Easy BACnet
  1. Home
  2. BACnet points lists
  3. Honeywell
  4. TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)

Thermostat (fan coil, conventional and heat pump) · BACnet points list

Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The TC300 family are commercial touchscreen thermostats that run fan coil, conventional or heat pump equipment. All models talk BACnet MS/TP; the TC320 models add Wi-Fi with BACnet IP. The guide lists the objects chapter by chapter: I/O configuration, sensor and output status, alarms, operating state, setpoints, network inputs, service mode and schedule.

This page lists 531 BACnet objects for the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) — 378 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Honeywell’s documentation hosted by SupplyHouse.com, not by Honeywell itself, so treat it as unofficial.

Manufacturer
Honeywell
Model
TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)
Equipment
Thermostat (fan coil, conventional and heat pump)
Equipment type
Heat pumps
BACnet objects
531 (378 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
TC300, TC320, TC300B-G, TC300C-G, TC320B-G, TC320C-G, T300 Series
Source document
TC300 Thermostats BACnet Integration Guide · 31-00646-05 · rev. Rev. 11-25 (unofficial copy, hosted by SupplyHouse.com)
Download CSV 531 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Honeywell’s current documentation and the live device before use. Not official Honeywell information. Terms of use.

BMS integration notes: Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)

Integration in brief

Write the system mode to MV 3 ni_ApplicationMode and occupancy to MV 6 ni_OccupancySensorState (or schedule state MV 1), and adjust the occupied setpoints AV 7 / AV 4. Read space temperature AV 2001, effective setpoints AV 2003 / AV 2004, effective occupancy MV 2014 and the alarm objects. The BMS can feed space temperature, humidity, CO2 and outdoor air through the ni_ inputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3ni_ApplicationModeSystem mode: auto, cool, heat, fan only, offWrite
MV 6ni_OccupancySensorStateNetwork occupancy: occupied, unoccupied, bypass, standbyWrite
AV 7Cfg_Setpoints_OccHeatSpOccupied heating setpointWrite
AV 4Cfg_Setpoints_OccCoolSpOccupied cooling setpointWrite
MV 583Cfg_FanCoilManualSpeedSelFan speed: auto, low, medium, highWrite
MV 2014no_EffOccStateEffective occupancy stateRead
AV 2001no_SpaceTempSpace temperature in useRead
AV 2003no_EffHeatSpEffective heating setpointRead
AV 2004no_EffCoolSpEffective cooling setpointRead
BV 2035no_GenericAlarmAny alarm activeRead

Enable & remote start

The thermostat runs on its own; the BMS steers it through the ni_ network inputs (application mode, occupancy, schedule state, shutdown BV 4). ni_ApplicationMode is not kept over a power cycle.

Heartbeat & communication loss

Network fail detect: when a bound network input is not updated within its fail-detect delay (0-3600 s), it falls back to Invalid, the last good value or a fixed value. Per-input enable, fallback and delay objects exist for occupancy (BV 159, AV 262, MV 2021, AV 263), shutdown (BV 164, AV 273, BV 165, AV 274) and network sensors (BV 2087, AV 2507, AV 2508).

Sensors & values from the BMS

Network inputs: ni_SpaceTemp AV 104, ni_SpaceRH AV 80, ni_SpaceCO2 AV 2511, ni_OutdoorTemp AV 89, ni_OutdoorHum AV 194, ni_DATemp AV 2024 and ni_PipeTempMode MV 2012. Network sensor configuration decides whether these are used.

Network setup

Watch out for

Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

531 of 531 shown
Type
Multi-state
Access
Show
Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) BACnet Points List
DescriptionStates
MV7Cfg_Equip_EquipTypeEquipment type.Write1=FanCoil, 2=Conventional, 3=HeatPump
BV13Cfg_HeatPmp_CngOvrRelayTypeHeat pump reversing valve type. (TC3xxB models only)Write0=EnergizeOnHeat, 1=EnergizeOnCool
MV2038Cfg_WaterFlowValveConfigWater flow valve type. (TC3xxB models only)Write1=None, 2=NormallyClosed, 3=NormallyOpen
MV2039Cfg_HeatPumpTypeHeat pump source type. (TC3xxB models only)Write1=AirSource, 2=WaterSource
MV2040Cfg_ConventionalModeConventional mode. (TC3xxB models only)Write1=1StageHeat&1StageCool, 2=1StageHeatOnly, 3=1StageCoolOnly, 4=2StageHeatOnly, 5=2StageCoolOnly
BV35Cfg_Mod_StgHt1EnModulating heat stage mode.Write0=Disable, 1=Enable
AV96Cfg_Heat_ModHtEnMinOutModulating heat minimum output when enabled.%Write
MV87Cfg_FanCoilFourPipeSingleCoilTypeFour pipe single coil valve type.Write1=Regulating&ChangeOver, 2=6-WayValve
MV2033Cfg_ChangeoverSwitchPolarityTypeChangeover switch polarity type.Write1=Closedwithheat, 2=Closedwithcool
MV2034Cfg_2PipeSingleCoilHeat&CoolSysModChangeoverType2 pipe single coil heat & cool system mode changeover method.Write1=PipeSensor, 2=NetworkInput, 3=ChangeoverSwitch, 4=ManualChangeover
BV377Cfg_Mod_StgCl1EnModulating cool use stage 1 as enabled.Write0=Disable, 1=Enable
AV1461Cfg_Cool_ModClEnMinOutModulating cool minimum output when enabled.%Write
MV575Cfg_FanCoilTypeFan coil typeWrite1=4PipeDualCoil, 2=4PipesingleCoil, 3=2PipeSingleCoil
MV576Cfg_FanCoilHtgTypeHeating valve type (or single valve type on single-coil units)Write1=None, 2=OnOff, 3=Floating, 4=Modulating
MV577Cfg_FanCoilClgTypeThe 4-pipe dual coil cooling valve models.Write1=None, 2=OnOff, 3=Floating, 4=Modulating
AV1721Cfg_FanCoilHtgDriveTimeFloating heating valve drive timesWrite
AV1722Cfg_FanCoilClgDriveTime4 pipe dual coil floating cooling drive time. (TC3xxB models only)sWrite
MV580Cfg_FanCoilTwoPipeSingleCoilType2 pipe single coil type.Write1=Heat&Cool, 2=HeatingOnly, 3=CoolingOnly
MV578Cfg_FanCoilHtgDriveTypeFloating heating valve drive directionWrite1=Direct, 2=Reverse
MV579Cfg_FanCoilClgDriveType4 pipe dual coil floating cooling drive time. (TC3xxB models only)Write1=Direct, 2=Reverse
BV453Cfg_FanCoilHtgFloatingSyncEnFloating heating valve resync enableWrite0=Disable, 1=Enable
BV462Cfg_FanCoilClgFloatingSyncEn4 pipe dual coil floating cooling sync enable. (TC3xxB models only)Write0=Disable, 1=Enable
BV459Cfg_FanCoilOnOffClgVlvChar4 pipe dual coil on/off cooling valve characteristicWrite0=NormallyClosed, 1=NormallyOpen
BV458Cfg_FanCoilonOffHtgVlvCharOn/off heating valve actionWrite0=NormallyClosed, 1=NormallyOpen
AV2007Cfg_Cool_valvefloatEnMinOut4 pipe dual coil floating Cooling valve minimum output when enabled. (TC3xxB models only)%Write
AV2008Cfg_Heat_valvefloatEnMinOutFloating heating valve minimum output when enabled%Write
BV2036Cfg_ChangeOverValveType4 pipe single coil changeover valve typeWrite0=EnergizeOnHeat, 1=EnergizeOnCool
BV2037Cfg_SixwayValveOutput6-way valve typeWrite0=0-10V, 1=2-10V
BV2038Cfg_SixwayValveDriveTypeSix way valve direct/reverse enable flagWrite0=Direct, 1=Reverse
AV2066Cfg_SixwayValveHeatingMinOutput6-way valve heat min outputWrite
AV2067Cfg_SixwayValveHeatingMaxOutput6-way valve heat max outputWrite
AV2068Cfg_SixwayValveCoolingMinOutput6-way valve cool min outputWrite
AV2069Cfg_SixwayValveCoolingMaxOutput6-way valve cool max outputWrite
BV2079Cfg_ADR_EnableUser can configure to enable ADR functionWrite0=Off, 1=On
AV2496Cfg_ADR_OffsetUser can set the offset value of the ADR.Δ°FWrite
AO2006no_UIO3Universal Output shared to network.Read
AO64no_UIO1Universal Output shared to network.Read
AO63no_UIO2Universal Output shared to network.Read
BO74no_DO1Digital Output shared to network.Read0=Off, 1=On
BO75no_DO2Digital Output shared to network.Read0=Off, 1=On
BO76no_DO3Digital Output shared to network.Read0=Off, 1=On
BO77no_DIO1Digital Output shared to network.TC300B-G/ TC320B-G is DIO1, and TC300C-G/TC320C-G is DO4.Read0=Off, 1=On
BO78no_DIO2Digital output DIO2 (B models) or DO5 (C models) shared to networkRead0=Off, 1=On
MV26Cfg_UIO1Function assigned to universal input/output UIO1Write1=None, 2=6-WayValve, 3=ModulatingCool, 4=ModulatingHeat, 5=ModulatingValve, 6=VariableSpeedFan, 7=DischargeAirSensor, 8=DrainPanSensor, 9=OccupancySensor, 10=ProofOfAirflow, 11=PipeSensor, 12=SpaceTempSensor, 13=ChangeoverSwitch, 14=ProofOfWaterFlow, 15=OutDoorAirSensor, 16=ShutdownSensor, 17=Customized1, 18=Customized2, 19=Customized3, 20=FreezeSwitch, 21=EntryDoorSwitch, 22=Balcony/Window, 31=CO2Output
MV27Cfg_UIO2Function assigned to universal input/output UIO2Write1=None, 2=6-WayValve, 3=ModulatingCool, 4=ModulatingHeat, 5=ModulatingValve, 6=VariableSpeedFan, 7=DischargeAirSensor, 8=DrainPanSensor, 9=OccupancySensor, 10=ProofOfAirflow, 11=PipeSensor, 12=SpaceTempSensor, 13=ChangeoverSwitch, 14=ProofOfWaterFlow, 15=OutDoorAirSensor, 16=ShutdownSensor, 17=Customized1, 18=Customized2, 19=Customized3, 20=FreezeSwitch, 21=EntryDoorSwitch, 22=Balcony/Window, 31=CO2Output
MV2004Cfg_UIO3Function assigned to universal input/output UIO3Write1=None, 2=6-WayValve, 3=ModulatingCool, 4=ModulatingHeat, 5=ModulatingValve, 6=VariableSpeedFan, 7=DischargeAirSensor, 8=DrainPanSensor, 9=OccupancySensor, 10=ProofOfAirflow, 11=PipeSensor, 12=SpaceTempSensor, 13=ChangeoverSwitch, 14=ProofOfWaterFlow, 15=OutDoorAirSensor, 16=ShutdownSensor, 17=Customized1, 18=Customized2, 19=Customized3, 20=FreezeSwitch, 21=EntryDoorSwitch, 22=Balcony/Window, 31=CO2Output
MV28Cfg_DO1Function assigned to digital output DO1Write1=None, 2=HeatingOn/Off, 3=HeatingFloatingOpen, 4=CoolingFloatingOpen, 5=ValveOn/Off, 6=ValveFloatingOpen, 11=ChangeoverValve, 12=FanCommand, 13=HighSpeedFan, 14=MediumSpeedFan, 15=LowSpeedFan, 16=AuxiliaryHeat, 30=HeatStage1, 31=CoolStage1, 32=ValveStage1, 35=Dehumidifier, 36=Humidifier, 52=CO2Output, 53=LightingControlOutput, 54=OccupancyOutput
MV29Cfg_DO2Function assigned to digital output DO2Write1=None, 7=HeatingFloatingClose, 8=CoolingFloatingClose, 9=CoolingOn/Off, 10=ValveFloatingClose, 11=ChangeoverValve, 12=FanCommand, 13=HighSpeedFan, 14=MediumSpeedFan, 15=LowSpeedFan, 16=AuxiliaryHeat, 31=CoolStage1, 34=ReversingValve, 35=Dehumidifier, 36=Humidifier, 50=HeatStage2, 51=CoolStage2, 52=CO2Output, 53=LightingControlOutput, 54=OccupancyOutput
MV30Cfg_DO3Function assigned to digital output DO3Write1=None, 4=CoolingFloatingOpen, 9=CoolingOn/Off, 11=ChangeoverValve, 12=FanCommand, 13=HighSpeedFan, 14=MediumSpeedFan, 15=LowSpeedFan, 16=AuxiliaryHeat, 30=HeatStage1, 31=CoolStage1, 33=WaterFlowValve, 35=Dehumidifier, 36=Humidifier, 52=CO2Output, 53=LightingControlOutput, 54=OccupancyOutput
MV31Cfg_DIO1_DO4Function assigned to DIO1 / DO4Write1=None, 8=CoolingFloatingClose, 11=ChangeoverValve, 12=FanCommand, 13=HighSpeedFan, 14=MediumSpeedFan, 15=LowSpeedFan, 16=AuxiliaryHeat, 18=DischargeAirSensor, 19=DrainPanSensor, 20=OccupancySensor, 21=ProofOfAirflow, 22=PipeSensor, 23=SpaceTempSensor, 24=ChangeoverSwitch, 25=ProofOfWaterFlow, 26=OutdoorAirSensor, 27=ShutdownSensor, 35=Dehumidifier, 36=Humidifier, 37=Customized1, 38=Customized2, 39=Customized3, 40=FreezeSwitch, 41=EntryDoorSwitch, 42=Balcony/Window, 52=CO2Output, 53=LightingControlOutput, 54=OccupancyOutput
MV32Cfg_DIO2_DO5Function assigned to DIO2 / DO5Write1=None, 11=ChangeoverValve, 12=FanCommand, 13=HighSpeedFan, 14=MediumSpeedFan, 15=LowSpeedFan, 16=AuxiliaryHeat, 18=DischargeAirSensor, 19=DrainPanSensor, 20=OccupancySensor, 21=ProofOfAirflow, 22=PipeSensor, 23=SpaceTempSensor, 24=ChangeoverSwitch, 25=ProofOfWaterFlow, 26=OutdoorAirSensor, 27=ShutdownSensor, 35=Dehumidifier, 36=Humidifier, 37=Customized1, 38=Customized2, 39=Customized3, 40=FreezeSwitch, 41=EntryDoorSwitch, 42=Balcony/Window, 52=CO2Output, 53=LightingControlOutput, 54=OccupancyOutput
BI1phy_ChangeOverSwitchChangeover switch statusRead0=Close, 1=Open
AI1phy_DatSensorDischarge air sensor output value°FRead
BI2phy_DrainpanSensorDrain pan sensor statusRead0=Off, 1=On
BI3phy_OccupancySensorOccupancy sensor statusRead0=Standby, 1=Unoccupied
BI4phy_ProofOfAirFlowSensorProof of air flow sensor statusRead0=Off, 1=On
AI2phy_PipeSensorPipe sensor output value°FRead
BI6phy_ShutdownSensorShutdown sensor statusRead0=Off, 1=On
AI3phy_SpaceTempSensorSpace temperature sensor output value°FRead
BI5phy_ProofofWaterflowProof of waterflow status. (TC3xxB models only)Read0=Off, 1=On
AI4phy_OutdoorAirSensorOutdoor air sensor value°FRead
BI7phy_FreezeSwitchFreeze switch status.Read0=Close, 1=Open
BI8phy_EntryDoorSwitchEntry door switch status.Read0=Close, 1=Open
BI9phy_BalconcyWindowSwitchBalconcy/window switch status.Read0=Close, 1=Open
AO2001no_SixWay_Valve_CoolingSix-way valve cooling control output%Read
AO2002no_SixWay_Valve_HeatingSix-way valve Heating control output%Read
AO2003no_Modulating_CoolModulating cool control output%Read
AO2004no_Modulating_HeatModulating heat control output%Read
AO2005no_VariableFanVariable Fan control output%Read
BO2001no_Auxiliary_HeatAuxiliary heat control outputRead0=Off, 1=On
BO2002no_ChangeOverValveChangeover valve control outputRead0=Off, 1=On
BO2004no_Cooling_Valve(On/Off)Cooling on/off valve output statusRead0=Off, 1=On
BO2005no_Heating_Valve(On/Off)Heating on/off valve output statusRead0=Off, 1=On
BO2006no_Cooling_Floating_OpenCooling floating valve open control output. (TC3xxB models only)Read0=Off, 1=On
BO2007no_Cooling_Floating_CloseCooling floating valve close control output. (TC3xxB models only)Read0=Off, 1=On
BO2008no_Heating_Floating_OpenHeating floating valve open control output. (TC3xxB models only)Read0=Off, 1=On
BO2009no_Heating_Floating_CloseHeating floating valve close control output. (TC3xxB models only)Read0=Off, 1=On
BO2010no_High_Single_Speed_FanHigh speed fan on/off statusRead0=Off, 1=On
BO2011no_Low_Speed_FanLow speed fan on/off statusRead0=Off, 1=On
BO2012no_Medium_Speed_FanMedium speed fan on/off statusRead0=Off, 1=On
BO2014no_Modulating_Cooling_stage_1Modulating cool stage1 on/off statusRead0=Off, 1=On
BO2015no_Modulating_Heating_stage_1Modulating heat stage1 on/off statusRead0=Off, 1=On
BO2016no_WaterFlowValveWater flow valve control output. (TC3xxB models only)Read0=Off, 1=On
BO2017no_ReversingValveRevering valve control output. (TC3xxB models only)Read0=Off, 1=On
BO9no_HumActiveHumidifier control output. (TC3xxB models only)Read0=Off, 1=On
BO2070no_Conventional_Cooling_stage_2Conventional cool stage2 on/off status. (TC3xxB models only)Read0=Off, 1=On
BO2071no_Conventional_Heating_stage_2Convention heat stage2 on/off status. (TC3xxB models only)Read0=Off, 1=On
BO2075no_CO2_Binary_ValueCO2 Output Binary Logical ValueRead0=Off, 1=On
AO2007no_CO2_Analog_ValueCO2 Output Analog Logical ValueRead
BO2076no_Light_Control_OutputLighting Control OutputRead0=Off, 1=On
BO2077no_Occupancy_OutputOccupancy OutputRead0=Off, 1=On
BV31Cfg_OccSensCharOccupancy sensor input characteristics selectionWrite0=NormallyOpen, 1=NormallyClosed
BV33Cfg_AirFlwStsCharAirflow status input characteristics selectionWrite0=NormallyOpen, 1=NormallyClosed
AV185Cfg_UISensCalOffset_DATempUniversal input discharge air temperature calibration offsetΔ°FWrite
AV186Cfg_UISensCalOffset_OATempOutdoor air temperature calibration offsetΔ°FWrite
BV383Cfg_WaterFlwStsCharWaterflow sensor input characteristics selection. (TC3xxB models only)Write0=NormallyOpen, 1=NormallyClosed
MV372Cfg_SpcSensCharSpace temperature Sensor characteristic selectionWrite1=NTC10KTypeII, 2=NTC10KTypeIII, 3=NTC20K
AV1464Cfg_UISensCalOffset_SpcTempSpace temperature calibration offsetΔ°FWrite
BV2092Cfg_Control_OnboardOccupancySensorEnUsers can enable or disable the control of the onboard occupancy sensorWrite0=Off, 1=On
AV1475Cfg_ModHeatMin_OutputMinimum output voltage when modulating heating is enabledWrite
BV380Cfg_ModHeatActionModulating heat polarity selectionWrite0=Direct, 1=Reverse
AV1476Cfg_ModCoolMin_OutputMinimum output voltage when modulating cooling is enabledWrite
BV381Cfg_ModCoolActionModulating cool polarity selectionWrite0=Direct, 1=Reverse
MV373Cfg_VarSpeedFanTypeVariable fan speed type characteristic selectionWrite1=0-10V, 2=2-10V
AV1477Cfg_ModHeatMax_OutputMaximum voltage on heating outputWrite
AV1478Cfg_ModCoolMax_OutputMaximum voltage on cooling outputWrite
MV2005Cfg_PipeSensCharPipe sensor typeWrite1=NTC10KTypeII, 2=NTC10KTypeIII, 3=NTC20K
MV502Cfg_OASensChar1Outdoor air sensor type.Write1=NTC10K Type II, 2=NTC10K Type III, 3=NTC20K
MV503Cfg_DASensChar1Discharge air sensor typeWrite1=NTC10KTypeII, 2=NTC10KTypeIII, 3=NTC20K
BV455Cfg_LeakDetectorSensorCharLeak detector/ Drain pan sensor characteristicsWrite0=NormallyOpen, 1=NormallyClosed
BV34Cfg_ShutdownCharShutdown sensor typeWrite0=NormallyOpen, 1=NormallyClosed
MV2046Cfg_Customized1SensorTypeCustomized1 input type of the sensorWrite1=DigitalInput, 2=VoltageInput, 3=TemperatureSensor
BV2061Cfg_Customized1DigitalInputTypeCustomized1 digital input type of the sensorWrite0=NormallyOpen, 1=NormallyClosed
BV2062Cfg_Customized1VoltageInputControlActionCustomized1 sensor the polarity of the voltage inputWrite0=Direct, 1=Reverse
AV2443Cfg_Customized1VoltageMinInputCustomized1 minimum voltage input for the sensorWrite
AV2444Cfg_Customized1VoltageMaxInputCustomized1 maximum voltage input for the sensorWrite
MV2047Cfg_Customized1TempSensorTypeCustomized1 temperature sensor input typeWrite1=NTC10K Type II, 2=NTC10K Type III, 3=NTC20K
MV2048Cfg_Customized2SensorTypeCustomized2 input type of the sensorWrite1=DigitalInput, 2=VoltageInput, 3=TemperatureSensor
BV2063Cfg_Customized2DigitalInputTypeCustomized2 digital input type of the sensorWrite0=NormallyOpen, 1=NormallyClosed
BV2064Cfg_Customized2VoltageInputControlActionCustomized2 sensor the polarity of the voltage inputWrite0=Direct, 1=Reverse
AV2445Cfg_Customized2VoltageMinInputCustomized2 minimum voltage input for the sensorWrite
AV2446Cfg_Customized2VoltageMaxInputCustomized2 maximum voltage input for the sensorWrite
MV2049Cfg_Customized2TempSensorTypeCustomized2 temperature sensor input typeWrite1=NTC10K Type II, 2=NTC10K Type III, 3=NTC20K
MV2050Cfg_Customized3SensorTypeCustomized3 input type of the sensorWrite1=DigitalInput, 2=VoltageInput, 3=TemperatureSensor
BV2065Cfg_Customized3DigitalInputTypeCustomized3 digital input type of the sensorWrite0=NormallyOpen, 1=NormallyClosed
BV2066Cfg_Customized3VoltageInputControlActionCustomized3 sensor the polarity of the voltage inputWrite0=Direct, 1=Reverse
AV2447Cfg_Customized3VoltageMinInputCustomized3 minimum voltage input for the sensorWrite
AV2448Cfg_Customized3VoltageMaxInputCustomized3 maximum voltage input for the sensorWrite
MV2051Cfg_Customized3TempSensorTypeCustomized3 temperature sensor input typeWrite1=NTC10K Type II, 2=NTC10K Type III, 3=NTC20K
BV2075Cfg_CO2_OutputEnableEnable CO2 output.Write0=Off, 1=On
MV2065Cfg_CO2_DeviceTypeThe user selects the CO2 device type.Write1=Analog, 2=Binary
MV2066Cfg_CO2_AnalogTypeThe user selects the CO2 analog type.Write1=0-10V, 2=2-10V
BV2076Cfg_CO2_BinaryTypeThe user selects the CO2 binary type.Write0=NormallyOpen, 1=NormallyClosed
AV2485Cfg_CO2_ThresholdLimitThe user set the trigger threshold for the CO2 binary type.Write
AV2486Cfg_CO2_ThresholdDeadbandThe user can set the CO2 threshold deadband.Write
AV2487Cfg_EntryDoor_ActionDelayTimeDelay before the entry door switch triggers its actionWrite
MV2067Cfg_EntryDoor_OpenActionThe user can set the action to open the Entry door switch sensor.Write1=NoAction, 2=DisableHVACSystem, 3=SwitchToUnoccupied Mode, 4=AlarmOnly
AV2488Cfg_Balcony_Window_ActionDelayTimeDelay before the balcony/window switch triggers its actionWrite
MV2068Cfg_Balcony_Window_OpenActionThe user can set the action to open the balcony/ window sensor.Write1=DisableHVACSystem, 2=SwitchToUnoccupied Mode, 3=AlarmOnly
BV2077Cfg_Light_OutputTypeThe user can set the type of lighting control output.Write0=NormallyOpen, 1=NormallyClosed
AV2489Cfg_Light_OFFDelayTimeThe user set the time delay for turning off the lighting.Write
BV2085Cfg_Light_OutputEnableEnable Lingting Control Output.Write0=Off, 1=On
AV2490Cfg_Occupancy_SensorDelayTimeThe user set the time delay for occupancy sensor.Write
BV2078Cfg_Occupancy_OutputTypeThe user set the occupancy type.Write0=NormallyOpen, 1=NormallyClosed
BV2086Cfg_Occupancy_OutputEnableEnable Occupancy Output.Write0=Off, 1=On
BV2071Cfg_FreezeSwitchCharFreeze switch sensor input characteristics selection.Write0=NormallyOpen, 1=NormallyClosed
BV2080Cfg_EntryDoorSensorTypeEntry door sensor input characteristics selection.Write0=NormallyOpen, 1=NormallyClosed
BV2081Cfg_BalconcyWindowSensorTypeBalcony/Window sensor input characteristics selection.Write0=NormallyOpen, 1=NormallyClosed
BV2002AlarmPriority_ProofofAirFlowSupply fan status mismatch alarm & priority.Read0=Inactive, 1=Active
BV2049AlarmPriority_SpaceFreezeProtectSpace temperature below the freeze limit for 120 sRead0=Inactive, 1=Active
BV2057AlarmPriority_WaterFlwPrfProof of water flow alarm & priority. (TC3xxB models only)Read0=Inactive, 1=Active
BV2050AlarmPriority_UnknownTimeTime lost alarmRead0=Inactive, 1=Active
AV2081AlarmPriority_TempSensTemperature sensor alarm priorityRead
AV2082AlarmPriority_HumSensHumidity sensor alarm priorityRead
MV2036Alarm_SylkCommFailureSylk communication failure; shows which sensor or many failedRead1=Normal, 2=SylkAddr2Fail, 3=SylkAddr3Fail, 4=SylkAddr4Fail, 5=SylkAddr5Fail, 8=SylkAddr8Fail, 10=SylkAddr10Fail, 16=ManySylkFail
AV2084AlarmPriority_SpcTempHI_LolimitSpace temperature out of range alarm priorityRead
MV2029AlarmPriority_DATempAlarm_FaultDischarge air sensor alarm: failed (high) or out of range (medium)Read1=Inactive, 2=Medium, 3=High
MV2042AlarmPriority_OATempAlarm_FaultOutdoor air sensor alarm: failed (high) or out of range (medium)Read1=Inactive, 2=Medium, 3=High
BV2011AlarmPriority_ShutdownFaultShutdown signal received from network or terminalRead0=Inactive, 1=Active
MV2030Alarm_PipeSensorFailurePipe sensor failure occurs.Read1=Inactive, 3=Active
AV2085Alarm_PipeSensorTempHeatOrCoolThresholdPipe water temperature not suitable for heating or coolingRead
BV2051Alarm_RoomTempTrendFailureRoom temperature changing trend is reversed with system operating mode.Read0=Inactive, 1=Active
BV2052Alarm_CHWDrainPanSensorDrain pan sensor alarmRead0=Inactive, 1=Active
MV2031Alarm_PipeSensorOutofRangePipe sensor temperature out of range.Read1=Inactive, 3=Active
MV2052Alarm_WSHPSystemEnableStateWater source heat pump disabled from the network; compressor offRead1=Inactive, 3=Active
MV2074AlarmPriority_OccuSen_FaultOccupancy sensor alarm & priority.Read1=Inactive, 3=Active
MV2075AlarmPriority_LightSen_FaultLight sensor alarm & priority.Read1=Inactive, 3=Active
MV2076AlarmPriority_BalWinSen_FaultBalcony/Window sensor alarm & priority.Read1=Inactive, 3=Active
MV2077AlarmPriority_EnDoorOpSen_FaultEntry door open sensor alarm & priority.Read1=Inactive, 3=Active
MV2078AlarmPriority_CO2LvlAlarm_Faultwhen the CO2 sensor has hardware fault, high alarm is reportedRead1=Inactive, 2=Medium, 3=High
BV2008AlarmPriority_Co2lvlHighlimitWhen the value of CO2 sensor exceeds the threshold, alarm is reported.Read0=Inactive, 1=Active
BV2010AlarmPriority_CoilFreezeProtAlmCoil freeze switch active (fan coil units)Read0=Inactive, 1=Active
AV2088Cfg_ProofofAirFlowAlarmBit flags for outputs to shut off on an airflow proof alarmWrite
AV193Cfg_Alarm_WaterFlowAlarmConfigBit flags for outputs to shut off on a water flow alarm (TC3xxB models only)Write
AV2441Cfg_SpaceTempFaultyAlarmBit flags for action when the remote space sensor is invalidWrite
AV2098Cfg_RoomTempTrendFailureShut down all digital outputs on a room temperature trend failureWrite
AV2100Cfg_DrainPanSensorAlarmBit flags for outputs to shut off on a drain pan alarmWrite
AV2475Cfg_CoilFreezeProtectionAlarmBit flags for outputs to turn on during a coil freeze alarmWrite
AV291Cfg_CO2Alarm_LvlHighLimCO2 level above which the CO2 alarm is raisedWrite
BV2067no_Customized1DigitalOutputCustomized1 sensor digital outputRead0=Off, 1=On
AV2449no_Customized1VoltageOutputCustomized1 sensor voltage output percentage%Read
AV2450no_Customized1TempOutputCustomized1 sensor temperature output°FRead
BV2068no_Customized2DigitalOutputCustomized2 sensor digital outputRead0=Off, 1=On
AV2451no_Customized2VoltageOutputCustomized2 sensor voltage output percentage%Read
AV2452no_Customized2TempOutputCustomized2 sensor temperature output°FRead
BV2069no_Customized3DigitalOutputCustomized3 sensor digital outputRead0=Off, 1=On
AV2453no_Customized3VoltageOutputCustomized3 sensor voltage output percentage%Read
AV2454no_Customized3TempOutputCustomized3 sensor temperature output°FRead
MV2044no_HeatOATLockOutOutdoor air temperature heat lockout flag. (TC3xxB models only)Read1=None, 2=HeatLockout, 3=CompressorLockout, 4=AuxiliaryHeatLockout
BV2059no_CoolOATLockOutOutdoor air temperature Cool lockout flag. (TC3xxB models only)Read0=Off, 1=On
AV2026no_CoolCtrl_RunTimeAccumulateOutputs the actual run time of cooling controlhRead
MV2013no_LocalOccSensStateLocal occupancy sensor state.Read1=Occupied, 2=Unoccupied, 3=Unused
AV2027no_AuxHeatTermLdOutTerminal load for auxiliary heat%Read
MVmin2014no_EffOccStateEffective occupancy stateRead1=Commercial Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=NoOverride
AV2028no_CoolStg1_RunTimeAccumulateOutputs the actual run time of cooling stage 1hRead
AV2029no_HeatCtrl_RunTimeAccumulateOutputs the actual run time of heating controlhRead
AV2030no_HeatStg1_RunTimeAccumulateOutputs the actual run time of heating stage 1hRead
AV2031no_Fan_RunTimeAccumulateOutputs the actual run time of Fan.hRead
BV2015no_OccupancyStateSystem is in occupied/ unoccupied state.Read0=Unoccupied, 1=Occupied
BV2016no_HeatDatLockoutDischarge Air High Limit output: DAT heating lockout flagRead0=Off, 1=On
BV2017no_IsAuxHeatDisableAuxiliary heating enabled/ disabled.Read0=Off, 1=On
BV2018no_IsHeatDisableHeating enabled/ disabled.Read0=Off, 1=On
BV2019no_IsFanOnlyFan only mode enabled/ disabled.Read0=Off, 1=On
AV2032no_EffSpEffective setpoint°FRead
MV2015no_EffTempModeEffective temperature modeRead1=CoolMode, 2=ReheatMode, 3=HeatMode, 4=EmergencyHeat, 5=Off, 6=Ventilation
AV2033no_EffAuxHeatSetpointEffective auxiliary heat setpoint.°FRead
BV2020no_SystemDisableSystem disable.Read0=Off, 1=On
BV2021no_DehumActiveDehumidification active/ inactive.Read0=Inactive, 1=Active
BV2022no_BypassStateBypass state outputRead0=NoBypass, 1=Bypass
MV2016no_ManualOverrideManual overrideRead1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MV2017no_EffOccSensStateEffective occupancy sensor stateRead1=Occupied, 2=UnOccupied, 3=Unused
BV2023no_CoolDatLockoutDischarge air high limit output: DAT cooling lockout flagRead0=Off, 1=On
AV2036no_CoolTermLdOutTerminal load for cooling%Read
BV2025no_IsCoolDisableCooling enabled/ disabled.Read0=Enable, 1=Disable
AV2038no_HeatTermLdOutTerminal load for heating%Read
BV2026no_FanStartFan start commandRead0=Off, 1=On
AV2040no_DaTempDischarge air temperature°FRead
AV2041no_PipeTempPipe sensor temperature°FRead
MV2018no_EffSchCurrentStateCurrent schedule state to network.Read1=Occupied_Wake, 2=Unoccupied_Away, 3=Bypass_Return, 4=Standby_Sleep, 5=NoOverride, 6=None_Custom, 7=None_Vacation, 8=None_Unrented
MV2019no_EffSchNextStateNext schedule state to network.Read1=Occupied_Wake, 2=Unoccupied_Away, 3=Bypass_Return, 4=Standby_Sleep, 5=NoOverride, 6=None_Custom, 7=None_Vacation, 8=None_Unrented
AV2042no_EffTUNCOSMinutes until the next schedule changeminRead
AV2043no_OverrideRemTimeTime left before the override endsminRead
AV2044no_CtrlSpaceTempControl space temperature output (Only for testing purpose)°FRead
BV2030no_RecoveryStatusThis point gives out when the system is in recovery mode.Read0=Normal, 1=Recovery
AV2045no_TermLdOutTerminal load, -200 to +200 % (negative = heating)%Read
AV2046no_EffDATSpEffective discharge air control setpoint°FRead
AVmin2001no_SpaceTempSpace Temperature°FRead
AV2002no_SpaceHumiditySpace Humidity%RHRead
AVmin2003no_EffHeatSpEffective Heating Setpoint°FRead
AVmin2004no_EffCoolSpEffective Cooling Setpoint°FRead
MV2001no_SetpointStsSetpoint status; Temporary after a user adjustmentRead1=Occupied_Wake, 2=Unoccupied_Away, 3=Temporary, 4=Standby_Return, 5=Permanent, 6=Fixedsetpoint, 7=Sleep, 8=Custom, 9=Vacation, 10=Unrented
AV2439no_OaTempOutdoor air temperature.°FRead
AV2440no_OaHumidityOutdoor air Humidity.%RHRead
AV2442no_SpaceCO2Space CO2Read
BVmin2035no_GenericAlarmGeneral alarm flagRead0=Inactive, 1=Active
AV2470no_CoolStg2_RunTimeAccumulateOutputs the actual run time of cooling stage 2. (TC3xxB models only)hRead
AV2471no_HeatStg2_RunTimeAccumulateOutputs the actual run time of heating stage 2. (TC3xxB models only)hRead
AV2506no_LightSensorOutputLight sensor output.Read
CSV1no_DateAndTimeUsers can check the time of the device through the networkRead
AV2021no_ScheduleTimeToNextTime to next schedule stateminRead
AV2513no_ScheduleHospitalityPointsValueHospitality status points valueRead
MV2079no_ScheduleActiveSchedule activation status.Read1=None, 2=Weekly, 3=Holiday, 4=SpecialEvent, 5=Vacation
MV2054Cfg_ScheduleTypeUsers can choose commercial, residential, fixed setpoint schedule or hospitality schedule.Write1=Commercial, 2=Residential, 3=FixedSetpoint, 4=Hospitality
MV2027no_ScheduleCurrentStateCurrent schedule state.Read1=Occupied_Wake, 2=Unoccupied_Away, 3=Temporary_Return, 4=Standby_Sleep, 5=None_Custom, 6=None_Vacation, 7=None_Unrented
MV2028no_ScheduleNextStateNext schedule state.Read1=Occupied_Wake, 2=Unoccupied_Away, 3=Temporary_Return, 4=Standby_Sleep, 5=None_Custom, 6=None_Vacation, 7=None_Unrented
AV223no_SylkAddr2TempTR40-H-CO2: Temperature (May also use models TR40, TR40-H, TR40-CO2, TR40-H-CO2)°FRead
AV224no_SylkAddr2HumTR40-H-CO2: Humidity (May also use models TR40, TR40-H, TR40-CO2, TR40-H-CO2)%RHRead
AV225no_SylkAddr2CO2TR40-H-CO2: CO2. (May also use models TR40-CO2, TR40-H-CO2)ppmRead
AV226no_SylkAddr3TempAddress 3 TR40: Temperature°FRead
AV227no_SylkAddr4TempAddress 4 TR40: Temperature°FRead
AV228no_SylkAddr5TempAddress 5 TR40: Temperature°FRead
AV231no_SylkAddr8TempAddress 8 C7400S: Temperature.°FRead
AV232no_SylkAddr8HumAddress 8 C7400S: Humidity.%RHRead
AV235no_SylkAddr10TempAddress 10 C7400S: Temperature°FRead
AV236no_SylkAddr10HumAddress 10 C7400S: Humidity%RHRead
AV2505no_SylkAddr6TempTR100 Em TR75: Temperature.°FRead
AV230no_SylkAddr6HumTR100 Em TR75: Humidity.%RHRead
BV2039Cfg_AuxiliaryHeatEnableAuxiliary heat enableWrite0=Off, 1=On
MV2003Cfg_HeatPmp_AuxModeAuxiliary heat typeWrite1=Peripheral, 2=Supplemental
AV2018Cfg_AuxiliaryHeatPeriperalDroopPeripheral aux heat droopΔ°FWrite
AV2019Cfg_AuxiliaryHeatSupplementalDroopSupplemental aux heat droopΔ°FWrite
BV2001Cfg_AuxHeat_FanOnOffFan run on/Off when aux heat onWrite0=Off, 1=On
AV50Cfg_HeatPmp_AuxHeatLockoutSpOutdoor air temperature auxiliary heat lockout.°FWrite
AV215Cfg_HeatPmp_UpStgTmrUp stage timer valueminWrite
BV2055Cfg_HeatPmp_UpStgTmrEnUp stage timer enableWrite0=Off, 1=On
AV53Cfg_HeatPmp_AuxHeatRampFactorAuxiliary heat recovery ramp factorWrite
BV466Cfg_AuxiliaryHeat_EnableOATLockoutEnable auxiliary heat outdoor air temperature lockout. (TC3xxB models only)Write0=Disable, 1=Enable
AV2110Cfg_CompressorDelayCompressor delay time setting. (TC3xxB models only)sWrite
AV51Cfg_HeatPmp_CompLockoutSpOutdoor air temperature compressor lockout. (TC3xxB models only)°FWrite
BV465Cfg_Compressor_EnableOATLockoutEnable compressor outdoor air temperature lockout. (TC3xxB models only)Write0=Disable, 1=Enable
AV41Cfg_Cool_TrCooling throttling rangeΔ°FWrite
AV42Cfg_Cool_ItCooling integral time 0 = disable (i.e., proportional only)sWrite
AV44Cfg_Cool_CPHCooling system response. (TC3xxB models only)Write
AV45Cfg_Cool_MinOnTimeCooling stage minimum on time. (TC3xxB models only)sWrite
AV82Cfg_Cool_MinOffTimeCooling stage minimum off time. (TC3xxB models only)sWrite
AV46Cfg_Cool_CoolLockoutSpOutdoor air temperature cool lockout. (TC3xxB models only)°FWrite
AV47Cfg_Cool_DischLoLimSpDischarge air temperature low limit setpoint°FWrite
BV467Cfg_Cool_EnableOATLockoutEnable cool outdoor air temperature lockout. (TC3xxB models only)Write0=Disable, 1=Enable
AV101Cfg_Thermostat_DeadbandTemperature differential between heat and cool setpointΔ°FWrite
BV2040Cfg_DehumEnableEnable/disable dehumidificationWrite0=Off, 1=On
AV48Cfg_Dehum_SpaceRHHighLimitSpace relative humidity (RH) high limit setpoint%RHWrite
AV2022Cfg_Dehum_OverCool_OffsetDehumidification over cool offsetΔ°FWrite
BV133Cfg_Dehum_StageReHeatOpEnStaged reheat operation enableWrite0=Disable, 1=Enable
BV2041Cfg_DehumAuxHeatForReheatAux heat reheat enableWrite0=Disable, 1=Enable
MV12Cfg_FanTypeFan can be configured as single speed, two speed or as a variable speed fan.Write1=SingleSpeed, 2=TwoSpeed, 3=ThreeSpeed, 4=VariableSpeed
MV89Cfg_FanDefaultModeFan Mode of operation config by user & supervisor.Write1=Auto, 2=Circulate, 3=Continuous
AV39Cfg_FanRunOffDelayCoolFan run on time after all cooling terminal turns off.sWrite
AV40Cfg_FanRunOnDelayHeatFan run on delay time after heating terminal turns on.sWrite
AV2017Cfg_FanRunOffDelayHeatFan run on time after all heating terminal turns off.sWrite
AV2087Cfg_FanConfigBit flags for allowed fan modes (auto bit must be 1)Write
AV2472Cfg_FanManualVariableSpeedThe user can manually set the speed of the variable fan.%Write
MV2063Cfg_FanVariableSwitchTypeUsers can select variable fan speed switch type.Write1=ThreeSpeed, 2=VariableSpeed
MV2062Cfg_FanResSpeedSettingUsers can select the fan speed setting to the residential schedule.Write1=Fixed, 2=AutoControl
MVmin583Cfg_FanCoilManualSpeedSelFan speedWrite1=Auto, 2=Low, 3=Medium, 4=High, 5=Off, 6=Circulate, 7=Variable
MV2055Cfg_FanResWakeModeUsers can set the fan mode to the residential schedule wake status.Write1=Auto, 2=Circulate, 3=Continuous
MV2056Cfg_FanResAwayModeUsers can set the fan mode to the residential schedule away status.Write1=Auto, 2=Circulate, 3=Continuous
MV2057Cfg_FanResReturnModeUsers can set the fan mode to the residential schedule return status.Write1=Auto, 2=Circulate, 3=Continuous
MV2058Cfg_FanResSleepModeUsers can set the fan mode to the residential schedule sleep status.Write1=Auto, 2=Circulate, 3=Continuous
MV2059Cfg_FanResCustomModeUsers can set the fan mode to the residential schedule custom status.Write1=Auto, 2=Circulate, 3=Continuous
MV2060Cfg_FanResVacationModeUsers can set the fan mode to the residential schedule vacation status.Write1=Auto, 2=Circulate
BV10Cfg_FanOnHeatFan in heat mode: external duct thermostat or thermostat outputWrite0=Off, 1=On
BV2074Cfg_AuxiliaryHeat_DisableCompressorHeat pump: auxiliary heat on disables the compressor stageWrite0=Off, 1=On
MV585Cfg_TwoSpeedVentModeFan speed for ventilation modeWrite1=Low, 2=High
MV586Cfg_FanCoilThreeSpeedVentModeFan speed for ventilation modeWrite1=Low, 2=Medium, 3=High
MV581Cfg_FanCoilTwoSpeedTypeTwo speed fan output type. (TC3xxB models only)Write1=MultipleOutputsAtATime, 2=OneOutputAtATime
MV582Cfg_FanCoilThreeSpeedTypeThree speed fan output type. (TC3xxB models only)Write1=MultipleOutputsAtATime, 2=OneOutputAtATime
AV1470Cfg_VarSpeedFan_VentSpeedVariable speed fan speed for ventilation mode%Write
MV15Cfg_FanSpeed_CmprCoolSingleHeat pump two speed compressor single mode. (TC3xxB models only)Write1=Low, 2=High, 3=Auto
MV2041Cfg_FanSpeed_CoolSingleModeConventional two speed cool single mode. (TC3xxB models only)Write1=Low, 2=High, 3=Auto
MV17Cfg_FanSpeed_HeatSingleConventional two speed heat single mode. (TC3xxB models only)Write1=Low, 2=High, 3=Auto
MV2043Cfg_FanSpeed_AuxHeatModeHeat pump two speed auxiliary heat single mode. (TC3xxB models only)Write1=Low, 2=High, 3=Auto
AV1468Cfg_VarSpeedFan_CoolMinSpeedVariable speed fan min speed for cool%Write
AV1469Cfg_VarSpeedFan_CoolMaxSpeedVariable speed fan max speed for cool%Write
AV1473Cfg_VarSpeedFan_HeatMinSpeedVariable speed fan min speed for heat%Write
AV1474Cfg_VarSpeedFan_HeatMaxSpeedVariable speed fan max speed for heat%Write
MV18Cfg_FanSpeed_HeatMultiConventional two speed heat multi mode. (TC3xxB models only)Write1=Low, 2=High, 3=Auto
MV2061Cfg_FanSpeed_CoolMultiConventional two speed cool multi mode. (TC3xxB models only)Write1=Low, 2=High, 3=Auto
AV2473Cfg_VarSpeedFan_AdjustLowSpeedVariable speed fan low speed for adjustable mode.%Write
AV2474Cfg_VarSpeedFan_AdjustHighSpeedVariable speed fan high speed for adjustable mode.%Write
AV54Cfg_Heat_TrHeating throttling rangeΔ°FWrite
AV55Cfg_Heat_ItHeating integral time 0 = disable (i.e., proportional only)sWrite
AV57Cfg_Heat_CPHHeating system responseWrite
AV58Cfg_Heat_MinOnTimeHeating stage minimum on time. (TC3xxB models only)sWrite
AV59Cfg_Heat_MinOffTimeHeating stage minimum off time. (TC3xxB models only)sWrite
AV60Cfg_Heat_HeatLockoutSpOutdoor air temperature heat lockout. (TC3xxB models only)°FWrite
AV61Cfg_Heat_DischHiLimSpDischarge air temperature high limit setpoint°FWrite
MV2045Cfg_Heat_FuelTypeHeating fuel type; sets the default cycles per hourWrite1=Gas/Oil, 2=Electric
BV464Cfg_Heat_EnableOATLockoutEnable heat outdoor air temperature lockout. (TC3xxB models only)Write0=Disable, 1=Enable
MV9Cfg_Control_MainSensorTemperature sensor selectionWrite1=LocalSensor, 2=RemoteSensor, 3=Multi-Sensor
AV14Cfg_Control_PowerupDelayInitial delay to start control after power cycle.sWrite
MV2069Cfg_Control_CO2SensorCO2 sensor selectionWrite1=LocalSensor, 2=RemoteSensor, 3=MultiSensors
MV2070Cfg_Control_HumiditySensorHumidity sensor selectionWrite1=LocalSensor, 2=RemoteSensor, 3=MultiSensors
MV2071Cfg_ZoneReSens_HumSenActionAction on invalid remote humidity: use local sensor or stop equipmentWrite1=SuspendHumidit yOutput, 2=RevertToOnboard
MV2072Cfg_ZoneReSens_CO2SenActionAction on invalid remote CO2: use local sensor or stop equipmentWrite1=SuspendCO2Ou tput, 2=RevertToOnboard
BV136Cfg_Thermostat_TstUnitSelThermostat unit definition (Imperial/ Metric)Write0=Fahrenheit, 1=Celsius
BV2060Cfg_Thermostat_CommUnitSelThermostat communication unit definition (Imperial/ Metric)Write0=Fahrenheit, 1=Celsius
MV505Cfg_BrandTypeVendor ID and Vendor name will be changed when modify brand type.Write1=Honeywell, 2=Alerton, 3=None, 4=Custom
MV2053Cfg_Thermostat_LanguageTypeUsers can change the HMI language.Write1=English, 2=Spanish, 3=French, 4=Italian, 5=German
BV2034Cfg_StdbyConfigStandby actionWrite0=StandbyAsUnoccupied, 1=StandbyAsOccupied
AV256Cfg_Thermostat_ClAdjStPtTemporary cool setpoint adjustment from User or from the supervisor.°FWrite
AV257Cfg_Thermostat_HtAdjStPtTemporary heat setpoint adjustment from user or from the supervisor.°FWrite
BV2088no_ADR_StatusThe user check the status of ADR.Read0=Disable, 1=Enable
BV2056Cfg_HumidificationEnableHumidification enable. (TC3xxB models only)Write0=Off, 1=On
AV62Cfg_Hum_SpaceRHLowLimitSpace relative humidity (RH) low limit setpoint. (TC3xxB models only)%Write
AV254Cfg_SpcAlarm_TempHighLimSpace temperature alarm high limit°FWrite
AV255Cfg_SpcAlarm_TempLowLimSpace temperature alarm low limit°FWrite
AV332Cfg_DaTAlarm_TempHighLimDischarge air temperature alarm high limit°FWrite
AV333Cfg_DATAlarmTempLowLimDischarge air temperature alarm low limit°FWrite
AV2070Cfg_PipeTempHeatThresholdPipe sensor threshold for heating°FWrite
AV2071Cfg_PipeTempCoolThresholdPipe sensor threshold for cooling°FWrite
AV2072Cfg_PipeTempHighLimitPipe temperature alarm high limit°FWrite
AV2073Cfg_PipeTempLowLimitPipe temperature alarm low limit°FWrite
AV2074Cfg_PipeSpaceHeatTempOffset2 pipe single coil hybrid control space temperature offset for heatingΔ°FWrite
AV2075Cfg_PipeSpaceCoolTempOffset2 pipe single coil hybrid control space temperature offset for coolingΔ°FWrite
AV2437Cfg_OutdoorAirTempHighLimitOutdoor air temperature alarm high limit°FWrite
AV2438Cfg_OutdoorAirTempLowLimitOutdoor air temperature alarm low limit°FWrite
MV130Cfg_ZoneMultiSens_ControlMain control sensor configurationWrite1=Average, 2=Min, 3=Max, 4=Smart
AV33Cfg_ZoneMultiSens_Sens1_WtAveraging weight of the on-board temperature sensorWrite
AV34Cfg_ZoneMultiSens_Sens2_WtAveraging weight of Sylk temperature sensor at address 2Write
AV35Cfg_ZoneMultiSens_Sens3_WtAveraging weight of Sylk temperature sensor at address 3Write
AV36Cfg_ZoneMultiSens_Sens4_WtAveraging weight of Sylk temperature sensor at address 4Write
AV37Cfg_ZoneMultiSens_Sens5_WtAveraging weight of Sylk temperature sensor at address 5Write
MV77Cfg_ZoneMultiHumSens_ControlHumidity sensor configurationWrite1=Average, 2=Min, 3=Max, 4=Smart
AV181Cfg_ZoneMultiSens_HumSens1_WtAveraging weight of the on-board humidity sensorWrite
AV180Cfg_ZoneMultiSens_HumSens2_WtAveraging weight of Sylk humidity sensor at address 2Write
AV2519Cfg_ZoneMultiSens_Sens7_WtAveraging weight of the analog space temperature inputWrite
AV2491Cfg_ZoneMultiSens_CO2Sens2_WtAveraging weight of the Sylk CO2 sensor at address 2Write
AV2492Cfg_ZoneMultiSens_CO2Sens1_WtAveraging weight of the local CO2 sensorWrite
MV2073Cfg_ZoneMultiCO2Sens_ControlCO2 sensor configuration.Write1=Average, 2=Min, 3=Max
AV2493Cfg_ZoneMultiSens_TempSelThe user is able to choose which temperature sensors to participate in the calculationWrite
AV2494Cfg_ZoneMultiSens_HumSelThe user is able to choose which humidity sensors to participate in the calculationWrite
AV2495Cfg_ZoneMultiSens_CO2SelThe user is able to choose which CO2 sensors to participate in the calculationWrite
AV218Cfg_ZoneMultiSens_HumSens6_WtAveraging weight of Sylk humidity sensor at address 6Write
AV219Cfg_ZoneMultiSens_Sens6_WtAveraging weight of Sylk temperature sensor at address 6Write
AVmin7Cfg_Setpoints_OccHeatSpOccupied Heat Setpoint°FWrite
AVmin4Cfg_Setpoints_OccCoolSpOccupied Cool Setpoint°FWrite
AV8Cfg_Setpoints_StbyHeatSpStandby Heat Setpoint°FWrite
AV5Cfg_Setpoints_StbyCoolSpStandby Cool Setpoint°FWrite
AV9Cfg_Setpoints_UnOccHeatSpUnoccupied Heat Setpoint°FWrite
AV6Cfg_Setpoints_UnOccCoolSpUnoccupied Cool Setpoint°FWrite
AV2457Cfg_Setpoints_FixedSpCoolSpFixedSetpoint cooling setpoint.°FWrite
AV2456Cfg_Setpoints_FixedSpHeatSpFixedSetpoint heating setpoint°FWrite
AV2458Cfg_Setpoints_ResWakeHeatSpUsers can set the residential heat setpoint in wake state.°FWrite
AV2459Cfg_Setpoints_ResWakeCoolSpUsers can set the residential cool setpoint in wake state.°FWrite
AV2460Cfg_Setpoints_ResAwayHeatSpUsers can set the residential heat setpoint in wake state.°FWrite
AV2461Cfg_Setpoints_ResAwayCoolSpUsers can set the residential cool setpoint in wake state.°FWrite
AV2462Cfg_Setpoints_ResReturnHeatSpUsers can set the residential heat setpoint in wake state.°FWrite
AV2463Cfg_Setpoints_ResReturnCoolSpUsers can set the residential cool setpoint in wake state.°FWrite
AV2464Cfg_Setpoints_ResSleepHeatSpUsers can set the residential heat setpoint in wake state.°FWrite
AV2465Cfg_Setpoints_ResSleepCoolSpUsers can set the residential cool setpoint in wake state.°FWrite
AV2466Cfg_Setpoints_ResCustomHeatSpUsers can set the residential heat setpoint in wake state.°FWrite
AV2467Cfg_Setpoints_ResCustomCoolSpUsers can set the residential cool setpoint in wake state.°FWrite
AV2468Cfg_Setpoints_ResVacationHeatSpUsers can set the residential heat setpoint in wake state.°FWrite
AV2469Cfg_Setpoints_ResVacationCoolSpUsers can set the residential cool setpoint in wake state.°FWrite
AV2509Cfg_Setpoints_HospTargetSPUsers can set the target setpoint in hospitality°FWrite
AV2510Cfg_Setpoints_HospOccuDiffAbsValUsers can set the differential value of the target setpoint in the occupied state.°FWrite
AV2478Cfg_Setpoints_HospRenUnoccDiffAbsValSetpoint differential for the rented-unoccupied hotel state°FWrite
AV2479Cfg_Setpoints_HospUnrentedHeatSPUsers can set the unrented heat setpoint in hospitality°FWrite
AV2480Cfg_Setpoints_HospUnrentedCoolSPUsers can set the unrented cool setpoint in hospitality°FWrite
AV2516Cfg_Setpoints_HospTargetLowLimThe minimum limit of the target setpoint°FWrite
AV2517Cfg_Setpoints_HospTargetHighLimThe maximum limit of the target setpoint°FWrite
AV2518Cfg_Setpoints_HospAdjustSPThe user adjusts the relative value of the setpoint.°FWrite
AV2481Cfg_Hospitality_DelayTimeBeforePtUser can set delay time before occupancy status change logic.Write
AV2482Cfg_Hospitality_AwakePTPerMinUser can set awake time until unoccupied stateWrite
AV2483Cfg_Hospitality_SleepPTPerMinUser can set sleep time until unoccupied state.Write
AV2484Cfg_Hospitality_AwakeLightLevThUser can set awake light level threshold.Write
AV2532Cfg_Setpoints_HospUnrentedToOccDelTimeDelay from unrented to occupied in hotel modeWrite
AV2025Cfg_PipePurgeTimePipe purge durationminWrite
AV2079Cfg_PipePurgeIntervalPipe purge intervalhWrite
MV2025Cfg_ValveCycleValve cycle typeWrite1=1min/24hours, 2=2min/24hours, 3=Disable
AV2080Cfg_TimeOutHeating run time before the pipe temperature checkhWrite
BV2053Cfg_HybridControlEnableHeat2 pipe single coil heat hybrid control enable flagWrite0=Off, 1=On
BV2054Cfg_HybridControLEnableCool2 pipe single coil cool hybrid control enable flagWrite0=Off, 1=On
AV2101Cfg_CoolTimeOutHeating/cooling run time before the pipe temperature checkhWrite
AV18Cfg_Recovery_MaxCoolRampRateMaximum cooling setpoint rampΔ°FWrite
AV16Cfg_Recovery_MinCoolRampRateMinimum cooling setpoint rampΔ°FWrite
AV17Cfg_Recovery_MaxCoolRampTempOutdoor air temperature at the maximum cool setpoint ramp°FWrite
AV15Cfg_Recovery_MinCoolRampTempOutdoor air temperature at the minimum cool setpoint ramp°FWrite
AV22Cfg_Recovery_MaxHeatRampRateMaximum heating setpoint rampΔ°FWrite
AV20Cfg_Recovery_MinHeatRampRateMaximum heating setpoint rampΔ°FWrite
AV21Cfg_Recovery_MaxHeatRampTempOutdoor air temperature at the maximum heat setpoint ramp°FWrite
AV19Cfg_Recovery_MinHeatRampTempOutdoor air temperature at the minimum heat setpoint ramp°FWrite
AV1723Cfg_FanCoilSupTempHtgSpDischarge air control maximum heating setpoint.°FWrite
AV1724Cfg_FanCoilSupTempClgSpDischarge air control minimum cooling setpoint.°FWrite
BV454Cfg_FanCoilDATSpEnSwitchDischarge air control enable flagWrite0=Off, 1=On
AV2009Cfg_FanCoilDATHeatOffsetDischarge air control heating initial offsetΔ°FWrite
AV2010Cfg_FanCoilDATCoolOffsetDischarge air control cooling initial offsetΔ°FWrite
AV2011Cfg_DaT_Ctrl_Cool_TrDischarge air control cooling throttling rangeΔ°FWrite
AV2012Cfg_DaT_Ctrl_Cool_ItDischarge air control cooling integral timesWrite
AV2014Cfg_DaT_Ctrl_Heat_TrDischarge air control heating throttling rangeΔ°FWrite
AV2015Cfg_DaT_Ctrl_Heat_ItDischarge air control heating integral timesWrite
AV23Cfg_LocalSensCalOffset_TempLocal onboard temperature sensor calibration offsetΔ°FWrite
AV103Cfg_LocalSensCalOffset_HumLocal onboard humidity sensor calibration offset%RHWrite
AV24Cfg_SylkCalOffset_SylkBus2TempTR40_2/ TR-21 temperature calibration offsetΔ°FWrite
AV25Cfg_SylkCalOffset_SylkBus2RHTR40_2 humidity calibration offset%RHWrite
AV26Cfg_SylkCalOffset_SylkBus3TempTR40_3 temperature calibration offsetΔ°FWrite
AV27Cfg_SylkCalOffset_SylkBus4TempTR40_4 temperature calibration offsetΔ°FWrite
AV28Cfg_SylkCalOffset_SylkBus5TempTR40_5 Temperature calibration offsetΔ°FWrite
AV29Cfg_SylkCalOffset_SylkBus8TempC7400S outdoor air temperature calibration offset.Δ°FWrite
AV30Cfg_SylkCalOffset_SylkBus8RHC7400S outdoor air humidity calibration offset.%RHWrite
AV31Cfg_SylkCalOffset_SylkBus10TempC7400S Discharge Air Temperature calibration offsetΔ°FWrite
AV32Cfg_SylkCalOffset_SylkBus10RHC7400S Discharge Air Humidity calibration offset%RHWrite
AV2512Cfg_LocalSensCalOffset_CO2Local onboard CO2 sensor calibration offset.Write
AV2502Cfg_SylkCalOffset_SylkBus6TempTR100 Em TR75 temperature calibration offset.Δ°FWrite
AV2503Cfg_SylkCalOffset_SylkBus6RHTR100 Em TR75 humidity calibration offset.Write
MV2032Cfg_Sylk_SylkBus2TypeSylk bus addr-2 device typeWrite1=TR40, 2=TR50
MV85Cfg_Sylk_SylkBus2EnSylk bus addr-2 device enable/ disableWrite1=NotConfigured, 2=TempOnly, 3=TempHum, 4=TempHumCO2, 5=TempCO2
BV147Cfg_Sylk_SylkBus3EnSylk bus addr-3 device enable/ disableWrite0=Disable, 1=Enable
BV148Cfg_Sylk_SylkBus4EnSylk bus addr-4 device enable/ disableWrite0=Disable, 1=Enable
BV149Cfg_Sylk_SylkBus5EnSylk bus addr-5 device enable/ disableWrite0=Disable, 1=Enable
BV151Cfg_Sylk_SylkBus8EnSylk bus addr-8 device enable/ disable.Write0=Disable, 1=Enable
BV153Cfg_Sylk_SylkBus10EnSylk bus addr-10 device enable/ disableWrite0=Disable, 1=Enable
MV86Cfg_Sylk_SylkBus6EnSylk bus addr-6 device enable/ disable.Write1=NotConfigured, 2=TempOnly, 3=TempHum
MV8Cfg_Thermostat_SysSwitchSystem switch: changes the unit operating modeWrite1=Auto, 2=Cool, 3=Heat, 4=Ventilation, 5=Off, 6=Emergency heat
AV10Cfg_Thermostat_BypOverrideTimeUnoccupied override timeminWrite
AV102Cfg_Thermostat_TempOffSpLimitThis point is used to limit the range of user adjustable setpoint.Δ°FWrite
AV2023Cfg_Thermostat_SystemConfigTo limit available user configurable options. BIT 3 Off must be set as 1.Write
BV135Cfg_Thermostat_OverrideThermostat bypass overrideWrite0=OverrideOff, 1=OverrideOn
MV2035Cfg_TstatOverrideTypeThermostat override typeWrite1=Permanent, 2=Temporary
AV12Cfg_Thermostat_MinCoolSpMinimum cool setpoint of thermostat.°FWrite
AV13Cfg_Thermostat_MaxHeatSpMaximum heat setpoint of thermostat.°FWrite
AV2005no_mstpHeaderCrcErrorThe number of header CRC errors in received framesRead
AV2006no_mstpDataCrcErrThe number of data CRC errors in received framesRead
BV174ni_mstpClearErrWrite to 1 and then 0 will clear header CRC and data CRC count.Write0=Unclear, 1=Clear
AV2455no_WifiRssi(ApplicableonlytoTC320B-G/TC320C-Gthermostats.)WiFi RSSI (Received Signal Strength Indicator) value.Read
AV1ni_NetTUNCOSTUNCOS is the difference between the future change in event & current event in minutes.minWrite
MVmin3ni_ApplicationModeApplication mode from the network; not kept over a power cycleWrite1=Auto, 2=Cool, 3=Heat, 4=FanOnly, 5=Off, 6=EmergencyHeat
BV1ni_BypassStateNet bypass input to enable bypass timerWrite0=Disable, 1=Enable
MVmin6ni_OccupancySensorStateNetwork occupancy sensor stateWrite1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=NoOverride
AV89ni_OutdoorTempOutdoor air temperatue from network input.°FWrite
AV194ni_OutdoorHumOutdoor air humidity from network input.%RHWrite
BV4ni_ShutdownStateSystem shutdown input from network.Write0=Normal, 1=Shutdown
AV80ni_SpaceRHSpace humidity network input%RHWrite
AV104ni_SpaceTempSpace temperature network input°FWrite
BV25ni_WSHPEnableStateWater source heat pump enable shared from the networkWrite0=WSHPSystemEnable, 1=WSHPSystemDisable
MV38ni_RunTimeResetRuntime accumulate reset network input.Write1=Normal, 2=FanReset, 3=CoolReset, 4=HeatingReset
AV2024ni_DATempDischarge air temperature network input°FWrite
MV2012ni_PipeTempModePipe temperature mode network inputWrite1=None, 2=Cool, 3=Heat
MV1ni_NetSchCurrentStateSchedule state from the network (occupied, unoccupied, standby, rented)Write1=Occupied_Wake, 2=Unoccupied_Away, 3=Bypass_Return, 4=Standby_Sleep, 5=NoOverride, 6=None_Custom, 7=None_Vacation, 8=None_Unrented
MV2ni_NetSchNextStateNext schedule state from network.Write1=Occupied_Wake, 2=Unoccupied_Away, 3=Bypass_Return, 4=Standby_Sleep, 5=NoOverride, 6=None_Custom, 7=None_Vacation, 8=None_Unrented
BV2ni_ADREnUsers can set ADR functions remotely.Write0=Disable, 1=Enable
AV2511ni_SpaceCO2Space CO2 network input.Write
BV159Cfg_NetOccSenFailDetEnOccupancy sensor fail detect enableWrite0=Disable, 1=Enable
AV262Cfg_NetOccSenFailFalbckOccupancy sensor fail detect fallbackWrite
MV2021Cfg_NetOccSenFailFxdValOccupancy sensor fail detect fallback valueWrite1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=NoOverride
AV263Cfg_NetOccSenFailDetDlyOccupancy sensor fail detect delaysWrite
BV164Cfg_NetShtdwnFailDetEnShut down fail detect enableWrite0=Disable, 1=Enable
AV273Cfg_NetShtdwnFailFalbckShut down fail detect fallbackWrite
BV165Cfg_NetShtdwnFailFxdValShut down fail detect fallback valueWrite0=Normal, 1=Shutdown
AV274Cfg_NetShtdwnFailDetDlyShut down fail detect delaysWrite
BV169Cfg_NetWSHPEnStFailDetEnNetwork failure detection for the shared heat pump enableWrite0=Disable, 1=Enable
AV284Cfg_NetWSHPEnStFailFalbckNetwork Fail Detection Fall back value. (TC3xxB models only)Write
BV170Cfg_NetWSHPEnStFailFxdValFallback value used when that network input failsWrite0=WSHPSystemEnable, 1=WSHPSystemDisable
AV285Cfg_NetWSHPEnStFailDetDlyNetwork Fail Detection delay in seconds. (TC3xxB models only)sWrite
BV2073Cfg_NetPipeTempModFailDetEnPipe temp mode fail detect enable.Write0=Disable, 1=Enable
AV2476Cfg_NetPipeTempModFailFalbckPipe Temp Mode Fail Detect FallbackWrite
MV2064Cfg_NetPipeTempModFailFxdValPipe Temp Mode Fail Detect Fallback ValueWrite1=None, 2=Cool, 3=Heat
AV2477Cfg_NetPipeTempModFailDetDlyPipe Temp Mode Fail Detect DelayWrite
BV2087Cfg_NetFailDetEnNetwork sensor fail detect enable.Write0=Disable, 1=Enable
AV2507Cfg_NetFailFalbckNetwork sensor fail detect fallback.Write
AV2508Cfg_NetFailDetDlyNetwork sensor fail detect delay.Write
BV6ni_ServiceModeEnService mode for commissioning; shuts down all equipmentWrite0=NoOverride, 1=Service
MV2026ni_ServiceFanFan speed command while in service modeWrite1=0ff, 2=On, 3=Low, 4=Medium, 5=High
AV85ni_ServiceFanSpeedFan speed configuration network input for variable speed fan when service mode is enabled.%Write
BV2042ni_ServiceHeatOnOffOn/Off heat valve status network input when service mode is enabled.Write0=Off, 1=On
BV2043ni_ServiceCoolOnOffOn/Off cool valve status network input when service mode is enabled.Write0=Off, 1=On
MV2022ni_ServiceHeatFloatingFloating heat valve status network input when service mode is enabled. (TC3xxB models only)Write1=Off, 2=Open, 3=Close
MV2023ni_ServiceCoolFloatingFloating cool valve status network input when service mode is enabled. (TC3xxB models only)Write1=Off, 2=Open, 3=Close
AV2076ni_ServiceModulatingHeatModulating heat valve status network input when service mode is enabled.%Write
AV2077ni_ServiceModulatingCoolModulating cool valve status network input when service mode is enabled.%Write
AV2078ni_ServiceSixWayValveSix way valve status network input when service mode is enabled.Write
BV2044ni_ServiceAuxHeatAuxiliary heat status network input when service mode is enabled.Write0=Off, 1=On
BV2045ni_ServiceChangeOverChangeover valve status when service mode is enabledWrite0=Off, 1=On
BV19ni_ServiceHeatStage1Heat stage 1 command while in service modeWrite0=Off, 1=On
BV2046ni_ServiceCoolStage1Cool stage 1 status network input when service mode is enabled.Write0=Off, 1=On
BV2047ni_ServiceValveStage1Modulating valve stage 1 status network input when service mode is enabled.Write0=Off, 1=On
BV2048ni_ServiceValveOnOffModulating valve status network input when service mode is enabled.Write0=Off, 1=On
MV2024ni_ServiceValveFloatingFloating valve status network input when service mode is enabled. (TC3xxB models only)Write1=Off, 2=Open, 3=Close
AV2086ni_ServiceValveModulatingModulating valve status network input when service mode is enabled.Write
BV22ni_ServiceRevVlvCmdReversing valve status when service mode is enable. (TC3xxB models only)Write0=Off, 1=On
BV2058ni_ServiceWaterFlowValveCmdWaterFlow valve status when service mode is enable. (TC3xxB models only)Write0=Off, 1=On
BV23ni_ServiceSimpleDehCmdDehumidifier status when service mode is enable. (TC3xxB models only)Write0=Off, 1=On
BV24ni_ServiceSimpleHumCmdHumidifier status when service mode is enable. (TC3xxB models only)Write0=Off, 1=On
BV20ni_ServiceHeatStage2Conventional heat stage 2 status network input when service mode is enabled (TC3xxB models only)Write0=Off, 1=On
BV2070ni_ServiceCoolStage2Conventional Cool stage2 status network input when service mode is enabled. (TC3xxB models only)Write0=Off, 1=On
BV2082ni_ServiceCO2BinaryOutputCO2 binary output status when service mode is enable.Write0=Off, 1=On
AV2497ni_ServiceCO2AnalogOutputCO2 analog output status when service mode is enable.Write
BV2083ni_ServiceLightingControlLighting control output status when service mode is enable.Write0=Off, 1=On
BV2084ni_ServiceOccupancyOutputOccupancy output status when service mode is enable.Write0=Off, 1=On
CAL1CalendarWrite
SCH2OccScheduleOccupancy scheduleWrite
Object ID lookup: Honeywell TC300 Commercial Thermostats point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)

How many BACnet points does the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) have?

This list has 531 BACnet objects: 4 analog inputs, 9 analog outputs, 253 analog values, 9 binary inputs, 26 binary outputs, 116 binary values, 1 calendar, 1 schedule, 111 multi-state values, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) BACnet points are writable?

378 of the 531 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) BACnet documentation?

Honeywell does not publish it on its own website. This list comes from TC300 Thermostats BACnet Integration Guide (31-00646-05), revision Rev. 11-25, a copy hosted by SupplyHouse.com at https://s3.amazonaws.com/s3.supplyhouse.com/product_files/Honeywell_T300_Series_Technical_Guide_2025.pdf. Ask Honeywell or its representative for the current revision.

What are the minimum BACnet points to integrate the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)?

Start with MV 3 ni_ApplicationMode (System mode: auto, cool, heat, fan only, off); MV 6 ni_OccupancySensorState (Network occupancy: occupied, unoccupied, bypass, standby); AV 7 Cfg_Setpoints_OccHeatSp (Occupied heating setpoint); AV 4 Cfg_Setpoints_OccCoolSp (Occupied cooling setpoint); MV 583 Cfg_FanCoilManualSpeedSel (Fan speed: auto, low, medium, high); MV 2014 no_EffOccState (Effective occupancy state); AV 2001 no_SpaceTemp (Space temperature in use); AV 2003 no_EffHeatSp (Effective heating setpoint); AV 2004 no_EffCoolSp (Effective cooling setpoint); BV 2035 no_GenericAlarm (Any alarm active).

How do I enable BMS control of the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)?

The thermostat runs on its own; the BMS steers it through the ni_ network inputs (application mode, occupancy, schedule state, shutdown BV 4). ni_ApplicationMode is not kept over a power cycle.

Does the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G) need a BACnet heartbeat or have a communication timeout?

Network fail detect: when a bound network input is not updated within its fail-detect delay (0-3600 s), it falls back to Invalid, the last good value or a fixed value. Per-input enable, fallback and delay objects exist for occupancy (BV 159, AV 262, MV 2021, AV 263), shutdown (BV 164, AV 273, BV 165, AV 274) and network sensors (BV 2087, AV 2507, AV 2508).

Can the BMS supply sensor values to the Honeywell TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)?

Network inputs: ni_SpaceTemp AV 104, ni_SpaceRH AV 80, ni_SpaceCO2 AV 2511, ni_OutdoorTemp AV 89, ni_OutdoorHum AV 194, ni_DATemp AV 2024 and ni_PipeTempMode MV 2012. Network sensor configuration decides whether these are used.

How do I check these points on the real TC300 Commercial Thermostats (TC300B-G / TC300C-G / TC320B-G / TC320C-G)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Honeywell BACnet points lists

Source: TC300 Thermostats BACnet Integration Guide · 31-00646-05 · rev. Rev. 11-25. Object names, instances and units are reproduced as published; descriptions are our own.