Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet points list

Updated 12 November 2026

Short answer

A UPS power supply with a read-only BACnet MS/TP interface: two binary inputs report whether it is running on line or battery and whether a battery is connected, and four analog inputs give load, VA, battery capacity and time remaining.

This page lists 6 BACnet objects for the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Functional Devices’s own free documentation, linked below.

Manufacturer
Functional Devices
Model
PSH600-UPS-BC / PSH550-UPS-BC UPS power supply
Equipment
Other equipment (UPS power supply)
Equipment type
Other equipment
BACnet objects
6 (0 writable)
Transport
BACnet MS/TP
Firmware
Firmware 2.04, application 1.5 (PSH600) / 1.09 (PSH550)
Default device instance
277000
Also known as
PSH600-UPS-BC, PSH550-UPS-BC, PSH600-UPS, PSH550-UPS
Source document
PSH600-UPS-BC PICS v1.5 · rev. 2017-07-07
Download CSV 6 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Functional Devices’s current documentation and the live device before use. Not official Functional Devices information. Terms of use.

BMS integration notes: Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply

Integration in brief

Read-only device: poll BI1 for on-battery, BI2 for battery present, and AI3/AI4 for remaining capacity and run time.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 1BI1On battery when 1 (UPS)Read
BI 2BI2Battery connectedRead
AI 3AI3Battery capacity, %Read
AI 4AI4Battery time remaining, minRead
AI 1AI1Load, %Read

Network setup

Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

6 of 6 shown
Type
AnalogBinary
Show
Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet Points List
DescriptionStates
BImin1BI1Power source: line or UPS batteryRead0=Line, 1=UPS
BImin2BI2Battery connectedRead0=Not Connected, 1=Connected
AImin1AI1UPS percent load%Read
AI2AI2VA load (0-600 VA; 0-550 on PSH550)VARead
AImin3AI3UPS battery capacity%Read
AImin4AI4Battery time remainingminRead
Object ID lookup: Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PSH600-UPS-BC / PSH550-UPS-BC UPS power supply and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply

How many BACnet points does the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply have?

This list has 6 BACnet objects: 4 analog inputs, 2 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply BACnet documentation?

The source is PSH600-UPS-BC PICS v1.5, revision 2017-07-07, published free by Functional Devices at https://www.functionaldevices.com/sfsites/c/cms/delivery/media/MCUSNFT77CGBGENORBIKEAKTJJKI.

What are the minimum BACnet points to integrate the Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply?

Start with BI 1 BI1 (On battery when 1 (UPS)); BI 2 BI2 (Battery connected); AI 3 AI3 (Battery capacity, %); AI 4 AI4 (Battery time remaining, min); AI 1 AI1 (Load, %).

How do I check these points on the real PSH600-UPS-BC / PSH550-UPS-BC UPS power supply?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Functional Devices BACnet points lists

Source: PSH600-UPS-BC PICS v1.5 · rev. 2017-07-07. Object names, instances and units are reproduced as published; descriptions are our own.