Other equipment (BACnet relay / I/O module) · BACnet points list

Functional Devices RIBTW24B-BCAO BACnet relay with analog output BACnet points list

Updated 12 November 2026

Short answer

A BACnet MS/TP relay module with one relay (BO1), one analog output in percent (AO1), one binary input and one analog input. All four objects are plain I/O; there is no on-board control logic.

This page lists 4 BACnet objects for the Functional Devices RIBTW24B-BCAO BACnet relay with analog output — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Functional Devices’s own free documentation, linked below.

Manufacturer
Functional Devices
Model
RIBTW24B-BCAO BACnet relay with analog output
Equipment
Other equipment (BACnet relay / I/O module)
Equipment type
Other equipment
BACnet objects
4 (2 writable)
Transport
BACnet MS/TP
Firmware
Firmware 2.04, application 1.5 (the device object table prints 1.3)
Default device instance
277000
Also known as
RIBTW24B-BCAO, BACnet RIB analog output
Source document
RIBTW24B-BCAO PICS v1.5 · rev. 2017-05-17
Download CSV 4 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Functional Devices’s current documentation and the live device before use. Not official Functional Devices information. Terms of use.

BMS integration notes: Functional Devices RIBTW24B-BCAO BACnet relay with analog output

Integration in brief

Write BO1 for the relay and AO1 for the 0-100 % output; read BI1 and AI1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1BO1Relay commandCommand
AO 1AO1Analog output, 0-100 %Command
BI 1BI1Binary input statusRead
AI 1AI1Analog input valueRead

Network setup

Functional Devices RIBTW24B-BCAO BACnet relay with analog output BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

4 of 4 shown
Type
Access
Show
Functional Devices RIBTW24B-BCAO BACnet relay with analog output BACnet Points List
DescriptionStates
AImin1AI1Analog input: 0-5/0-10 Vdc or 10K T2/T3 thermistorany BACnet unit (writable)Read
AOmin1AO1Analog output, 0-100 %%Command
BImin1BI1Binary inputReadInactive/Active text user-set
BOmin1BO1Relay outputCommand
Object ID lookup: Functional Devices RIBTW24B-BCAO BACnet relay with analog output point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RIBTW24B-BCAO BACnet relay with analog output and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Functional Devices RIBTW24B-BCAO BACnet relay with analog output

How many BACnet points does the Functional Devices RIBTW24B-BCAO BACnet relay with analog output have?

This list has 4 BACnet objects: 1 analog input, 1 analog output, 1 binary input, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Functional Devices RIBTW24B-BCAO BACnet relay with analog output BACnet points are writable?

2 of the 4 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Functional Devices RIBTW24B-BCAO BACnet relay with analog output BACnet documentation?

The source is RIBTW24B-BCAO PICS v1.5, revision 2017-05-17, published free by Functional Devices at https://www.functionaldevices.com/sfsites/c/cms/delivery/media/MCMZAXTTRWMFFHVOP2XN54A2ANAI.

What are the minimum BACnet points to integrate the Functional Devices RIBTW24B-BCAO BACnet relay with analog output?

Start with BO 1 BO1 (Relay command); AO 1 AO1 (Analog output, 0-100 %); BI 1 BI1 (Binary input status); AI 1 AI1 (Analog input value).

How do I check these points on the real RIBTW24B-BCAO BACnet relay with analog output?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Functional Devices BACnet points lists

Source: RIBTW24B-BCAO PICS v1.5 · rev. 2017-05-17. Object names, instances and units are reproduced as published; descriptions are our own.