Fluid cooler / cooling tower control panel (1-4 cells) · BACnet points list

EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) BACnet points list

Updated 12 November 2026

Short answer

The Sage PLC panel runs EVAPCO fluid cooler cells: pumps, fans on VFDs, make-up water, basin heaters, louver de-icing and lead/lag between cells. It talks BACnet MS/TP on its RS-485 port (or Modbus RTU, chosen at the HMI) and BACnet IP on its Ethernet port. The BMS can enable the system, send a leaving fluid setpoint, acknowledge alarms and must toggle a heartbeat object.

This page lists 164 BACnet objects for the EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EVAPCO’s own free documentation, linked below.

Manufacturer
EVAPCO
Model
Sage Water & Energy Conservation Control System (Sage PLC)
Equipment
Fluid cooler / cooling tower control panel (1-4 cells)
Equipment type
Cooling towers & fluid coolers
BACnet objects
164 (25 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Sage, EVAPCO Sage, Sage PLC, Sage controller, Sage control panel, EVAPCO fluid cooler controller
Source document
Operations & Maintenance Instructions Addendum - Communications Guide for Sage Water & Energy Conservation Control System · rev. Revision 1.3
Download CSV 164 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against EVAPCO’s current documentation and the live device before use. Not official EVAPCO information. Terms of use.

BMS integration notes: EVAPCO Sage Water & Energy Conservation Control System (Sage PLC)

Integration in brief

Pick BACnet MS/TP or Modbus RTU for the serial port at the HMI (BACnet IP uses the Ethernet port; IP and MS/TP are not available together). Write bnEnableSystem to enable the system and bnBASSP for the leaving fluid setpoint, and keep the BMS heartbeat toggling. Monitor bnSYSEnabled, bnLocalRemoteStatus, the common leaving temperature, cell fan speeds and the alarm flags; bnALM_ACK acknowledges alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 35bnEnableSystemSystem enable from the BMS (1 = enabled)Write
AV 24bnBASSPLeaving fluid setpoint, 0.1 °F (850 = 85.0 °F)Write
BV 36bnALM_ACKAcknowledge alarms (1 = acknowledge)Write
BV 25bnLocalRemoteStatusControl mode: 0 local, 1 remoteRead
BV 26bnSYSEnabledSystem enabled statusRead
AV 52bnActiveSetpointActive fluid setpoint in use, 0.1 °FRead
AV 30bnCommonLeavingTempAverage leaving fluid temperature, 0.1 °FRead
AV 28bnC1VFDSpeedCell 1 fan speed, 0.1 %Read
BV 21bnC1VFDFaultALMCell 1 VFD fault alarmRead
BV 103bnHighCommonTempALMHigh common supply water temperature alarmRead

Enable & remote start

bnEnableSystem (BV 35) enables the system from the BMS; bnLocalRemoteStatus shows whether the panel is in local or remote control.

Heartbeat & communication loss

The guide lists bnBMSHeartbeat: 0 means waiting for the PLC to set it to 1 (5 s), 1 means waiting for the BMS to write it back to 0 (30 s). The guide does not say what the panel does when the BMS misses it. It is printed with the same instance as another object (BV 109), so confirm the live object before mapping it.

Network setup

Watch out for

EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

164 of 164 shown
Type
AnalogBinary
Access
Show
EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) BACnet Points List
DescriptionStates
BV0bnC1MakeupOnCell 1 Make-up SolenoidRead0=Off, 1=On
BV1bnC1PumpAStatusCell 1 Pump StatusRead0=Off, 1=On
BV2bnC1PumpALockedStatusCell 1 Pump Locked StatusRead0=Pump Locked On, 1=Pump Not Locked On
BV3bnC1BasinHeaterStatusCell 1 Basin Heater StatusRead0=Heaters Off, 1=Heaters On
BV4bnC1DischargeDamperCell 1 Discharge Damper StatusRead0=Dampers Closed, 1=Dampers Energized
BV5bnC1DischargeDamperAUXSwitchCell 1 Damper AUX Switch StatusRead0=Dampers Closed, 1=Dampers Open
BV6bnC1DeicingSeqCell 1 De-icing Sequence StatusRead0=Not Active, 1=Active
BV7bnC1CyclePumpsCell 1 Cycle Pump Routine StatusRead0=Not Active, 1=Active
BV8bnC1VFDStatusCell 1 VFD StatusRead0=Off, 1=On
BV9bnC1FanMotorHeatersCell 1 Fan Space Heater StatusRead0=Off, 1=On
BV10bnC1HeaterLWACell 1 Basin Heater Low Water AlarmRead0=No Alarm, 1=Alarm
BV11bnC1HeaterCONALMCell 1 Basin Heater Contactor AlarmRead0=No Alarm, 1=Alarm
BV12bnC1PumpAConFaultCell 1 Pump Contactor AlarmRead0=No Alarm, 1=Alarm
BV13bnC1HWACell 1 High Water AlarmRead0=No Alarm, 1=Alarm
BV14bnC1LWACell 1 Low Water AlarmRead0=No Alarm, 1=Alarm
BV15bnC1LowBasinTempALMCell 1 Low Basin Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV16bnC1HighSupplyTempALMCell 1 High Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV17bnC1LowSupplyTempALMCell 1 Low Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV18bnC1HighReturnTempALMCell 1 High Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV19bnC1LowReturnTempALMCell 1 Low Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV20bnC1BYPConALMCell 1 Fan Bypass Contactor AlarmRead0=No Alarm, 1=Alarm
BVmin21bnC1VFDFaultALMCell 1 VFD Fault AlarmRead0=No Alarm, 1=Alarm
BV22bnC1DamperLimitSwitchFLTCell 1 Damper Limit Switch AlarmRead0=No Alarm, 1=Alarm
BV23bnC1VibrationFaultALMCell 1 Vibration Switch AlarmRead0=No Alarm, 1=Alarm
BV24bnC1PumpANoFlowCell 1 Pump No Flow AlarmRead0=No Alarm, 1=Alarm
BVmin25bnLocalRemoteStatusSystem Control ModeRead0=Local (Default), 1=Remote
BVmin26bnSYSEnabledSystem Enabled StatusRead0=Not Enabled (Default), 1=Enabled
BV27bnHotStartRoutineSystem Hot Start Routine StatusRead0=Not Active, 1=Active
BV28bnHighAmbientTempALMHigh Ambient Temperature AlarmRead0=No Alarm, 1=Alarm
BV29bnLowAmbientTempLow Ambient Temperature AlarmRead0=No Alarm, 1=Alarm
BV30bn100CapALM100% Capacity AlarmRead0=No Alarm, 1=Alarm
BV31bnC1MakeupDisableCell 1 Drain Basin/Make-up Disable StatusRead0=Make-up Enabled (Default), 1=Drain Basin/Make-up Disabled
BV32bnC1PumpARuntimeResetCell 1 Pump Runtime ResetWrite0=No Reset, 1=Reset Runtime Hours
BV33bnC1FanRuntimeResetCell 1 Fan Runtime ResetWrite0=No Reset, 1=Reset Runtime Hours
BV34bnSavingsProritySystem Savings PriorityWrite0=Water Savings Priority (Default), 1=Energy Savings Priority
BVmin35bnEnableSystemSystem EnabledWrite0=Not Enabled (Default), 1=Enabled
BVmin36bnALM_ACKAcknowledge AlarmsWrite0=Not Acknowledged, 1=Alarms Acknowledged
BV37bnC2MakeupONCell 2 Make-up SolenoidRead0=Off, 1=On
BV38bnC2PumpAStatusCell 2 Pump StatusRead0=Off, 1=On
BV39bnC2PumpALockedStatusCell 2 Pump Locked StatusRead0=Pump Locked On, 1=Pump Not Locked On
BV40bnC2BasinHeaterStatusCell 2 Basin Heater StatusRead0=Heaters Off, 1=Heaters On
BV41bnC2DischargeDamperCell 2 Discharge Damper StatusRead0=Dampers Closed, 1=Dampers Energized
BV42bnC2DischargeDamperAUXSwitchCell 2 Discharge Damper StatusRead0=Dampers Closed, 1=Dampers Open
BV43bnC2DeicingSeqCell 2 De-icing Sequence StatusRead0=Not Active, 1=Active
BV44bnC2CyclePumpsCell 2 Cycle Pump Routine StatusRead0=Not Active, 1=Active
BV45bnC2VFDStatusCell 2 VFD StatusRead0=Off, 1=On
BV46bnC2FanMotorHeatersCell 2 Fan Space Heater StatusRead0=Off, 1=On
BV47bnC2HeaterLWACell 2 Basin Heater Low Water AlarmRead0=No Alarm, 1=Alarm
BV48bnC2HeaterCONALMCell 2 Basin Heater Contactor AlarmRead0=No Alarm, 1=Alarm
BV49bnC2PumpAConFaultCell 2 Pump Contactor AlarmRead0=No Alarm, 1=Alarm
BV50bnC2HWACell 2 High Water AlarmRead0=No Alarm, 1=Alarm
BV51bnC2LWACell 2 Low Water AlarmRead0=No Alarm, 1=Alarm
BV52bnC2LowBasinTempALMCell 2 Low Basin Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV53bnC2HighSupplyTempALMCell 2 High Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV54bnC2LowSupplyTempALMCell 2 Low Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV55bnC2HighReturnTempALMCell 2 High Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV56bnC2LowReturnTempALMCell 2 Low Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV57bnC2BYPConALMCell 2 Fan Bypass Contactor AlarmRead0=No Alarm, 1=Alarm
BV58bnC2VFDFaultALMCell 2 VFD Fault AlarmRead0=No Alarm, 1=Alarm
BV59bnC2DamperLimitSwitchFLTCell 2 Damper Limit Switch AlarmRead0=No Alarm, 1=Alarm
BV60bnC2VibrationFaultALMCell 2 Vibration Switch AlarmRead0=No Alarm, 1=Alarm
BV61bnC2PumpANoFlowCell 2 Pump No Flow AlarmRead0=No Alarm, 1=Alarm
BV62bnC2MakeupDisableCell 2 Drain Basin/Make-up Disable StatusRead0=Make-up Enabled (Default), 1=Drain Basin/Make-up Disabled
BV63bnC2PumpARuntimeResetCell 2 Pump Runtime ResetWrite0=No Reset, 1=Reset Runtime Hours
BV64bnC2FanRuntimeResetCell 2 Fan Runtime ResetWrite0=No Reset, 1=Reset Runtime Hours
BV65bnLeadLagSetSystem Lead Lag SetWrite0=Cell 2 Lead, 1=Cell 1 Lead (Default)
BV66bnC3PumpAStatusCell 3 Pump StatusRead0=Off, 1=On
BV67bnC3PumpALockedStatusCell 3 Pump Locked StatusRead0=Pump Locked On, 1=Pump Not Locked On
BV68bnC3DischargeDamperCell 3 Discharge Damper StatusRead0=Dampers Closed, 1=Dampers Energized
BV69bnC3DischargeDamperAUXSwitchCell 3 Discharge Damper Switch StatusRead0=Dampers Closed, 1=Dampers Open
BV70bnC3CyclePumpsCell 3 Cycle Pump Routine StatusRead0=Not Active, 1=Active
BV71bnC3VFDStatusCell 3 VFD StatusRead0=Off, 1=On
BV72bnC3FanMotorHeatersCell 3 Fan Space Heater StatusRead0=Off, 1=On
BV73bnC3PumpAConFaultCell 3 Pump Contactor AlarmRead0=No Alarm, 1=Alarm
BV74bnC3HighSupplyTempALMCell 3 High Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV75bnC3LowSupplyTempALMCell 3 Low Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV76bnC3HighReturnTempALMCell 3 High Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV77bnC3LowReturnTempALMCell 3 Low Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV78bnC3BYPConALMCell 3 Fan Bypass Contactor AlarmRead0=No Alarm, 1=Alarm
BV79bnC3VFDFaultALMCell 3 VFD Fault AlarmRead0=No Alarm, 1=Alarm
BV80bnC3DamperLimitSwitchFLTCell 3 Damper Limit Switch AlarmRead0=No Alarm, 1=Alarm
BV81bnC3VibrationFaultALMCell 3 Vibration Switch AlarmRead0=No Alarm, 1=Alarm
BV82bnC3PumpANoFlowCell 3 Pump No Flow AlarmRead0=No Alarm, 1=Alarm
BV83bnC3PumpARuntimeResetCell 3 Pump Runtime Reset StatusWrite0=No Reset, 1=Reset Runtime Hours
BV84bnC3FanRuntimeResetCell 3 Fan Runtime ResetWrite0=No Reset, 1=Reset Runtime Hours
BV85bnC4PumpAStatusCell 4 Pump StatusRead0=Off, 1=On
BV86bnC4PumpALockedStatusCell 4 Pump Locked StatusRead0=Pump Locked On, 1=Pump Not Locked On
BV87bnC4DischargeDamperAUXSwitchCell 4 Discharge Damper StatusRead0=Dampers Closed, 1=Dampers Open
BV88bnC4CyclePumpsCell 4 Cycle Pump Routine StatusRead0=Not Active, 1=Active
BV89bnC4VFDStatusCell 4 VFD StatusRead0=Off, 1=On
BV90bnC4FanMotorHeatersCell 4 Fan Space Heater StatusRead0=Off, 1=On
BV91bnC4PumpAConFaultCell 4 Pump Contactor AlarmRead0=No Alarm, 1=Alarm
BV92bnC4HighSupplyTempALMCell 4 High Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV93bnC4LowSupplyTempALMCell 4 Low Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV94bnC4HighReturnTempALMCell 4 High Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV95bnC4LowReturnTempALMCell 4 Low Return Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV96bnC4BYPConALMCell 4 Fan Bypass Contactor AlarmRead0=No Alarm, 1=Alarm
BV97bnC4VFDFaultALMCell 4 VFD Fault AlarmRead0=No Alarm, 1=Alarm
BV98bnC4DamperLimitSwitchFLTCell 4 Damper Limit Switch AlarmRead0=No Alarm, 1=Alarm
BV99bnC4VibrationFaultALMCell 4 Vibration Switch AlarmRead0=No Alarm, 1=Alarm
BV100bnC4PumpANoFlowCell 4 Pump No Flow AlarmRead0=No Alarm, 1=Alarm
BV101bnC4PumpARuntimeResetCell 4 Pump Runtime Reset StatusWrite0=No Reset, 1=Reset Runtime Hours
BV102bnC4FanRuntimeResetCell 4 Fan Runtime ResetWrite0=No Reset, 1=Reset Runtime Hours
BVmin103bnHighCommonTempALMHigh Common Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV104bnLowCommonTempALMLow Common Supply Water Temperature AlarmRead0=No Alarm, 1=Alarm
BV105bnLeadLagLockedLead/Lag Cell LockedRead0=Cell 2 Lead, 1=Cell 1 Lead
BV106bnC1MakeupDisableBASCell 1 Disable Make-upWrite0=Make-up Enabled (Default), 1=Drain Basin/Make-up Disabled
BV107bnC2MakeupDisableBASCell 2 Disable Make-upWrite0=Make-up Enabled (Default), 1=Drain Basin/Make-up Disabled
BV108bnCurrentOperationSystem Current OperationRead0=Automatic (Default), 1=Manual
BV109bnC4DischargeDamperCell 4 Discharge Damper StatusRead0=Dampers Closed, 1=Dampers Energized
AV0bnC1ReturnTempCell 1 return (entering) fluid temperature (value x10)°FRead
AV1bnC1SupplyTempCell 1 supply (leaving) fluid temperature (value x10)°FRead
AV2bnC1BasinWaterTempCell 1 basin water temperature (value x10)°FRead
AV3bnAmbientTempAmbient air temperature (value x10)°FRead
AV4bnC1PumpARuntimeCell 1 pump runtimehRead
AV5bnC1CyclePumpTimeCell 1 cycle-pumps routine time leftminRead
AV6bnC1DeicingTimeLeftCell 1 de-icing routine time leftminRead
AV7bnC1TimeLeftUnitDeicingStartCell 1 time until de-icing startsminRead
AV8bnC1PumpALockTimeCell 1 pump lock time leftminRead
AV9bnC1FanRuntimeCell 1 fan motor runtimehRead
AV10bnHeaterCntrlTempBasin heater on temperature (default 400 = 40.0 °F) (value x10)°FRead
AV11bnDeicingSeqStartTempLouver de-icing start temperature (default 400) (value x10)°FRead
AV12bnCurrentModeCurrent operating mode (0 = off)Read
AV13bnHotStartTimeLeftHot start routine time leftminRead
AV14bnHighReturnALMSPHigh return temperature alarm limit (default 1050) (value x10)°FWrite
AV15bnLowReturnALMSPLow return temperature alarm limit (default 850) (value x10)°FWrite
AV16bnHighSupplyALMSPHigh supply temperature alarm limit (default 950) (value x10)°FWrite
AV17bnLowSupplyALMSPLow supply temperature alarm limit (default 750) (value x10)°FWrite
AV18bnHighAmbientALMSPHigh ambient temperature alarm limit (default 1000) (value x10)°FWrite
AV19bnLowAmbientALMSPLow ambient temperature alarm limit (default 320) (value x10)°FWrite
AV20bnLowBasinTempALMSPLow basin temperature alarm limit (default 380) (value x10)°FWrite
AV21bnDamperOffsetTempSPDamper offset temperature (default 30) (value x10)°FWrite
AV22bnBasinHeaterTempSPBasin heater temperature setpoint (default 400) (value x10)°FWrite
AV23bnDeiceTempSPDe-icing temperature setpoint (default 400) (value x10)°FWrite
AVmin24bnBASSPBAS leaving fluid temperature setpoint (default 850) (value x10)°FWrite
AV25bnC2ReturnTempCell 2 return (entering) fluid temperature (value x10)°FRead
AV26bnC2SupplyTempCell 2 supply (leaving) fluid temperature (value x10)°FRead
AV27bnC2BasinWaterTempCell 2 basin water temperature (value x10)°FRead
AVmin28bnC1VFDSpeedCell 1 fan speed (value x10)%Read
AV29bnC2VFDSpeedCell 2 fan speed (value x10)%Read
AVmin30bnCommonLeavingTempAverage leaving fluid temperature, all cells (value x10)°FRead
AV31bnC2PumpARuntimeCell 2 pump runtimehRead
AV32bnC2CyclePumpTimeLeftCell 2 cycle-pumps routine time leftminRead
AV33bnC2TimeLeftUnitDeicingStartCell 2 time until de-icing startsminRead
AV34bnC2DeicingTimeLeftCell 2 de-icing routine time leftminRead
AV35bnC2PumpALockTimeCell 2 pump lock time leftminRead
AV36bnC2FanRuntimeCell 2 fan motor runtimehRead
AV37bnRecordLeadCellCurrent lead cellRead
AV38bnC3FanRuntimeCell 3 fan motor runtimehRead
AV39bnC3CyclePumpTimeLeftCell 3 cycle-pumps routine time leftminRead
AV40bnC3PumpALockTimeCell 3 pump lock time leftminRead
AV41bnC3PumpARuntimeCell 3 pump runtimehRead
AV42bnC3ReturnTempCell 3 return (entering) fluid temperature (value x10)°FRead
AV43bnC3SupplyTempCell 3 supply (leaving) fluid temperature (value x10)°FRead
AV44bnC3VFDSpeedCell 3 fan speed (value x10)%Read
AV45bnC4ReturnTempCell 4 return (entering) fluid temperature (value x10)°FRead
AV46bnC4SupplyTempCell 4 supply (leaving) fluid temperature (value x10)°FRead
AV47bnC4VFDSpeedCell 4 fan speed (value x10)%Read
AV48bnC4PumpARuntimeCell 4 pump runtimehRead
AV49bnC4CyclePumpTimeLeftCell 4 cycle-pumps routine time leftminRead
AV50bnC4PumpALockTimeCell 4 pump lock time leftminRead
AV51bnC4FanRuntimeCell 4 fan motor runtimehRead
AVmin52bnActiveSetpointActive fluid temperature setpoint (default 850) (value x10)°FRead
AV53bnTimeBTWNDeicingSequencesTime between de-icing startsminRead
Object ID lookup: EVAPCO Sage Water & Energy Conservation Control System point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Sage Water & Energy Conservation Control System (Sage PLC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EVAPCO Sage Water & Energy Conservation Control System (Sage PLC)

How many BACnet points does the EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) have?

This list has 164 BACnet objects: 54 analog values, 110 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) BACnet points are writable?

25 of the 164 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) BACnet documentation?

The source is Operations & Maintenance Instructions Addendum - Communications Guide for Sage Water & Energy Conservation Control System, revision Revision 1.3, published free by EVAPCO at https://www.evapco.com/media/1962586.

What are the minimum BACnet points to integrate the EVAPCO Sage Water & Energy Conservation Control System (Sage PLC)?

Start with BV 35 bnEnableSystem (System enable from the BMS (1 = enabled)); AV 24 bnBASSP (Leaving fluid setpoint, 0.1 °F (850 = 85.0 °F)); BV 36 bnALM_ACK (Acknowledge alarms (1 = acknowledge)); BV 25 bnLocalRemoteStatus (Control mode: 0 local, 1 remote); BV 26 bnSYSEnabled (System enabled status); AV 52 bnActiveSetpoint (Active fluid setpoint in use, 0.1 °F); AV 30 bnCommonLeavingTemp (Average leaving fluid temperature, 0.1 °F); AV 28 bnC1VFDSpeed (Cell 1 fan speed, 0.1 %); BV 21 bnC1VFDFaultALM (Cell 1 VFD fault alarm); BV 103 bnHighCommonTempALM (High common supply water temperature alarm).

How do I enable BMS control of the EVAPCO Sage Water & Energy Conservation Control System (Sage PLC)?

bnEnableSystem (BV 35) enables the system from the BMS; bnLocalRemoteStatus shows whether the panel is in local or remote control.

Does the EVAPCO Sage Water & Energy Conservation Control System (Sage PLC) need a BACnet heartbeat or have a communication timeout?

The guide lists bnBMSHeartbeat: 0 means waiting for the PLC to set it to 1 (5 s), 1 means waiting for the BMS to write it back to 0 (30 s). The guide does not say what the panel does when the BMS misses it. It is printed with the same instance as another object (BV 109), so confirm the live object before mapping it.

How do I check these points on the real Sage Water & Energy Conservation Control System (Sage PLC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EVAPCO BACnet points lists

Source: Operations & Maintenance Instructions Addendum - Communications Guide for Sage Water & Energy Conservation Control System · rev. Revision 1.3. Object names, instances and units are reproduced as published; descriptions are our own.