Dry / adiabatic fluid cooler controller · BACnet points list

EVAPCO eco-Air Controller (AC / NEMA Motors) BACnet points list

Updated 28 October 2026

Short answer

Same eco-Air PLC as the EC edition but for units with conventional AC fan motors, so the per-EC-fan objects are unused. BACnet IP runs on the Ethernet port and BACnet MS/TP on the RS-485 terminal shared with Modbus RTU. The object list covers enable and state, temperatures, setpoints, fan-speed limits, adiabatic pre-cooling stages and remote fan-speed control.

This page lists 68 BACnet objects for the EVAPCO eco-Air Controller (AC / NEMA Motors) — 38 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EVAPCO’s own free documentation, linked below.

Manufacturer
EVAPCO
Model
eco-Air Controller (AC / NEMA Motors)
Equipment
Dry / adiabatic fluid cooler controller
Equipment type
Cooling towers & fluid coolers
BACnet objects
68 (38 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
eco-Air PLC, EVAPCO Controller, COMM24 AC, COMM22NEMA, eco-Air NEMA motor
Source document
EVAPCO Controller User's Manual Addendum - Communications Guide AC Motor Edition · COMM24 AC-E · rev. 2025-10
Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: EVAPCO eco-Air Controller (AC / NEMA Motors)

Integration in brief

Select BACnet MS/TP or Modbus RTU for the serial port on the HMI (BACnet IP is always on the Ethernet port), set addresses under Service > BMS & Network, then use BV 0 to enable the unit from the BMS. Read AV 16, AV 0 and the common alarm and write AV 3 for the process setpoint; remote fan speed works through BV 77, AV 101 and AV 105.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0bnEnableUnitBMS enable/disable when configured for BMS enableWrite
AV 3bnSetpointTempPrimary process setpoint (writable)Write
AV 16bnUnitStateOperating state and reason it is offRead
AV 0bnOutletTempProcess fluid outlet temperatureRead
AV 2bnActiveSetpointSetpoint currently in controlRead
AV 33bnRefFanSpeedCommanded fan speedRead
BV 10bnCommonAlarmStatusCommon alarm output statusRead

Enable & remote start

Write BV 0 bnEnableUnit = 1 (only works when the unit is configured to be enabled via BMS); AV 16 = 4 means off via BMS.

Sensors & values from the BMS

Remote fan speed: BV 77 bnRemoteEnable = 1, AV 101 bnRemoteSource = 2 (Communication), then write AV 105. AV 103/AV 104 set the fallback speeds used if the analog speed input is lost.

Network setup

Watch out for

EVAPCO eco-Air Controller (AC / NEMA Motors) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

68 of 68 shown
Type
AnalogBinary
Access
Show
EVAPCO eco-Air Controller (AC / NEMA Motors) BACnet Points List
DescriptionStates
BVmin0bnEnableUnitEnables the unit if it is configured to be enabled via BMSWrite0=Unit not enabled, 1=Unit enabled
BV1bnRemoteDigitalState of remote digital inputRead0=No voltage present, 1=Voltage present
BV2bnProcessAlarmFault for either the outlet temperature sensor or the inlet pressureRead0=Normal, 1=Process sensor is not detected
BV3bnValveStatus1State of first adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV4bnValveStatus2State of second adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV5bnValveStatus3State of third adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV6bnValveStatus4State of fourth adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV7bnManualFlushManually starts the precooling flushing cycleWrite0=Not active, 1=Start manual flush
BV8bnReleasePrecoolRelease precoolWrite0=Precooling system will not function, 1=Precooling system will function when needed
BV9bnEnableCommonAlarmEnables the common alarm for the digital outputWrite0=Common alarm not enabled, 1=Common alarm enabled
BVmin10bnCommonAlarmStatusStatus of the alarm digital outputRead0=No alarm/not active, 1=Alarm/active
BV11bnForceFullSpeedForce full speedWrite0=Not enabled, 1=Forces fans to run at 100 percent fan speed
BV12bnEnableStageOntimeEnable stage ontimeWrite0=Not active, 1=Valve must remain on for the minimum run time
BV77bnRemoteEnableRemote enableWrite0=Not enabled, 1=Fan speed is controlled either by analog input or communication.
AVmin0bnOutletTempOutlet temperature of the process fluidDeg.Read
AV1bnAmbientTempTemperature detected by the ambient temperature sensorDeg.Read
AVmin2bnActiveSetpointActive set point that the eco-Air unit will maintainDeg.Read
AVmin3bnSetpointTempPrimary process temperature setpoint used when all other alternate setpoints are notDeg.Write
AV4bnSetpoint2TempTrigSetpoint that when the ambient temperature falls below, will switch the controlDeg.Write
AV5bnTempRegulationBandTemperature band between the minimum and maximum fan speed for P fanDeg.Write
AV6bnSetpoint2TempTrigDiffTemperature differential added to the ambient temperature setpoint 2 triggerDeg.Write
AV7bnPrecoolMinTempMinimum ambient temperature at which the precooling system may operateDeg.Write
AV8bnPrecoolMinTempDiffAmbient temperature offset added to the minimum allowable temperatureDeg.Write
AV9bnProportionalGainProportional gain constant used for the PID controllerUnitsWrite
AV10bnSwitchTemp1Minimum temperature, above which the precooling stage 1 has permission to operateDeg.Read
AV11bnSwitchTemp2Minimum temperature, above which the precooling stage 2 has permission to operateDeg.Read
AV12bnSwitchTemp3Minimum temperature, above which the precooling stage 3 has permission to operateDeg.Read
AV13bnSwitchTemp4Minimum temperature, above which the precooling stage 4 has permission to operateDeg.Read
AV14bnFlushFanSpeedDesired fan speed while performing a flushing cycle%Write
AV15bnSetpoint2TempAlternate process temperature set pointDeg.Write
AVmin16bnUnitStateCurrent state of the EVAPCO ControllerRead1=Unit on and operational, 2=Unit is off by an alarm, 4=Unit is off via BMS, Modbus/ BACnet, 6=Unit is off via the digital input, 7=Unit is switched off locally, 8=Manual mode enabled for fan speed control
AV17bnMinFanSpeedMinimum allowable fan speed%Write
AV18bnMaxFanSpeedMaximum allowable fan speed%Write
AV19bnEnergySaveFanSpeedFan speed, above which the precooling system will activate%Write
AV20bnQuietMaxFanSpeedMaximum allowable fan speed in quiet operation%Write
AV21bnPID_IntegralPID integral termSec.Write
AV22bnPID_DerivativePID derivative termSec.Write
AV23bnNumWetStagesCount of stages that have been enabled for the adiabatic systemUnitsRead
AV24bnPrecoolStage1_IncreaseCount of seconds that must pass with the process temperature above setSec.Write
AV25bnPrecoolStage1_DecreaseCount of seconds that must pass with the process temperature below setSec.Write
AV26bnRefrigerantFor condenser applicationsWrite1=R22, 2=R134a, 3=R404A, 4=R407C, 5=R410A, 6=R407A, 7=R407F, 8=R290, 9=R507A, 10=R717 (NH3), 11=R723, 12=R1234ze, 13=R744 (CO2), 14=R448A, 15=R427A, 16=R450A (N13), 17=R513A, 18=R449A, 19=R1234yf, 20=R454B, 21=R454C, 22=R455A, 23=434A, 24=R422A, 25=R32, 26=R452B, 27=R452A, 28=Custom
AV27bnPrecoolStage1_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV28bnPrecoolStage2_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV29bnPrecoolStage3_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV30bnPrecoolStage4_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV32bnInletPressureInlet pressure reading via pressure sensor inputPress.Read
AVmin33bnRefFanSpeedDesired fan speed determined by the controller%Read
AV34bnFlushingTimeCount of minutes to perform the flushing routine once initiatedMin.Write
AV35bnFlushTimeAccCount of seconds the flushing routine has been activeSec.Read
AV36bnDryingTimeCount of minutes to dry the pre-cooling padsMin.Write
AV37bnDryTimeAccCount of seconds the drying routine has been activeSec.Read
AV38bnFan_HoursCount of hours the fans have been operationalHoursRead
AV39bnPrecoolStage1_HoursCount of hours the first valve has been operationalHoursRead
AV40bnPrecoolStage2_HoursCount of hours the second valve has been operationalHoursRead
AV41bnPrecoolStage3_HoursCount of hours the third valve has been operationalHoursRead
AV42bnPrecoolStage4_HoursCount of hours the fourth valve has been operationalHoursRead
AV43bnPrecool24_IncreaseCount of seconds that must pass with the process temperature above setpointSec.Write
AV44bnPrecool24_DecreaseCount of seconds that must pass with the process temperature below setpointSec.Write
AV45bnPrecool24_DecreaseAccCount of seconds with the process temperature below setpointSec.Read
AV46bnPrecool1_DecreaseAccCount of seconds with the process temperature below setpointSec.Read
AV47bnPrecool24_IncreaseAccCount of seconds with the process temperature above the setpointSec.Read
AV48bnPrecool1_IncreaseAccCount of seconds with the process temperature above the setpointSec.Read
AV101bnRemoteSourceSource of the reference fan speed:Write1=Analog Input, 2=Communication see ANALOG_ VALUE:105
AV102bnRemoteAmbTrigWhen the source is set to Analog InputDeg.Write
AV103bnRemoteHighFanSpeedFan(s) will operate at the high default fan speed with a loss%Write
AV104bnRemoteLowFanSpeedFan(s) will operate at the low default fan speed with a loss%Write
AV105bnRemoteFanSpeedWith remote fan speed enabled and the source set to Communications%Write
AV106bnFanSpeedAIFan speed ai%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eco-Air Controller (AC / NEMA Motors) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EVAPCO eco-Air Controller (AC / NEMA Motors)

How many BACnet points does the EVAPCO eco-Air Controller (AC / NEMA Motors) have?

This list has 68 BACnet objects: 54 analog values, 14 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EVAPCO eco-Air Controller (AC / NEMA Motors) BACnet points are writable?

38 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EVAPCO eco-Air Controller (AC / NEMA Motors) BACnet documentation?

The source is EVAPCO Controller User's Manual Addendum - Communications Guide AC Motor Edition (COMM24 AC-E), revision 2025-10, published free by EVAPCO at https://www.evapco.eu/media/772760.

What are the minimum BACnet points to integrate the EVAPCO eco-Air Controller (AC / NEMA Motors)?

Start with BV 0 bnEnableUnit (BMS enable/disable when configured for BMS enable); AV 3 bnSetpointTemp (Primary process setpoint (writable)); AV 16 bnUnitState (Operating state and reason it is off); AV 0 bnOutletTemp (Process fluid outlet temperature); AV 2 bnActiveSetpoint (Setpoint currently in control); AV 33 bnRefFanSpeed (Commanded fan speed); BV 10 bnCommonAlarmStatus (Common alarm output status).

How do I enable BMS control of the EVAPCO eco-Air Controller (AC / NEMA Motors)?

Write BV 0 bnEnableUnit = 1 (only works when the unit is configured to be enabled via BMS); AV 16 = 4 means off via BMS.

Can the BMS supply sensor values to the EVAPCO eco-Air Controller (AC / NEMA Motors)?

Remote fan speed: BV 77 bnRemoteEnable = 1, AV 101 bnRemoteSource = 2 (Communication), then write AV 105. AV 103/AV 104 set the fallback speeds used if the analog speed input is lost.

How do I check these points on the real eco-Air Controller (AC / NEMA Motors)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EVAPCO BACnet points lists

Source: EVAPCO Controller User's Manual Addendum - Communications Guide AC Motor Edition · COMM24 AC-E · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.