Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet points list
Updated 12 November 2026
Flexit's overview spreadsheet of the BACnet objects in a ProNordic unit (CS2500 controller with the SP85 BACnet IP module). It has 79 objects: the BMS mode command, operating mode status, temperatures and setpoints, valve and pump outputs, five fan steps per fan, fan readings, filter pressures, fire damper status and A/B/C alarms. Many objects only exist when the matching accessory or configuration is present (marked S, C or A in the list).
This page lists 79 BACnet objects for the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Flexit’s own free documentation, linked below.
- Manufacturer
- Flexit
- Model
- ProNordic with CS2500 controller (SP85 BACnet IP module)
- Equipment
- Air handling unit controller (commercial heat recovery AHU)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 79 (21 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Flexit ProNordic, ProNordic, CS2500, Flexit CS2500, SP85, Kommunikasjonsmodul BACnet IP SP85, Oversikt Bacnet-objekt Flexit ProNordic
Reference only, provided as-is: verify against Flexit’s current documentation and the live device before use. Not official Flexit information. Terms of use.
BMS integration notes: Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)
Write MV 32040 BMS Regulation to run the unit from the BMS (Auto, Off, or Economy/Comfort steps 1-3). Adjust the comfort and economy heating setpoints if needed. Read MV 6080 for the actual operating mode, the outdoor/supply/extract temperatures, the fan values and the A/B/C alarm MVs; MV 19 resets alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 32040 | BMS Regulation | Mode command: 1 Auto, 2 Off, 3-8 Economy/Comfort steps | Write |
| AV 22817 | Setpoint Komfort Heating | Comfort heating setpoint | Write |
| AV 35713 | Setpoint Economi Heating | Economy heating setpoint | Write |
| MV 19 | Reset Alarm (A,B,C) | Alarm reset | Write |
| MV 6080 | Operating mode Operation Aggregate | Actual operating mode (off, comfort, economy, start) | Read |
| AI 45150 | Supply temperature | Supply air temperature | Read |
| AI 53218 | Outdoor temperature | Outdoor air temperature | Read |
| AI 28256 | Extract temperature | Extract air temperature | Read |
| MV 46769 | A-Alarm Danger | A alarm active when 2 | Read |
| MV 38643 | B-Alarm | B alarm active when 2 | Read |
Enable & remote start
MV 32040 BMS Regulation selects Auto (unit follows its own schedule), Off, or a fixed Economy or Comfort fan step from the BMS.
Network setup
- BACnet IP needs the SP85 communication module on the CS2500 controller.
Watch out for
- MV 56125 temperature regulation mode is status only; Flexit says not to change it.
- Several instances are printed twice for different points; confirm against the live unit's object list.
Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 32040 | BMS Regulation | BMS mode command; standard | Write | 1=Auto, 2=Off, 3=Economy St 1, 4=Economy St 2, 5=Economy St 3, 6=Comfort St 1, 7=Comfort St 2, 8=Comfort St 3 | |
| MV | 56125 | Operating mode Temp regulation | Main function; standard; Status only, do not write | Read | 1=Supply, 2=Room/Cascade, 3=Extract/Cascade, 4=Room Summer/Winter, 5=Extract Summer/Winter, 6=Room | |
| MVmin | 6080 | Operating mode Operation Aggregate | Main function; standard | Read | 1=Off, 2=On, 3=Off, 4=Comfort, 5=Economy, 6=After cooling, 7=Start | |
| BV | 32321 | Status AHU | Main function; standard | Read | 2=Configuration mode, 3=Fire, 4=Alarmstopp, 5=Nødstopp, 6=Alarm, 7=Spjeldmotsionering, 8=Manuell, 9=Støttedrift, 10=External regulation, 11=Optimizing, 12=Room unit, 13=Free cooling, 14=BMS, 15=Time schedule, 16=Schedule T, 17=calendar, 18=Service switch | |
| AImin | 53218 | Outdoor temperature | Temperature; standard | °C | Read | |
| AImin | 45150 | Supply temperature | Temperature; standard | °C | Read | |
| AImin | 28256 | Extract temperature | Temperature; standard | °C | Read | |
| AI | 40895 | Exhaust temperature | Temperature; accessory | °C | Read | |
| AI | 40895 | Return water temperature | Temperature; accessory | °C | Read | |
| AI | 20915 | Supply temperature extra sequence | Temperature; accessory | °C | Read | |
| AV | 80 | Min supply temperature (Extract/Cascade regulation) | Temperature; configuration | °C | Write | |
| AV | 5 | Max supply temperature (Extract/Cascade regulation) | Temperature; configuration | °C | Write | |
| AVmin | 35713 | Setpoint Economi Heating | Temperature; standard | °C | Write | |
| AV | 61866 | Setpoint Economi Cooling | Temperature; configuration/accessory | °C | Write | |
| AVmin | 22817 | Setpoint Komfort Heating | Temperature; standard | °C | Write | |
| AV | 8970 | Setpoint Komfort Cooling | Temperature; configuration/accessory | °C | Write | |
| AV | 58349 | Setpoint Extra Heating (own sequence) | Temperature; configuration/accessory | °C | Write | |
| AV | 30463 | Setpoint Extra Cooling (own sequence) | Temperature; configuration/accessory | °C | Write | |
| AV | 30105 | Current Setpoint Cooling | Temperature; configuration/accessory | °C | Read | |
| AV | 4018 | Current Setpoint Heating | Temperature; configuration/accessory | °C | Read | |
| AO | 37442 | Electrical Heating Value | Temperature; configuration/accessory | % | Read | |
| AO | 26209 | Heating Valve Value | Temperature; configuration/accessory | % | Read | |
| AO | 30925 | Cooling Valve Value | Temperature; configuration/accessory | % | Read | |
| AO | 46994 | Valve Extra Heating Value | Temperature; configuration/accessory | % | Read | |
| AO | 30463 | Valve Extra Cooling Value | Temperature; configuration/accessory | % | Read | |
| BO | 10264 | Pump Heating Status | Temperature; configuration/accessory | Read | ||
| BO | 10276 | Pump Cooling Status | Temperature; configuration/accessory | Read | ||
| BO | 31944 | Pump Extra Heating Status | Temperature; configuration/accessory | Read | ||
| BO | 63601 | Pump Extra Cooling Status | Temperature; configuration/accessory | Read | ||
| MV | 30094 | Cooling Machine Status | Temperature; configuration/accessory | Read | 1=Off, 2=On | |
| AV | 52572 | Supply fan St 1 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 22144 | Supply fan St 2 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 8244 | Supply fan St 3 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 28953 | Supply fan St 4 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 1965 | Supply fan St 5 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 45030 | Extract fan St 1 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 13370 | Extract fan St 2 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 17038 | Extract fan St 3 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 5027 | Extract fan St 4 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 25879 | Extract fan St 5 | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Write | |
| AV | 46589 | Current Setpoint Supply fan | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Read | |
| AV | 33255 | Current Setpoint Extract fan | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Read | |
| AO | 59037 | Current Output Supply fan | Air flow | % | Read | |
| AV | 56628 | Current Value Supply fan | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Read | |
| AV | 59694 | Current Value Extract fan | Air flow; Pa with accessory, m3/h standard, l/s by configuration | Pa,m3/h,l/s | Read | |
| AO | 40119 | Current Output Extract fan | Air flow | % | Read | |
| AV | 52945 | Current SFP | Air flow; standard | kW/m3/s | Read | |
| BI | 11643 | Digital input 1 | Regulation; standard | Read | ||
| BI | 7448 | Digital input 2 | Regulation; standard | Read | ||
| BI | 3385 | Digital input 3 | Regulation; standard | Read | ||
| BI | 96701 | Fire/Smoke input 1 | Regulation; accessory/configuration | Read | ||
| BI | 59736 | Fire/Smoke input 2 | Regulation; accessory/configuration | Read | ||
| AI | 3737 | CO2 Current Value | Regulation; accessory/configuration | ppm | Read | |
| AI | 22649 | CO2 Setpoint | Regulation; accessory/configuration | ppm | Read | |
| AV | 23 | CO2 Compensation | Regulation; accessory/configuration | % | Write | |
| BO | 6170 | Outdoor Damper Output | Regulation; standard | Read | ||
| BO | 43251 | Exhaust Damper Output | Regulation; standard | Read | ||
| MV | 24347 | Firedamer Operating Mode | Regulation; accessory/configuration | Read | 2=Closed, 3=Closing/Opening, 4=Open | |
| MV | 9703 | Firedamper Status | Regulation; accessory/configuration | Read | 2=Ok, 3=Test, 4=Alarm | |
| AI | 40720 | Current Filter Pressure Supply | Filter; standard | Pa | Read | |
| AI | 13692 | Current Filter Pressure Extract | Filter; standard | Pa | Read | |
| AV | 39417 | Current Density Supply Filter | Filter; standard | % | Read | |
| AV | 31282 | Current Density Extract Filter | Filter; standard | % | Read | |
| MVmin | 46769 | A-Alarm Danger | Alarms; standard | Read | 1=Normal, 2=Alarm | |
| MV | 42640 | A-Alarm High | Alarms; standard | Read | 1=Normal, 2=Alarm | |
| MVmin | 38643 | B-Alarm | Alarms; standard | Read | 1=Normal, 2=Alarm | |
| MV | 38643 | C-Alarm | Alarms; standard | Read | 1=Normal, 2=Alarm | |
| MVmin | 19 | Reset Alarm (A,B,C) | Alarms; standard | Write | 1=Executing | |
| BO | 5714 | Alarm output | Alarms; standard | Read | 0=Normal, 1=Alarm | |
| AV | 47377 | Supply fan RPM | Fans; standard | rpm | Read | |
| AV | 23951 | Supply fan Effect | Fans; standard | kW | Read | |
| AV | 57785 | Supply fan Frequency | Fans; standard | Hz | Read | |
| AV | 36916 | Supply fan Opretating Hours | Fans; standard | h | Read | |
| AV | 60827 | Extract fan RPM | Fans; standard | rpm | Read | |
| AV | 22850 | Extract fan Effect | Fans; standard | kW | Read | |
| AV | 9628 | Extract fan Frequency | Fans; standard | Hz | Read | |
| AV | 38137 | Extract fan Opretating Hours | Fans; standard | h | Read | |
| AO | 5922 | Heat Recovery Current Value | Heat recovery; standard | % | Read | |
| AV | 17247 | Heat Recovery Efficiency | Heat recovery; accessory/configuration | % | Read |
No points match these filters.
Object ID lookup: Flexit ProNordic with CS2500 controller point IDs by name
MV32040BMS RegulationMV56125Operating mode Temp regulationMV6080Operating mode Operation AggregateBV32321Status AHUAI53218Outdoor temperatureAI45150Supply temperatureAI28256Extract temperatureAI40895Exhaust temperatureAI40895Return water temperatureAI20915Supply temperature extra sequenceAV80Min supply temperature (Extract/Cascade regulation)AV5Max supply temperature (Extract/Cascade regulation)AV35713Setpoint Economi HeatingAV61866Setpoint Economi CoolingAV22817Setpoint Komfort HeatingAV8970Setpoint Komfort CoolingAV58349Setpoint Extra Heating (own sequence)AV30463Setpoint Extra Cooling (own sequence)AV30105Current Setpoint CoolingAV4018Current Setpoint HeatingAO37442Electrical Heating ValueAO26209Heating Valve ValueAO30925Cooling Valve ValueAO46994Valve Extra Heating ValueAO30463Valve Extra Cooling ValueBO10264Pump Heating StatusBO10276Pump Cooling StatusBO31944Pump Extra Heating StatusBO63601Pump Extra Cooling StatusMV30094Cooling Machine StatusAV52572Supply fan St 1AV22144Supply fan St 2AV8244Supply fan St 3AV28953Supply fan St 4AV1965Supply fan St 5AV45030Extract fan St 1AV13370Extract fan St 2AV17038Extract fan St 3AV5027Extract fan St 4AV25879Extract fan St 5AV46589Current Setpoint Supply fanAV33255Current Setpoint Extract fanAO59037Current Output Supply fanAV56628Current Value Supply fanAV59694Current Value Extract fanAO40119Current Output Extract fanAV52945Current SFPBI11643Digital input 1BI7448Digital input 2BI3385Digital input 3BI96701Fire/Smoke input 1BI59736Fire/Smoke input 2AI3737CO2 Current ValueAI22649CO2 SetpointAV23CO2 CompensationBO6170Outdoor Damper OutputBO43251Exhaust Damper OutputMV24347Firedamer Operating ModeMV9703Firedamper StatusAI40720Current Filter Pressure SupplyAI13692Current Filter Pressure ExtractAV39417Current Density Supply FilterAV31282Current Density Extract FilterMV46769A-Alarm DangerMV42640A-Alarm HighMV38643B-AlarmMV38643C-AlarmMV19Reset Alarm (A,B,C)BO5714Alarm outputAV47377Supply fan RPMAV23951Supply fan EffectAV57785Supply fan FrequencyAV36916Supply fan Opretating HoursAV60827Extract fan RPMAV22850Extract fan EffectAV9628Extract fan FrequencyAV38137Extract fan Opretating HoursAO5922Heat Recovery Current ValueAV17247Heat Recovery Efficiency
Integration notes
- The spreadsheet has no read/write column. Access here is inferred: the BMS mode command, the alarm reset and the setpoint/fan-step AVs are marked W, everything else R.
- Printed instance clashes are kept as printed: AI 40895 is listed for both exhaust temperature and return water temperature, and MV 38643 for both B-alarm and C-alarm. AV 30463 and AO 30463 are different object types.
- BV 32321 Status AHU is printed as a Binary Value but with 17 state texts (2-18); check the type on the live unit.
- State texts follow the Norwegian sheet where the English sheet differs: MV 30094 1=Off/2=On and BO 5714 0=Normal/1=Alarm (the English sheet prints them the other way or 1/2).
- Fan step and fan value AVs are in Pa (pressure accessory), m3/h (standard) or l/s (by configuration).
- The file also has Norwegian and Swedish sheets with the same instances; names here are from the English sheet, typos included.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ProNordic with CS2500 controller (SP85 BACnet IP module) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)
How many BACnet points does the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) have?
This list has 79 BACnet objects: 10 analog inputs, 8 analog outputs, 37 analog values, 5 binary inputs, 7 binary outputs, 1 binary value, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet points are writable?
21 of the 79 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet documentation?
The source is Overview Bacnet-object Flexit ProNordic (BACnet Flexit CS2500), revision 2024-09, published free by Flexit at https://flexitwebsiteprodstorage.blob.core.windows.net/product-documents/10670.
What are the minimum BACnet points to integrate the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)?
Start with MV 32040 BMS Regulation (Mode command: 1 Auto, 2 Off, 3-8 Economy/Comfort steps); AV 22817 Setpoint Komfort Heating (Comfort heating setpoint); AV 35713 Setpoint Economi Heating (Economy heating setpoint); MV 19 Reset Alarm (A,B,C) (Alarm reset); MV 6080 Operating mode Operation Aggregate (Actual operating mode (off, comfort, economy, start)); AI 45150 Supply temperature (Supply air temperature); AI 53218 Outdoor temperature (Outdoor air temperature); AI 28256 Extract temperature (Extract air temperature); MV 46769 A-Alarm Danger (A alarm active when 2); MV 38643 B-Alarm (B alarm active when 2).
How do I enable BMS control of the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)?
MV 32040 BMS Regulation selects Auto (unit follows its own schedule), Off, or a fixed Economy or Comfort fan step from the BMS.
How do I check these points on the real ProNordic with CS2500 controller (SP85 BACnet IP module)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.