Air handling unit controller (commercial heat recovery AHU) · BACnet points list

Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet points list

Updated 12 November 2026

Short answer

Flexit's overview spreadsheet of the BACnet objects in a ProNordic unit (CS2500 controller with the SP85 BACnet IP module). It has 79 objects: the BMS mode command, operating mode status, temperatures and setpoints, valve and pump outputs, five fan steps per fan, fan readings, filter pressures, fire damper status and A/B/C alarms. Many objects only exist when the matching accessory or configuration is present (marked S, C or A in the list).

This page lists 79 BACnet objects for the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Flexit’s own free documentation, linked below.

Manufacturer
Flexit
Model
ProNordic with CS2500 controller (SP85 BACnet IP module)
Equipment
Air handling unit controller (commercial heat recovery AHU)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
79 (21 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Flexit ProNordic, ProNordic, CS2500, Flexit CS2500, SP85, Kommunikasjonsmodul BACnet IP SP85, Oversikt Bacnet-objekt Flexit ProNordic
Source document
Overview Bacnet-object Flexit ProNordic (BACnet Flexit CS2500) · rev. 2024-09
Download CSV 79 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Flexit’s current documentation and the live device before use. Not official Flexit information. Terms of use.

BMS integration notes: Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)

Integration in brief

Write MV 32040 BMS Regulation to run the unit from the BMS (Auto, Off, or Economy/Comfort steps 1-3). Adjust the comfort and economy heating setpoints if needed. Read MV 6080 for the actual operating mode, the outdoor/supply/extract temperatures, the fan values and the A/B/C alarm MVs; MV 19 resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 32040BMS RegulationMode command: 1 Auto, 2 Off, 3-8 Economy/Comfort stepsWrite
AV 22817Setpoint Komfort HeatingComfort heating setpointWrite
AV 35713Setpoint Economi HeatingEconomy heating setpointWrite
MV 19Reset Alarm (A,B,C)Alarm resetWrite
MV 6080Operating mode Operation AggregateActual operating mode (off, comfort, economy, start)Read
AI 45150Supply temperatureSupply air temperatureRead
AI 53218Outdoor temperatureOutdoor air temperatureRead
AI 28256Extract temperatureExtract air temperatureRead
MV 46769A-Alarm DangerA alarm active when 2Read
MV 38643B-AlarmB alarm active when 2Read

Enable & remote start

MV 32040 BMS Regulation selects Auto (unit follows its own schedule), Off, or a fixed Economy or Comfort fan step from the BMS.

Network setup

Watch out for

Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

79 of 79 shown
Type
Multi-state
Access
Show
Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet Points List
DescriptionStates
MVmin32040BMS RegulationBMS mode command; standardWrite1=Auto, 2=Off, 3=Economy St 1, 4=Economy St 2, 5=Economy St 3, 6=Comfort St 1, 7=Comfort St 2, 8=Comfort St 3
MV56125Operating mode Temp regulationMain function; standard; Status only, do not writeRead1=Supply, 2=Room/Cascade, 3=Extract/Cascade, 4=Room Summer/Winter, 5=Extract Summer/Winter, 6=Room
MVmin6080Operating mode Operation AggregateMain function; standardRead1=Off, 2=On, 3=Off, 4=Comfort, 5=Economy, 6=After cooling, 7=Start
BV32321Status AHUMain function; standardRead2=Configuration mode, 3=Fire, 4=Alarmstopp, 5=Nødstopp, 6=Alarm, 7=Spjeldmotsionering, 8=Manuell, 9=Støttedrift, 10=External regulation, 11=Optimizing, 12=Room unit, 13=Free cooling, 14=BMS, 15=Time schedule, 16=Schedule T, 17=calendar, 18=Service switch
AImin53218Outdoor temperatureTemperature; standard°CRead
AImin45150Supply temperatureTemperature; standard°CRead
AImin28256Extract temperatureTemperature; standard°CRead
AI40895Exhaust temperatureTemperature; accessory°CRead
AI40895Return water temperatureTemperature; accessory°CRead
AI20915Supply temperature extra sequenceTemperature; accessory°CRead
AV80Min supply temperature (Extract/Cascade regulation)Temperature; configuration°CWrite
AV5Max supply temperature (Extract/Cascade regulation)Temperature; configuration°CWrite
AVmin35713Setpoint Economi HeatingTemperature; standard°CWrite
AV61866Setpoint Economi CoolingTemperature; configuration/accessory°CWrite
AVmin22817Setpoint Komfort HeatingTemperature; standard°CWrite
AV8970Setpoint Komfort CoolingTemperature; configuration/accessory°CWrite
AV58349Setpoint Extra Heating (own sequence)Temperature; configuration/accessory°CWrite
AV30463Setpoint Extra Cooling (own sequence)Temperature; configuration/accessory°CWrite
AV30105Current Setpoint CoolingTemperature; configuration/accessory°CRead
AV4018Current Setpoint HeatingTemperature; configuration/accessory°CRead
AO37442Electrical Heating ValueTemperature; configuration/accessory%Read
AO26209Heating Valve ValueTemperature; configuration/accessory%Read
AO30925Cooling Valve ValueTemperature; configuration/accessory%Read
AO46994Valve Extra Heating ValueTemperature; configuration/accessory%Read
AO30463Valve Extra Cooling ValueTemperature; configuration/accessory%Read
BO10264Pump Heating StatusTemperature; configuration/accessoryRead
BO10276Pump Cooling StatusTemperature; configuration/accessoryRead
BO31944Pump Extra Heating StatusTemperature; configuration/accessoryRead
BO63601Pump Extra Cooling StatusTemperature; configuration/accessoryRead
MV30094Cooling Machine StatusTemperature; configuration/accessoryRead1=Off, 2=On
AV52572Supply fan St 1Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV22144Supply fan St 2Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV8244Supply fan St 3Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV28953Supply fan St 4Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV1965Supply fan St 5Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV45030Extract fan St 1Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV13370Extract fan St 2Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV17038Extract fan St 3Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV5027Extract fan St 4Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV25879Extract fan St 5Air flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sWrite
AV46589Current Setpoint Supply fanAir flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sRead
AV33255Current Setpoint Extract fanAir flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sRead
AO59037Current Output Supply fanAir flow%Read
AV56628Current Value Supply fanAir flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sRead
AV59694Current Value Extract fanAir flow; Pa with accessory, m3/h standard, l/s by configurationPa,m3/h,l/sRead
AO40119Current Output Extract fanAir flow%Read
AV52945Current SFPAir flow; standardkW/m3/sRead
BI11643Digital input 1Regulation; standardRead
BI7448Digital input 2Regulation; standardRead
BI3385Digital input 3Regulation; standardRead
BI96701Fire/Smoke input 1Regulation; accessory/configurationRead
BI59736Fire/Smoke input 2Regulation; accessory/configurationRead
AI3737CO2 Current ValueRegulation; accessory/configurationppmRead
AI22649CO2 SetpointRegulation; accessory/configurationppmRead
AV23CO2 CompensationRegulation; accessory/configuration%Write
BO6170Outdoor Damper OutputRegulation; standardRead
BO43251Exhaust Damper OutputRegulation; standardRead
MV24347Firedamer Operating ModeRegulation; accessory/configurationRead2=Closed, 3=Closing/Opening, 4=Open
MV9703Firedamper StatusRegulation; accessory/configurationRead2=Ok, 3=Test, 4=Alarm
AI40720Current Filter Pressure SupplyFilter; standardPaRead
AI13692Current Filter Pressure ExtractFilter; standardPaRead
AV39417Current Density Supply FilterFilter; standard%Read
AV31282Current Density Extract FilterFilter; standard%Read
MVmin46769A-Alarm DangerAlarms; standardRead1=Normal, 2=Alarm
MV42640A-Alarm HighAlarms; standardRead1=Normal, 2=Alarm
MVmin38643B-AlarmAlarms; standardRead1=Normal, 2=Alarm
MV38643C-AlarmAlarms; standardRead1=Normal, 2=Alarm
MVmin19Reset Alarm (A,B,C)Alarms; standardWrite1=Executing
BO5714Alarm outputAlarms; standardRead0=Normal, 1=Alarm
AV47377Supply fan RPMFans; standardrpmRead
AV23951Supply fan EffectFans; standardkWRead
AV57785Supply fan FrequencyFans; standardHzRead
AV36916Supply fan Opretating HoursFans; standardhRead
AV60827Extract fan RPMFans; standardrpmRead
AV22850Extract fan EffectFans; standardkWRead
AV9628Extract fan FrequencyFans; standardHzRead
AV38137Extract fan Opretating HoursFans; standardhRead
AO5922Heat Recovery Current ValueHeat recovery; standard%Read
AV17247Heat Recovery EfficiencyHeat recovery; accessory/configuration%Read
Object ID lookup: Flexit ProNordic with CS2500 controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ProNordic with CS2500 controller (SP85 BACnet IP module) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)

How many BACnet points does the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) have?

This list has 79 BACnet objects: 10 analog inputs, 8 analog outputs, 37 analog values, 5 binary inputs, 7 binary outputs, 1 binary value, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet points are writable?

21 of the 79 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Flexit ProNordic with CS2500 controller (SP85 BACnet IP module) BACnet documentation?

The source is Overview Bacnet-object Flexit ProNordic (BACnet Flexit CS2500), revision 2024-09, published free by Flexit at https://flexitwebsiteprodstorage.blob.core.windows.net/product-documents/10670.

What are the minimum BACnet points to integrate the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)?

Start with MV 32040 BMS Regulation (Mode command: 1 Auto, 2 Off, 3-8 Economy/Comfort steps); AV 22817 Setpoint Komfort Heating (Comfort heating setpoint); AV 35713 Setpoint Economi Heating (Economy heating setpoint); MV 19 Reset Alarm (A,B,C) (Alarm reset); MV 6080 Operating mode Operation Aggregate (Actual operating mode (off, comfort, economy, start)); AI 45150 Supply temperature (Supply air temperature); AI 53218 Outdoor temperature (Outdoor air temperature); AI 28256 Extract temperature (Extract air temperature); MV 46769 A-Alarm Danger (A alarm active when 2); MV 38643 B-Alarm (B alarm active when 2).

How do I enable BMS control of the Flexit ProNordic with CS2500 controller (SP85 BACnet IP module)?

MV 32040 BMS Regulation selects Auto (unit follows its own schedule), Off, or a fixed Economy or Comfort fan step from the BMS.

How do I check these points on the real ProNordic with CS2500 controller (SP85 BACnet IP module)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Flexit BACnet points lists

Source: Overview Bacnet-object Flexit ProNordic (BACnet Flexit CS2500) · rev. 2024-09. Object names, instances and units are reproduced as published; descriptions are our own.