Energy recovery ventilation unit (residential AHU) · BACnet points list

Flexit Nordic series (Nordic Basic BACnet list) BACnet points list

Updated 12 November 2026

Short answer

Flexit Nordic units have BACnet IP built in (Siemens Climatix S300 controller, POS3.6715). Flexit's basic list has 66 rows: ventilation mode commands and status, setpoints, timers for fireplace and rapid ventilation, sensor readings, outputs and A/B alarm handling. Several rows give two or three instance numbers because the object moves with the configured input or output terminal; each printed instance is listed here.

This page lists 85 BACnet objects for the Flexit Nordic series (Nordic Basic BACnet list) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Flexit’s own free documentation, linked below.

Manufacturer
Flexit
Model
Nordic series (Nordic Basic BACnet list)
Equipment
Energy recovery ventilation unit (residential AHU)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
85 (16 writable)
Transport
BACnet IP
Firmware
Application APTV 2.419 and above (per the Flexit GO BACnet guide)
Default device instance
2
Also known as
Flexit Nordic, Nordic S2, Nordic S3, Nordic S4, Nordic CL2, Nordic CL3, Nordic CL4, Nordic KS, Flexit GO, BACnet Basic list - Nordic, Climatix S300 POS3.6715
Source document
BACnet Basic list - Nordic · rev. 2020-10
Download CSV 85 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Flexit’s current documentation and the live device before use. Not official Flexit information. Terms of use.

BMS integration notes: Flexit Nordic series (Nordic Basic BACnet list)

Integration in brief

Set BV 50 Comfort button to 1 so the unit follows MV 42 Room operating mode, then write MV 42 (Stop/Away/Home/High). Write the home and away temperature setpoints (instance depends on supply or extract control). Read MV 361 for the present mode, the temperatures and fan speeds, and the A/B alarm indication points; MV 344 acknowledges or resets A alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 50Comfort buttonMust be 1 for MV 42 to take effectCommand
MV 42Room operating modeMode command: 1 Stop, 2 Away, 3 Home, 4 HighCommand
AV 1994Setpoint temperature when homeHome setpoint (supply air control default)Write
MV 344A-Alarm acknowledgementWrite 2 to acknowledge, 3 to reset A alarmsWrite
MV 361Heat recovery ventilation statePresent ventilation modeRead
AI 4Supply air temperatureSupply air temperatureRead
AI 1Outside air temperatureOutdoor air temperatureRead
AI 59Extract air temperatureExtract (return) air temperatureRead
MV 343A-Alarm indicationA alarm active when 2Read
MV 340B-Alarm indicationB alarm active when 2Read

Enable & remote start

MV 42 Room operating mode only works when BV 50 Comfort button is 1; with BV 50 at 0 the unit goes to Away after the AWAY delay (PIV 318). A ventilation mode wired to a digital input overrides MV 42.

Network setup

Watch out for

Flexit Nordic series (Nordic Basic BACnet list) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

85 of 85 shown
Type
Multi-stateOther
Access
Show
Flexit Nordic series (Nordic Basic BACnet list) BACnet Points List
DescriptionStates
BVmin50Comfort button0 = away after delay, 1 = follow room operating modeCommand0=Inactive, 1=Active
MVmin361Heat recovery ventilation statePresent ventilation modeRead1=Off, 2=Away, 3=Home, 4=High, 5=Fume hood, 6=Fireplace, 7=Temporary high
MVmin42Room operating modeVentilation mode command; needs BV 50 = 1Command1=Stop, 2=Away, 3=Home, 4=High
AV1985Setpoint temperature when awayInstance used with Sup (default); Range 10 to 30°CWrite
AV1988Setpoint temperature when awayInstance used with Ext; Range 10 to 30°CWrite
AVmin1994Setpoint temperature when homeInstance used with Sup (default); Range 10 to 30°CWrite
AV2070Setpoint temperature when homeInstance used with Ext; Range 10 to 30°CWrite
AV2038Remaining time of fireplace ventilationRange 0 to 360minRead
AV2031Remaining time of rapid ventilationRange 0 to 360minRead
PIV270Fireplace ventilation runtimeRange 0 to 360minWrite
PIV293Rapid ventilation runtimeRange 1 to 360minWrite
MV360Trigger temporary fireplace ventilationWrite1=Ready, 2=Trigger
MV357Trigger temporary rapid ventilationWrite1=Ready, 2=Trigger
PIV318AWAY delay timer durationRange 0 to 600minWrite
AV2096Room air quality 1Range 0 to 2000ppmRead
AI12Exhaust air fan speed feedbackRange 0 to 18000rpmRead
AI5Supply air fan speed feedbackRange 0 to 18000rpmRead
AI50Relative humidity for extract airHumidity sensor on X3; Range 0 to 100%Read
AI72Extract air pressureRange -3000 to 3000PaRead
AI73Supply air pressureRange -3000 to 3000PaRead
AI11Exhaust air temperatureRange -50 to 80°CRead
AImin59Extract air temperatureRange -50 to 80°CRead
AI31Frost protection temp.for heating coilRange -3000 to 3000PaRead
AImin1Outside air temperatureRange -50 to 50°CRead
AI75Room temperatureRange 0 to 50°CRead
AV2093Room air humidity 1Range 0 to 100%Read
AV2094Room air humidity 2Range 0 to 100%Read
AV2095Room air humidity 3Range 0 to 100%Read
AI50Room air quality input value (CU)Air quality sensor on X3; Range 0 to 2000ppmRead
AImin4Supply air temperatureRange -50 to 80°CRead
BI22AwayInstance used with DI1Read0=Inactive, 1=Active
BI29AwayInstance used with DI2Read0=Inactive, 1=Active
BI31AwayInstance used with X8 (default)Read0=Inactive, 1=Active
BI87CO detectorRead0=Inactive, 1=Active
BI32Emergency offRead0=Inactive, 1=Active
BI18Fire damper feedbackInstance used with DI1Read0=Inactive, 1=Active
BI25Fire damper feedbackInstance used with DI2Read0=Inactive, 1=Active
BI92Fire damper feedbackInstance used with X8Read0=Inactive, 1=Active
BI16Fume hood ventilation inputInstance used with DI1Read0=Inactive, 1=Active
BI23Fume hood ventilation inputInstance used with DI2 (default)Read0=Inactive, 1=Active
BI493Fume hood ventilation inputInstance used with CI79Read0=Inactive, 1=Active
BI17Fireplace ventilation inputInstance used with DI1Read0=Inactive, 1=Active
BI24Fireplace ventilation inputInstance used with DI2Read0=Inactive, 1=Active
BI33Heating coil overtemperature detectorRead0=Inactive, 1=Active
BI82HighInstance used with DI1 (default)Read0=Inactive, 1=Active
BI83HighInstance used with DI2Read0=Inactive, 1=Active
BI21HomeInstance used with DI1Read0=Inactive, 1=Active
BI28HomeInstance used with DI2Read0=Inactive, 1=Active
BI30HomeInstance used with X8Read0=Inactive, 1=Active
BI88Smoke/fire exhaust fan operationRead0=Inactive, 1=Active
BI90Smoke/fire fan off operationRead0=Inactive, 1=Active
BI91Smoke/fire supply & exhaust fan op.Read0=Inactive, 1=Active
BI89Smoke/fire supply fan operationRead0=Inactive, 1=Active
BI20StopInstance used with DI1Read0=Inactive, 1=Active
BI27StopInstance used with DI2Read0=Inactive, 1=Active
AO34Cooling coil valve positionRange 0 to 100%Read
AO4Exhaust air fan speedRange 0 to 100%Read
AO3Supply air fan speedRange 0 to 100%Read
AO29Heating coil electric positionRange 0 to 100%Read
AO12Heating coil valve positionRange 0 to 100%Read
AO0Rotary heat exchanger speedRange 0 to 100%Read
BO64Cooling coil pump commandInstance used with Q1Read0=Inactive, 1=Active
BO68Cooling coil pump commandInstance used with Q2Read0=Inactive, 1=Active
BO57Cooling coil pump commandInstance used with Q3Read0=Inactive, 1=Active
BO18Outside air damper commandInstance used with Q1 (default)Read0=Inactive, 1=Active
BO65Outside air damper commandInstance used with Q2Read0=Inactive, 1=Active
BO69Outside air damper commandInstance used with Q3Read0=Inactive, 1=Active
BO19Fire damper commandInstance used with Q1Read0=Inactive, 1=Active
BO66Fire damper commandInstance used with Q2Read0=Inactive, 1=Active
BO46Fire damper commandInstance used with Q3Read0=Inactive, 1=Active
BO58Heating coil pump commandRead0=Inactive, 1=Active
MVmin344A-Alarm acknowledgementAcknowledge or reset A alarmsWrite1=Ready, 2=Acknowledge, 3=Reset
AV8A-Alarm codeRange 0 to 9999Read
MVmin343A-Alarm indicationRead1=Normal, 2=Alarm
MV7A-Alarm stateRead1=Acknowledged, unlocked, 2=Unacknowledged, 3=Locked
MV341B-Alarm acknowledgementAcknowledge B alarmsWrite1=Ready, 2=Acknowledge
AV130B-Alarm codeRange 0 to 9999Read
MVmin340B-Alarm indicationRead1=Normal, 2=Alarm
MV18B-Alarm stateRead1=Acknowledged, unlocked, 2=Unacknowledged, 3=Locked
AV2025Display fault listRange 0 to 10000Read
AV2026Fault counterRange 0 to 2000Read
AV2027Fault list numberRange 1 to 10000Read
MV342Fault list operationWrite1=Ready, 2=Next fault, 3=Refresh
AV285Operating time filterRange 0 to 99999hWrite
AV286Operating time for filter replacementRange 0 to 99990hWrite
Object ID lookup: Flexit Nordic series point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Nordic series (Nordic Basic BACnet list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Flexit Nordic series (Nordic Basic BACnet list)

How many BACnet points does the Flexit Nordic series (Nordic Basic BACnet list) have?

This list has 85 BACnet objects: 12 analog inputs, 6 analog outputs, 17 analog values, 25 binary inputs, 10 binary outputs, 1 binary value, 11 multi-state values, 3 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Flexit Nordic series (Nordic Basic BACnet list) BACnet points are writable?

16 of the 85 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Flexit Nordic series (Nordic Basic BACnet list) BACnet documentation?

The source is BACnet Basic list - Nordic, revision 2020-10, published free by Flexit at https://flexitwebsiteprodstorage.blob.core.windows.net/product-documents/2963.

What are the minimum BACnet points to integrate the Flexit Nordic series (Nordic Basic BACnet list)?

Start with BV 50 Comfort button (Must be 1 for MV 42 to take effect); MV 42 Room operating mode (Mode command: 1 Stop, 2 Away, 3 Home, 4 High); AV 1994 Setpoint temperature when home (Home setpoint (supply air control default)); MV 344 A-Alarm acknowledgement (Write 2 to acknowledge, 3 to reset A alarms); MV 361 Heat recovery ventilation state (Present ventilation mode); AI 4 Supply air temperature (Supply air temperature); AI 1 Outside air temperature (Outdoor air temperature); AI 59 Extract air temperature (Extract (return) air temperature); MV 343 A-Alarm indication (A alarm active when 2); MV 340 B-Alarm indication (B alarm active when 2).

How do I enable BMS control of the Flexit Nordic series (Nordic Basic BACnet list)?

MV 42 Room operating mode only works when BV 50 Comfort button is 1; with BV 50 at 0 the unit goes to Away after the AWAY delay (PIV 318). A ventilation mode wired to a digital input overrides MV 42.

How do I check these points on the real Nordic series (Nordic Basic BACnet list)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.