- PSH600-UPS-BC / PSH550-UPS-BC UPS power supply
Other equipment (UPS power supply) · BACnet points list
Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet points list
Updated 12 November 2026
A UPS power supply with a read-only BACnet MS/TP interface: two binary inputs report whether it is running on line or battery and whether a battery is connected, and four analog inputs give load, VA, battery capacity and time remaining.
This page lists 6 BACnet objects for the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Functional Devices’s own free documentation, linked below.
- Manufacturer
- Functional Devices
- Model
- PSH600-UPS-BC / PSH550-UPS-BC UPS power supply
- Equipment
- Other equipment (UPS power supply)
- Equipment type
- Other equipment
- BACnet objects
- 6 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- Firmware 2.04, application 1.5 (PSH600) / 1.09 (PSH550)
- Default device instance
- 277000
- Also known as
- PSH600-UPS-BC, PSH550-UPS-BC, PSH600-UPS, PSH550-UPS
- Source document
- PSH600-UPS-BC PICS v1.5 · rev. 2017-07-07
Reference only, provided as-is: verify against Functional Devices’s current documentation and the live device before use. Not official Functional Devices information. Terms of use.
BMS integration notes: Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply
Read-only device: poll BI1 for on-battery, BI2 for battery present, and AI3/AI4 for remaining capacity and run time.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 1 | BI1 | On battery when 1 (UPS) | Read |
| BI 2 | BI2 | Battery connected | Read |
| AI 3 | AI3 | Battery capacity, % | Read |
| AI 4 | AI4 | Battery time remaining, min | Read |
| AI 1 | AI1 | Load, % | Read |
Network setup
- The PICS prints the device object ID default as DE277000 (vendor ID 277); it is writable.
- MS/TP master; baud rates are listed in the PICS. Max_Master defaults to 127.
Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | BI1 | Power source: line or UPS battery | Read | 0=Line, 1=UPS | |
| BImin | 2 | BI2 | Battery connected | Read | 0=Not Connected, 1=Connected | |
| AImin | 1 | AI1 | UPS percent load | % | Read | |
| AI | 2 | AI2 | VA load (0-600 VA; 0-550 on PSH550) | VA | Read | |
| AImin | 3 | AI3 | UPS battery capacity | % | Read | |
| AImin | 4 | AI4 | Battery time remaining | min | Read |
No points match these filters.
Object ID lookup: Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply point IDs by name
Integration notes
- Object names are user-writable and the PICS prints no factory default name, so each object is listed by its printed ID (BI1, AI1...). Names are limited to 4 characters.
- The PSH550-UPS-BC PICS (v1.9, 8 Nov 2016) prints the same six objects; only the AI2 range differs (0-550 VA vs 0-600 VA).
- AI meanings come from each object's Device_Type text (UPS Percent Load, VA Load, UPS Batt Capacity, Time Remaining).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PSH600-UPS-BC / PSH550-UPS-BC UPS power supply and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply
How many BACnet points does the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply have?
This list has 6 BACnet objects: 4 analog inputs, 2 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet documentation?
The source is PSH600-UPS-BC PICS v1.5, revision 2017-07-07, published free by Functional Devices at https://www.functionaldevices.com/sfsites/c/cms/delivery/media/MCUSNFT77CGBGENORBIKEAKTJJKI.
What are the minimum BACnet points to integrate the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply?
Start with BI 1 BI1 (On battery when 1 (UPS)); BI 2 BI2 (Battery connected); AI 3 AI3 (Battery capacity, %); AI 4 AI4 (Battery time remaining, min); AI 1 AI1 (Load, %).
How do I check these points on the real PSH600-UPS-BC / PSH550-UPS-BC UPS power supply?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Functional Devices BACnet points lists
- Other equipment (BACnet relay / I/O module)
Functional Devices RIB[*]24B-BCAI BACnet relay with analog input
Functional Devices RIB[*]24B-BCAI BACnet MS/TP relay with one analog input and two binary inputs.
Also known as: RIB24B-BCAI, RIB[*]24B-BCAI, BACnet RIB analog input - Other equipment (BACnet relay / I/O module)
Functional Devices RIBMNW24B-44-BC 4-input / 4-relay module
Functional Devices RIBMNW24B-44-BC BACnet MS/TP module with four binary inputs and four relays.
Also known as: RIBMNW24B-44-BC, RIBMW24B-44BC, RIBMNW24B-44 - Other equipment (BACnet input module)
Functional Devices RIBMNWD12-BC 12-input module with pulse counters
Functional Devices RIBMNWD12-BC 12-point binary input module with two pulse accumulators; RIBMNWD12-BCDI is the 12-input version without accumulators.
Also known as: RIBMNWD12-BC, RIBMNWD12-BCDI, RIBMNWD12 - Other equipment (BACnet relay / fan safety module)
Functional Devices RIBMNWLB-7-BC fan safety circuit / relay module
Functional Devices RIBMNWLB-7-BC (also RIBTWLB-7-BC, RIBTWLB-7-BC-N4) 2-relay, 8-input module that runs as a fan safety circuit by default.
Also known as: RIBMNWLB-7-BC, RIBTWLB-7-BC, RIBTWLB-7-BC-N4 - Other equipment (BACnet relay / I/O module)
Functional Devices RIBTW240xB-BC enclosed BACnet relay (1 relay, 1 input)
Functional Devices RIBTW240xB-BC enclosed BACnet MS/TP relays with one relay output and one binary input.
Also known as: RIBTW2401B-BC, RIBTW2402B-BC, RIBTW240xB-BC, BACnet RIB relay - Other equipment (BACnet relay / I/O module)
Functional Devices RIBTW24B-BCAO BACnet relay with analog output
Functional Devices RIBTW24B-BCAO BACnet MS/TP relay with one analog output, one analog input and one binary input.
Also known as: RIBTW24B-BCAO, BACnet RIB analog output - Other equipment (BACnet relay / I/O module)
Functional Devices RIBTWX240xB-BC / RIBMNWX240xB-BC BACnet relay (1 relay, 2 inputs)
Functional Devices RIBTWX240xB-BC (enclosed) and RIBMNWX240xB-BC (board) BACnet MS/TP relays with one relay output and two binary inputs.
Also known as: RIBTWX240xB-BC, RIBMNWX240xB-BC, RIBxW240xB-BC, RIBTWX2401B-BC, BACnet RIB relay 2 inputs
Source: PSH600-UPS-BC PICS v1.5 · rev. 2017-07-07. Object names, instances and units are reproduced as published; descriptions are our own.