30no_HeatCtrl_RunTimeAccumulateAO132no_CoolCtrl_RunTimeAccumulateAO31no_CompStg1_RunTimeAccumulateAO32no_CompStg2_RunTimeAccumulateAO58no_CompStg3_RunTimeAccumulateAO252no_CoolStg4_RunTimeAccumulateAO59no_ConvHeatTermLdOutAO60no_AuxHeatTermLdOutAO61no_CompTermLdOutAO85no_TermLdOutAO62no_EffTUNCOSAO65no_BypassRemTimeAO67no_CtrlSpaceTempBO82no_RecoveryStatusBO83no_ModEconEnAO68no_ModEconValueBO84no_DCVEnAO69no_DCVValueBO85no_MaLoLimActiveBO86no_IsFreeCoolAvailableBO87no_IsEconomizingAO70no_OaDmprPosAO71no_CompCurSensAO72no_FanCurSensAO73no_CompDATempBO94no_OccupancySensorBO95no_ShutdownStateBO96no_WSHPEnableStateAO97no_WSHPEnableValueBO98no_PurgeStateAO77no_EffLocalSchAO78no_mstpHeaderCrcErrorAO79no_mstpDataCrcErrAO81no_Sylk11PosAO82no_Sylk11CyclesBO117no_Sylk11StatusBO118no_Sylk11OverridenAO84no_Sylk11PowerReportMO126no_DeltaTConv/Aux/ModHtStg1AlarmMO127no_DeltaTConv/Aux/ModHtStg2AlarmMO128no_DeltaTConv/Aux/ModHtStg3AlarmMO129no_DeltaTCompHt/Cl/ConvClStg1AlarmMO130no_DeltaTCompHt/Cl/ConvClStg2AlarmMO131no_DeltaTCompHt/Cl/ConvClStg3AlarmMO213no_DeltaTCompHt/Cl/ConvClStg4AlarmMO132no_DeltaTModClAlarm(Fut)AO130no_DeltaTValueMO134no_DeltaTAlarmStatusBO102no_GenericAlarmMO247no_DRStatusMO185no_ModEconStatusBO128no_PckEconFaultMO112no_Sylk11CalibrStatusAO87no_Sylk11CalibrMaxAO88no_Sylk11CalibrMinBO501no_ExhaustFan1StatusBO502no_ExhaustFan2StatusBO505no_HWValveStatusBO506no_CWValveStatusBO64AlarmPriority_SupplyFanBO65AlarmPriority_SpaceFreezeProtectBO66AlarmPriority_WaterFlwPrfAI12Alarm_UI_SpcTempAI2Alarm_InternalHumSensBO68AlarmPriority_SpcTempHI_LolimitBO100AlarmPriority_Co2lvlHighlimitBO63Alarm_StPtOutOfRangeAlmBI3Alarm_UI_OccSensBO69AlarmPriority_OccSensFaultBI4Alarm_UI_DirtyFilterBO70AlarmPriority_DirtyFiltFaultBI5Alarm_UI_AirFlwStsBO71AlarmPriority_AirFlwFaultBI6Alarm_UI_ShutdownBO72AlarmPriority_ShutdownFaultAI4Alarm_UI_MATempMO9AlarmPriority_MATempAlarm_FaultAI5Alarm_UI_OATempMO10AlarmPriority_OATempAlarm_FaultAI6Alarm_UI_DATempMO11AlarmPriority_DATempAlarm_FaultAI18Alarm_UI_RATempMO110AlarmPriority_RATempAlarm_FaultAI7Alarm_UI_CO2LvlBI7Alarm_UI_WtrFlwStsBO73AlarmPriority_WtrFlwFaultAI14Alarm_UI_CompDASensBO88AlarmPriority_DirtyFilterMO24Alarm_SylkCommFailAI15Alarm_UI_HeatPumpFreqMO23AlarmPriority_HeatPumpFreqFaultBO91AlarmPriority_HeatPumpFailBO92AlarmPriority_UnknownTimeBO93AlarmPriority_ProximitySensAlarmBO99AlarmPriority_PckEcon_FaultBO101AlarmPriority_WindowOpenBO121AlarmPriority_Econ_FDD_NEWISBO123AlarmPriority_Econ_FDD_EWISNBO122AlarmPriority_Econ_FDD_DNMBO124AlarmPriority_Econ_FDD_EOABO125AlarmPriority_EconomizerFailureBO109AlarmPriority_Sylk11ActuatorFailBO126AlarmPriority_CoilFreezeProtAlmMO133AlarmPriority_DeltaTAlarmStatusMO187AlarmPriority_IntEconomizerFailureAO75OaTemp_DisplayAO76OaHum_DisplayCAL3Calendar1CAL4Calendar2CAL5Calendar3CAL6Calendar4CAL7Calendar5CAL8Calendar6CAL9Calendar7CAL10Calendar8CAL11Calendar9CAL12Calendar10SCH2EnumScheduleSCH3PurgeSchedule
Integration notes
- Access comes from the Access column or the table notes ("All points are writable" / "read-only").
- The guide gives the same type and instance to two different objects in 28 places (for example MV 20 is both Cfg_Heat_HeatType and no_EffOccState, MV 8 both Cfg_Thermostat_SysSwitch and no_ApplicationCommandMode). Both objects of each clashing pair are left out until a device confirms which is right.
- The short 'basic setup' table at the front of the guide has its type and instance columns shifted against the names; the detailed chapter tables are used instead.
- Cfg_Econ_MinDamperPos (AV 320) and the Low/Med variants (AV 321/322) are described per fan-speed count in the guide; each is listed once.
- 'Boolean Value' in the guide is listed as BV. Objects shown on several pages are listed once.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TC500A Commercial Thermostat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Honeywell TC500A Commercial Thermostat
How many BACnet points does the Honeywell TC500A Commercial Thermostat have?
This list has 644 BACnet objects: 15 analog inputs, 60 analog outputs, 318 analog values, 5 binary inputs, 70 binary outputs, 82 binary values, 10 calendars, 21 multi-state outputs, 2 schedules, 61 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Honeywell TC500A Commercial Thermostat BACnet points are writable?
466 of the 644 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Honeywell TC500A Commercial Thermostat BACnet documentation?
Honeywell does not publish it on its own website. This list comes from TC500A BACnet Integration Guide (31-00478-05), revision Rev. 02-23, a copy hosted by Cochrane Supply at https://www.cochranesupply.com/media/assets/product/documents/Honeywell/TC500A-N%20BACnet%20Intergration.pdf. Ask Honeywell or its representative for the current revision.
What are the minimum BACnet points to integrate the Honeywell TC500A Commercial Thermostat?
Start with MV 3 ni_ApplicationMode (System mode from the network); BV 158 ni_OccupancySensor (Network occupancy: 1 = occupied, 0 = unoccupied); AV 7 Cfg_Setpoints_OccHeatSp (Occupied heating setpoint); AV 4 Cfg_Setpoints_OccCoolSp (Occupied cooling setpoint); MV 583 Cfg_FanCoilManualSpeedSel (Fan coil fan speed: auto, low, medium, high, off); AO 18 no_SpaceTemp (Space temperature in use); AO 3 no_EffHeatSp (Effective heating setpoint); AO 4 no_EffCoolSp (Effective cooling setpoint); BO 19 no_FanStart (Fan start output state); BO 102 no_GenericAlarm (Any alarm active).
How do I enable BMS control of the Honeywell TC500A Commercial Thermostat?
The BMS steers the thermostat through ni_ network inputs: application mode (MV 3, not kept over a power cycle), occupancy (BV 158), bypass (BV 1), shutdown (BV 4) and smoke (BV 5). The schedule-state, occupancy-state, manual-override and emergency-override multistate inputs (MV 1, 4, 5, 6) clash with network outputs in the guide and are not listed.
Does the Honeywell TC500A Commercial Thermostat need a BACnet heartbeat or have a communication timeout?
Each shared network input has a fail-detect enable and delay (0-3600 s), for example occupancy BV 159 / AV 263, outdoor temperature BV 163 / AV 271, space temperature BV 168 / AV 282. When a bound input stops updating it falls back after the delay.
Can the BMS supply sensor values to the Honeywell TC500A Commercial Thermostat?
Network inputs: ni_SpaceTemp AV 104, ni_SpaceRH AV 80, ni_SpaceCO2 AV 81, ni_OutdoorTemp AV 89, ni_OutdoorHum AV 194, outdoor and return enthalpy/dew point AV 339-342. Sylk sensor values can be overridden through AV 238-251.
How do I check these points on the real TC500A Commercial Thermostat?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Honeywell BACnet points lists
Source: TC500A BACnet Integration Guide · 31-00478-05 · rev. Rev. 02-23. Object names, instances and units are reproduced as published; descriptions are our own.