 "manufacturer": "Functional Devices",
 "manufacturer_slug": "functional-devices",
 "model": "RIBTW24B-BCAO BACnet relay with analog output",
 "model_slug": "ribtw24b-bcao",
 "aliases": [
  "RIBTW24B-BCAO",
  "BACnet RIB analog output"
 ],
 "equipment_type": "Other equipment (BACnet relay / I/O module)",
 "applies_to": "Functional Devices RIBTW24B-BCAO BACnet MS/TP relay with one analog output, one analog input and one binary input.",
 "summary": "A BACnet MS/TP relay module with one relay (BO1), one analog output in percent (AO1), one binary input and one analog input. All four objects are plain I/O; there is no on-board control logic.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Firmware 2.04, application 1.5 (the device object table prints 1.3)",
 "default_device_instance": 277000,
 "access_inferred": false,
 "notes": [
  "Object names are user-writable and the PICS prints no factory default name, so each object is listed by its printed ID (BI1, BO1...).",
  "The PICS prints the AO identifier as \"A01\"; it is Analog Output 1.",
  "AO1 and BO1 have 16-level priority arrays; AO1 is fixed at 0-100 %."
 ],
 "source": {
  "title": "RIBTW24B-BCAO PICS v1.5",
  "doc_number": null,
  "revision_date": "2017-05-17",
  "url": "https://www.functionaldevices.com/sfsites/c/cms/delivery/media/MCMZAXTTRWMFFHVOP2XN54A2ANAI"
 },
 "integration": {
  "summary": "Write BO1 for the relay and AO1 for the 0-100 % output; read BI1 and AI1.",
  "minimum_points": [
   {
    "ref": "BO 1",
    "name": "BO1",
    "why": "Relay command"
   },
   {
    "ref": "AO 1",
    "name": "AO1",
    "why": "Analog output, 0-100 %"
   },
   {
    "ref": "BI 1",
    "name": "BI1",
    "why": "Binary input status"
   },
   {
    "ref": "AI 1",
    "name": "AI1",
    "why": "Analog input value"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The PICS prints the device object ID default as DE277000 (vendor ID 277); it is writable.",
   "MS/TP master; baud rates are listed in the PICS. Max_Master defaults to 127."
  ],
  "gotchas": []
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "AI1",
   "description": "Analog input: 0-5/0-10 Vdc or 10K T2/T3 thermistor",
   "units": "any BACnet unit (writable)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "AO1",
   "description": "Analog output, 0-100 %",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "BI1",
   "description": "Binary input",
   "units": "",
   "access": "R",
   "states": "Inactive/Active text user-set"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "BO1",
   "description": "Relay output",
   "units": "",
   "access": "C",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/functional-devices/ribtw24b-bcao",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}