Other equipment (BACnet input module) · BACnet points list
Functional Devices RIBMNWD12-BC 12-input module with pulse counters BACnet points list
Updated 12 November 2026
A BACnet MS/TP input module with twelve binary inputs and two Accumulator objects for pulse counting. The RIBMNWD12-BCDI version prints the same twelve BIs but no ACC objects.
This page lists 14 BACnet objects for the Functional Devices RIBMNWD12-BC 12-input module with pulse counters — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Functional Devices’s own free documentation, linked below.
- Manufacturer
- Functional Devices
- Model
- RIBMNWD12-BC 12-input module with pulse counters
- Equipment
- Other equipment (BACnet input module)
- Equipment type
- Other equipment
- BACnet objects
- 14 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- Firmware 2.04, application 2.15
- Default device instance
- 277000
- Also known as
- RIBMNWD12-BC, RIBMNWD12-BCDI, RIBMNWD12
- Source document
- RIBMNWD12-BC PICS v2.15 · rev. 2016-06-24
Reference only, provided as-is: verify against Functional Devices’s current documentation and the live device before use. Not official Functional Devices information. Terms of use.
BMS integration notes: Functional Devices RIBMNWD12-BC 12-input module with pulse counters
Read the twelve BIs; on the -BC version also read ACC1/ACC2 and set Scale/Prescale/Units to match the pulse meter.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 1 | BI1 | Input 1 status | Read |
| BI 2 | BI2 | Input 2 status | Read |
| ACC 1 | ACC1 | Pulse count 1 (-BC only) | Read |
| ACC 2 | ACC2 | Pulse count 2 (-BC only) | Read |
Network setup
- The PICS prints the device object ID default as DEV277000 (vendor ID 277); it is writable.
- MS/TP master; baud rates are listed in the PICS. Max_Master defaults to 127.
Watch out for
- Accumulator Max_Pres_Value is 65535.
Functional Devices RIBMNWD12-BC 12-input module with pulse counters BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | BI1 | Binary input 1 | Read | 0=OFF, 1=ON | |
| BImin | 2 | BI2 | Binary input 2 | Read | 0=OFF, 1=ON | |
| BI | 3 | BI3 | Binary input 3 | Read | 0=OFF, 1=ON | |
| BI | 4 | BI4 | Binary input 4 | Read | 0=OFF, 1=ON | |
| BI | 5 | BI5 | Binary input 5 | Read | 0=OFF, 1=ON | |
| BI | 6 | BI6 | Binary input 6 | Read | 0=OFF, 1=ON | |
| BI | 7 | BI7 | Binary input 7 | Read | 0=OFF, 1=ON | |
| BI | 8 | BI8 | Binary input 8 | Read | 0=OFF, 1=ON | |
| BI | 9 | BI9 | Binary input 9 | Read | 0=OFF, 1=ON | |
| BI | 10 | BI10 | Binary input 10 | Read | 0=OFF, 1=ON | |
| BI | 11 | BI11 | Binary input 11 | Read | 0=OFF, 1=ON | |
| BI | 12 | BI12 | Binary input 12 | Read | 0=OFF, 1=ON | |
| ACCmin | 1 | ACC1 | Pulse counter 1 (0-65535, scale/prescale writable) | any BACnet unit (writable) | Read | |
| ACCmin | 2 | ACC2 | Pulse counter 2 (0-65535, scale/prescale writable) | any BACnet unit (writable) | Read |
No points match these filters.
Object ID lookup: Functional Devices RIBMNWD12-BC 12-input module with pulse counters point IDs by name
Integration notes
- Object names are user-writable and the PICS prints no factory default name, so each object is listed by its printed ID (BI1, ACC1...). Names are limited to 4 characters.
- Binary input text defaults to OFF/ON and is writable; polarity can be reversed.
- ACC1-ACC2 have a Max_Pres_Value of 65535; Scale, Prescale and Units are writable.
- RIBMNWD12-BCDI (PICS v2.15, same date, media MCQIAIDEZHPNDEDFKXCSELY733CM) has BI1-BI12 only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RIBMNWD12-BC 12-input module with pulse counters and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Functional Devices RIBMNWD12-BC 12-input module with pulse counters
How many BACnet points does the Functional Devices RIBMNWD12-BC 12-input module with pulse counters have?
This list has 14 BACnet objects: 12 binary inputs, 2 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Functional Devices RIBMNWD12-BC 12-input module with pulse counters BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Functional Devices RIBMNWD12-BC 12-input module with pulse counters BACnet documentation?
The source is RIBMNWD12-BC PICS v2.15, revision 2016-06-24, published free by Functional Devices at https://www.functionaldevices.com/sfsites/c/cms/delivery/media/MCN523AYYAJRFPJKAX2WADISOQ4Q.
What are the minimum BACnet points to integrate the Functional Devices RIBMNWD12-BC 12-input module with pulse counters?
Start with BI 1 BI1 (Input 1 status); BI 2 BI2 (Input 2 status); ACC 1 ACC1 (Pulse count 1 (-BC only)); ACC 2 ACC2 (Pulse count 2 (-BC only)).
How do I check these points on the real RIBMNWD12-BC 12-input module with pulse counters?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Functional Devices BACnet points lists
- Other equipment (UPS power supply)
Functional Devices PSH600-UPS-BC / PSH550-UPS-BC UPS power supply
Functional Devices PSH600-UPS-BC and PSH550-UPS-BC 24 V UPS power supplies with BACnet MS/TP.
Also known as: PSH600-UPS-BC, PSH550-UPS-BC, PSH600-UPS, PSH550-UPS - Other equipment (BACnet relay / I/O module)
Functional Devices RIB[*]24B-BCAI BACnet relay with analog input
Functional Devices RIB[*]24B-BCAI BACnet MS/TP relay with one analog input and two binary inputs.
Also known as: RIB24B-BCAI, RIB[*]24B-BCAI, BACnet RIB analog input - Other equipment (BACnet relay / I/O module)
Functional Devices RIBMNW24B-44-BC 4-input / 4-relay module
Functional Devices RIBMNW24B-44-BC BACnet MS/TP module with four binary inputs and four relays.
Also known as: RIBMNW24B-44-BC, RIBMW24B-44BC, RIBMNW24B-44 - Other equipment (BACnet relay / fan safety module)
Functional Devices RIBMNWLB-7-BC fan safety circuit / relay module
Functional Devices RIBMNWLB-7-BC (also RIBTWLB-7-BC, RIBTWLB-7-BC-N4) 2-relay, 8-input module that runs as a fan safety circuit by default.
Also known as: RIBMNWLB-7-BC, RIBTWLB-7-BC, RIBTWLB-7-BC-N4 - Other equipment (BACnet relay / I/O module)
Functional Devices RIBTW240xB-BC enclosed BACnet relay (1 relay, 1 input)
Functional Devices RIBTW240xB-BC enclosed BACnet MS/TP relays with one relay output and one binary input.
Also known as: RIBTW2401B-BC, RIBTW2402B-BC, RIBTW240xB-BC, BACnet RIB relay - Other equipment (BACnet relay / I/O module)
Functional Devices RIBTW24B-BCAO BACnet relay with analog output
Functional Devices RIBTW24B-BCAO BACnet MS/TP relay with one analog output, one analog input and one binary input.
Also known as: RIBTW24B-BCAO, BACnet RIB analog output - Other equipment (BACnet relay / I/O module)
Functional Devices RIBTWX240xB-BC / RIBMNWX240xB-BC BACnet relay (1 relay, 2 inputs)
Functional Devices RIBTWX240xB-BC (enclosed) and RIBMNWX240xB-BC (board) BACnet MS/TP relays with one relay output and two binary inputs.
Also known as: RIBTWX240xB-BC, RIBMNWX240xB-BC, RIBxW240xB-BC, RIBTWX2401B-BC, BACnet RIB relay 2 inputs
Source: RIBMNWD12-BC PICS v2.15 · rev. 2016-06-24. Object names, instances and units are reproduced as published; descriptions are our own.