 "manufacturer": "Flexit",
 "manufacturer_slug": "flexit",
 "model": "ProNordic with CS2500 controller (SP85 BACnet IP module)",
 "model_slug": "pronordic-cs2500-bacnet",
 "aliases": [
  "Flexit ProNordic",
  "ProNordic",
  "CS2500",
  "Flexit CS2500",
  "SP85",
  "Kommunikasjonsmodul BACnet IP SP85",
  "Oversikt Bacnet-objekt Flexit ProNordic"
 ],
 "equipment_type": "Air handling unit controller (commercial heat recovery AHU)",
 "applies_to": "Flexit ProNordic commercial air handling units with the CS2500 controller and the SP85 BACnet IP communication module.",
 "summary": "Flexit's overview spreadsheet of the BACnet objects in a ProNordic unit (CS2500 controller with the SP85 BACnet IP module). It has 79 objects: the BMS mode command, operating mode status, temperatures and setpoints, valve and pump outputs, five fan steps per fan, fan readings, filter pressures, fire damper status and A/B/C alarms. Many objects only exist when the matching accessory or configuration is present (marked S, C or A in the list).",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The spreadsheet has no read/write column. Access here is inferred: the BMS mode command, the alarm reset and the setpoint/fan-step AVs are marked W, everything else R.",
  "Printed instance clashes are kept as printed: AI 40895 is listed for both exhaust temperature and return water temperature, and MV 38643 for both B-alarm and C-alarm. AV 30463 and AO 30463 are different object types.",
  "BV 32321 Status AHU is printed as a Binary Value but with 17 state texts (2-18); check the type on the live unit.",
  "State texts follow the Norwegian sheet where the English sheet differs: MV 30094 1=Off/2=On and BO 5714 0=Normal/1=Alarm (the English sheet prints them the other way or 1/2).",
  "Fan step and fan value AVs are in Pa (pressure accessory), m3/h (standard) or l/s (by configuration).",
  "The file also has Norwegian and Swedish sheets with the same instances; names here are from the English sheet, typos included."
 ],
 "source": {
  "title": "Overview Bacnet-object Flexit ProNordic (BACnet Flexit CS2500)",
  "doc_number": null,
  "revision_date": "2024-09",
  "url": "https://flexitwebsiteprodstorage.blob.core.windows.net/product-documents/10670"
 },
 "integration": {
  "summary": "Write MV 32040 BMS Regulation to run the unit from the BMS (Auto, Off, or Economy/Comfort steps 1-3). Adjust the comfort and economy heating setpoints if needed. Read MV 6080 for the actual operating mode, the outdoor/supply/extract temperatures, the fan values and the A/B/C alarm MVs; MV 19 resets alarms.",
  "minimum_points": [
   {
    "ref": "MV 32040",
    "name": "BMS Regulation",
    "why": "Mode command: 1 Auto, 2 Off, 3-8 Economy/Comfort steps"
   },
   {
    "ref": "AV 22817",
    "name": "Setpoint Komfort Heating",
    "why": "Comfort heating setpoint"
   },
   {
    "ref": "AV 35713",
    "name": "Setpoint Economi Heating",
    "why": "Economy heating setpoint"
   },
   {
    "ref": "MV 19",
    "name": "Reset Alarm (A,B,C)",
    "why": "Alarm reset"
   },
   {
    "ref": "MV 6080",
    "name": "Operating mode Operation Aggregate",
    "why": "Actual operating mode (off, comfort, economy, start)"
   },
   {
    "ref": "AI 45150",
    "name": "Supply temperature",
    "why": "Supply air temperature"
   },
   {
    "ref": "AI 53218",
    "name": "Outdoor temperature",
    "why": "Outdoor air temperature"
   },
   {
    "ref": "AI 28256",
    "name": "Extract temperature",
    "why": "Extract air temperature"
   },
   {
    "ref": "MV 46769",
    "name": "A-Alarm Danger",
    "why": "A alarm active when 2"
   },
   {
    "ref": "MV 38643",
    "name": "B-Alarm",
    "why": "B alarm active when 2"
   }
  ],
  "enable": "MV 32040 BMS Regulation selects Auto (unit follows its own schedule), Off, or a fixed Economy or Comfort fan step from the BMS.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP needs the SP85 communication module on the CS2500 controller."
  ],
  "gotchas": [
   "MV 56125 temperature regulation mode is status only; Flexit says not to change it.",
   "Several instances are printed twice for different points; confirm against the live unit's object list."
  ]
 },
 "points": [
  {
   "type": "MV",
   "instance": 32040,
   "name": "BMS Regulation",
   "description": "BMS mode command; standard",
   "units": "",
   "access": "W",
   "states": "1=Auto, 2=Off, 3=Economy St 1, 4=Economy St 2, 5=Economy St 3, 6=Comfort St 1, 7=Comfort St 2, 8=Comfort St 3"
  },
  {
   "type": "MV",
   "instance": 56125,
   "name": "Operating mode Temp regulation",
   "description": "Main function; standard; Status only, do not write",
   "units": "",
   "access": "R",
   "states": "1=Supply, 2=Room/Cascade, 3=Extract/Cascade, 4=Room Summer/Winter, 5=Extract Summer/Winter, 6=Room"
  },
  {
   "type": "MV",
   "instance": 6080,
   "name": "Operating mode Operation Aggregate",
   "description": "Main function; standard",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On, 3=Off, 4=Comfort, 5=Economy, 6=After cooling, 7=Start"
  },
  {
   "type": "BV",
   "instance": 32321,
   "name": "Status AHU",
   "description": "Main function; standard",
   "units": "",
   "access": "R",
   "states": "2=Configuration mode, 3=Fire, 4=Alarmstopp, 5=Nødstopp, 6=Alarm, 7=Spjeldmotsionering, 8=Manuell, 9=Støttedrift, 10=External regulation, 11=Optimizing, 12=Room unit, 13=Free cooling, 14=BMS, 15=Time schedule, 16=Schedule T, 17=calendar, 18=Service switch"
  },
  {
   "type": "AI",
   "instance": 53218,
   "name": "Outdoor temperature",
   "description": "Temperature; standard",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45150,
   "name": "Supply temperature",
   "description": "Temperature; standard",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28256,
   "name": "Extract temperature",
   "description": "Temperature; standard",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40895,
   "name": "Exhaust temperature",
   "description": "Temperature; accessory",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40895,
   "name": "Return water temperature",
   "description": "Temperature; accessory",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20915,
   "name": "Supply temperature extra sequence",
   "description": "Temperature; accessory",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "Min supply temperature (Extract/Cascade regulation)",
   "description": "Temperature; configuration",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Max supply temperature (Extract/Cascade regulation)",
   "description": "Temperature; configuration",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35713,
   "name": "Setpoint Economi Heating",
   "description": "Temperature; standard",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61866,
   "name": "Setpoint Economi Cooling",
   "description": "Temperature; configuration/accessory",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22817,
   "name": "Setpoint Komfort Heating",
   "description": "Temperature; standard",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8970,
   "name": "Setpoint Komfort Cooling",
   "description": "Temperature; configuration/accessory",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58349,
   "name": "Setpoint Extra Heating (own sequence)",
   "description": "Temperature; configuration/accessory",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30463,
   "name": "Setpoint Extra Cooling (own sequence)",
   "description": "Temperature; configuration/accessory",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30105,
   "name": "Current Setpoint Cooling",
   "description": "Temperature; configuration/accessory",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4018,
   "name": "Current Setpoint Heating",
   "description": "Temperature; configuration/accessory",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 37442,
   "name": "Electrical Heating Value",
   "description": "Temperature; configuration/accessory",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 26209,
   "name": "Heating Valve Value",
   "description": "Temperature; configuration/accessory",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 30925,
   "name": "Cooling Valve Value",
   "description": "Temperature; configuration/accessory",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 46994,
   "name": "Valve Extra Heating Value",
   "description": "Temperature; configuration/accessory",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 30463,
   "name": "Valve Extra Cooling Value",
   "description": "Temperature; configuration/accessory",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 10264,
   "name": "Pump Heating Status",
   "description": "Temperature; configuration/accessory",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 10276,
   "name": "Pump Cooling Status",
   "description": "Temperature; configuration/accessory",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 31944,
   "name": "Pump Extra Heating Status",
   "description": "Temperature; configuration/accessory",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 63601,
   "name": "Pump Extra Cooling Status",
   "description": "Temperature; configuration/accessory",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 30094,
   "name": "Cooling Machine Status",
   "description": "Temperature; configuration/accessory",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "AV",
   "instance": 52572,
   "name": "Supply fan St 1",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22144,
   "name": "Supply fan St 2",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8244,
   "name": "Supply fan St 3",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28953,
   "name": "Supply fan St 4",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1965,
   "name": "Supply fan St 5",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45030,
   "name": "Extract fan St 1",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13370,
   "name": "Extract fan St 2",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17038,
   "name": "Extract fan St 3",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5027,
   "name": "Extract fan St 4",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25879,
   "name": "Extract fan St 5",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46589,
   "name": "Current Setpoint Supply fan",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33255,
   "name": "Current Setpoint Extract fan",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 59037,
   "name": "Current Output Supply fan",
   "description": "Air flow",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56628,
   "name": "Current Value Supply fan",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59694,
   "name": "Current Value Extract fan",
   "description": "Air flow; Pa with accessory, m3/h standard, l/s by configuration",
   "units": "Pa,m3/h,l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 40119,
   "name": "Current Output Extract fan",
   "description": "Air flow",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52945,
   "name": "Current SFP",
   "description": "Air flow; standard",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11643,
   "name": "Digital input 1",
   "description": "Regulation; standard",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7448,
   "name": "Digital input 2",
   "description": "Regulation; standard",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3385,
   "name": "Digital input 3",
   "description": "Regulation; standard",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 96701,
   "name": "Fire/Smoke input 1",
   "description": "Regulation; accessory/configuration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 59736,
   "name": "Fire/Smoke input 2",
   "description": "Regulation; accessory/configuration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3737,
   "name": "CO2 Current Value",
   "description": "Regulation; accessory/configuration",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22649,
   "name": "CO2 Setpoint",
   "description": "Regulation; accessory/configuration",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "CO2 Compensation",
   "description": "Regulation; accessory/configuration",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 6170,
   "name": "Outdoor Damper Output",
   "description": "Regulation; standard",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 43251,
   "name": "Exhaust Damper Output",
   "description": "Regulation; standard",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 24347,
   "name": "Firedamer Operating Mode",
   "description": "Regulation; accessory/configuration",
   "units": "",
   "access": "R",
   "states": "2=Closed, 3=Closing/Opening, 4=Open"
  },
  {
   "type": "MV",
   "instance": 9703,
   "name": "Firedamper Status",
   "description": "Regulation; accessory/configuration",
   "units": "",
   "access": "R",
   "states": "2=Ok, 3=Test, 4=Alarm"
  },
  {
   "type": "AI",
   "instance": 40720,
   "name": "Current Filter Pressure Supply",
   "description": "Filter; standard",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13692,
   "name": "Current Filter Pressure Extract",
   "description": "Filter; standard",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39417,
   "name": "Current Density Supply Filter",
   "description": "Filter; standard",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31282,
   "name": "Current Density Extract Filter",
   "description": "Filter; standard",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 46769,
   "name": "A-Alarm Danger",
   "description": "Alarms; standard",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Alarm"
  },
  {
   "type": "MV",
   "instance": 42640,
   "name": "A-Alarm High",
   "description": "Alarms; standard",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Alarm"
  },
  {
   "type": "MV",
   "instance": 38643,
   "name": "B-Alarm",
   "description": "Alarms; standard",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Alarm"
  },
  {
   "type": "MV",
   "instance": 38643,
   "name": "C-Alarm",
   "description": "Alarms; standard",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Alarm"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "Reset Alarm (A,B,C)",
   "description": "Alarms; standard",
   "units": "",
   "access": "W",
   "states": "1=Executing"
  },
  {
   "type": "BO",
   "instance": 5714,
   "name": "Alarm output",
   "description": "Alarms; standard",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "AV",
   "instance": 47377,
   "name": "Supply fan RPM",
   "description": "Fans; standard",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23951,
   "name": "Supply fan Effect",
   "description": "Fans; standard",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57785,
   "name": "Supply fan Frequency",
   "description": "Fans; standard",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36916,
   "name": "Supply fan Opretating Hours",
   "description": "Fans; standard",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60827,
   "name": "Extract fan RPM",
   "description": "Fans; standard",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22850,
   "name": "Extract fan Effect",
   "description": "Fans; standard",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9628,
   "name": "Extract fan Frequency",
   "description": "Fans; standard",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38137,
   "name": "Extract fan Opretating Hours",
   "description": "Fans; standard",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5922,
   "name": "Heat Recovery Current Value",
   "description": "Heat recovery; standard",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17247,
   "name": "Heat Recovery Efficiency",
   "description": "Heat recovery; accessory/configuration",
   "units": "%",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/flexit/pronordic-cs2500-bacnet",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}