Dry / adiabatic fluid cooler controller · BACnet points list

EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) BACnet points list

Updated 28 October 2026

Short answer

Earlier eco-Air controller generation whose native protocol is Modbus RTU; BACnet needs an optional expansion card (pCONet RS-485 card for MS/TP, pcoWeb Ethernet card for BACnet IP). Object instances use large numbers (BV 100009, AV 200001 and so on) and temperatures are scaled in tenths of a degree. Points cover enable, unit state, temperatures, setpoints, fan limits, pre-cooling stages and per-fan alarms.

This page lists 187 BACnet objects for the EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EVAPCO’s own free documentation, linked below.

Manufacturer
EVAPCO
Model
eco-Air Controller, pCO version (EC Fans, 2020)
Equipment
Dry / adiabatic fluid cooler controller
Equipment type
Cooling towers & fluid coolers
BACnet objects
187 (33 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
COMM20EC, eco-Air pCO, pcoWeb, pCONet, EVAPCO EC Fan Communications Guide
Source document
EVAPCO Controller User's Manual Addendum - Communications Guide EC Fan Edition · COMM20EC · rev. 2020-04
Download CSV 187 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: EVAPCO eco-Air Controller, pCO version (EC Fans, 2020)

Integration in brief

Fit the BACnet expansion card (pCONet for MS/TP or pcoWeb for IP), set its parameters through the controller BIOS menu, then enable the unit via BV 100009. Read AV 200001 unit state, AV 100001 outlet temperature and BV 100026 common alarm, and write AV 100004 for the process setpoint.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 100009Enable UnitBMS enable/disable when configured for BMS enableWrite
AV 100004Set Point 1 TemperaturePrimary process setpoint (writable)Write
AV 200001Actual Unit StateOperating state and reason it is offRead
AV 100001Outlet TemperatureProcess fluid outlet temperature (0.1 °F)Read
AV 100003Active Set PointSetpoint currently in controlRead
AV 200029Reference Fan SpeedCommanded fan speedRead
BV 100026Common Alarm Digital Output StatusCommon alarm output statusRead

Enable & remote start

Write BV 100009 Enable Unit = 1; it only applies when the unit is configured to be enabled via BMS. AV 200001 = 4 means off via Modbus/BACnet.

Network setup

Watch out for

EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

187 of 187 shown
Type
AnalogBinary
Access
Show
EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) BACnet Points List
DescriptionStates
BVmin100009Enable UnitEnables the unit if it is configured to be enabled via BMSWrite0=Unit not enabled, 1=Unit enabled
BV100011Remote Digital Input StateState of remote digital inputRead0=No voltage present, 1=Voltage present
BV100016Process Sensor AlarmFault for either the outlet temperature sensor or the inlet pressureRead0=Normal, 1=Process sensor is not detected
BV100019Pre-cooling Valve 1 StatusState of first adiabatic pre-cooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV100020Pre-cooling Valve 2 StatusState of second adiabatic pre-cooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV100021Pre-cooling Valve 3 StatusState of third adiabatic pre-cooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV100022Pre-cooling Valve 4 StatusState of fourth adiabatic pre-cooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV100023Activate Manual FlushManually starts the flushing cycle of the adiabatic systemWrite0=Not active, 1=Start manual flush
BV100024Release Pre-cooling SystemRelease Pre-cooling SystemWrite0=Pre-cooling system will not function, 1=Pre-cooling system will function when needed
BV100025Enable Common AlarmEnables the common alarm for the digital outputWrite0=Common alarm not enabled, 1=Common alarm enabled
BVmin100026Common Alarm Digital Output StatusStatus of the alarm digital outputRead0=No alarm/not active, 1=Alarm/active
BV100035Force Fans to Run at Full SpeedForce Fans to Run at Full SpeedWrite0=Not enabled, 1=Forces fans to run at 100 percent fan speed
BV100037Enable Stage OntimeWhen active, the pre-cooling system will honor the minimum on timeWrite0=Not active, 1=Active
BV100401Fan 1 AlarmFan 1 AlarmRead0=Normal, 1=Alarm present
BV100402Fan 1 Communication StatusThis is the communication link between the Evapco controller and the fanRead0=Fan not online, 1=Fan is online
BV100411Fan 2 AlarmFan 2 AlarmRead0=Normal, 1=Alarm present
BV100412Fan 2 Communication StatusFan 2 Communication StatusRead0=Fan not online, 1=Fan is online
BV100421Fan 3 AlarmFan 3 AlarmRead0=Normal, 1=Alarm present
BV100422Fan 3 Communication StatusFan 3 Communication StatusRead0=Fan not online, 1=Fan is online
BV100431Fan 4 AlarmFan 4 AlarmRead0=Normal, 1=Alarm present
BV100432Fan 4 Communication StatusFan 4 Communication StatusRead0=Fan not online, 1=Fan is online
BV100441Fan 5 AlarmFan 5 AlarmRead0=Normal, 1=Alarm present
BV100442Fan 5 Communication StatusFan 5 Communication StatusRead0=Fan not online, 1=Fan is online
BV100451Fan 6 AlarmFan 6 AlarmRead0=Normal, 1=Alarm present
BV100452Fan 6 Communication StatusFan 6 Communication StatusRead0=Fan not online, 1=Fan is online
BV100461Fan 7 AlarmFan 7 AlarmRead0=Normal, 1=Alarm present
BV100462Fan 7 Communication StatusFan 7 Communication StatusRead0=Fan not online, 1=Fan is online
BV100471Fan 8 AlarmFan 8 AlarmRead0=Normal, 1=Alarm present
BV100472Fan 8 Communication StatusFan 8 Communication StatusRead0=Fan not online, 1=Fan is online
BV100481Fan 9 AlarmFan 9 AlarmRead0=Normal, 1=Alarm present
BV100482Fan 9 Communication StatusFan 9 Communication StatusRead0=Fan not online, 1=Fan is online
BV100491Fan 10 AlarmFan 10 AlarmRead0=Normal, 1=Alarm present
BV100492Fan 10 Communication StatusFan 10 Communication StatusRead0=Fan not online, 1=Fan is online
BV100501Fan 11 AlarmFan 11 AlarmRead0=Normal, 1=Alarm present
BV100502Fan 11 Communication StatusFan 11 Communication StatusRead0=Fan not online, 1=Fan is online
BV100511Fan 12 AlarmFan 12 AlarmRead0=Normal, 1=Alarm present
BV100512Fan 12 Communication StatusFan 12 Communication StatusRead0=Fan not online, 1=Fan is online
BV100521Fan 13 AlarmFan 13 AlarmRead0=Normal, 1=Alarm present
BV100522Fan 13 Communication StatusFan 13 Communication StatusRead0=Fan not online, 1=Fan is online
BV100531Fan 14 AlarmFan 14 AlarmRead0=Normal, 1=Alarm present
BV100532Fan 14 Communication StatusFan 14 Communication StatusRead0=Fan not online, 1=Fan is online
BV100541Fan 15 AlarmFan 15 AlarmRead0=Normal, 1=Alarm present
BV100542Fan 15 Communication StatusFan 15 Communication StatusRead0=Fan not online, 1=Fan is online
BV100551Fan 16 AlarmFan 16 AlarmRead0=Normal, 1=Alarm present
BV100552Fan 16 Communication StatusFan 16 Communication StatusRead0=Fan not online, 1=Fan is online
BV100561Fan 17 AlarmFan 17 AlarmRead0=Normal, 1=Alarm present
BV100562Fan 17 Communication StatusFan 17 Communication StatusRead0=Fan not online, 1=Fan is online
BV100571Fan 18 AlarmFan 18 AlarmRead0=Normal, 1=Alarm present
BV100572Fan 18 Communication StatusFan 18 Communication StatusRead0=Fan not online, 1=Fan is online
BV100581Fan 19 AlarmFan 19 AlarmRead0=Normal, 1=Alarm present
BV100582Fan 19 Communication StatusFan 19 Communication StatusRead0=Fan not online, 1=Fan is online
BV100591Fan 20 AlarmFan 20 AlarmRead0=Normal, 1=Alarm present
BV100592Fan 20 Communication StatusFan 20 Communication StatusRead0=Fan not online, 1=Fan is online
AVmin100001Outlet TemperatureOutlet temperature of the process fluid0.1°FRead
AV100002Ambient TemperatureTemperature detected by the ambient temperature sensor0.1°FRead
AVmin100003Active Set PointActive set point that the eco-Air unit will maintain0.1°FRead
AVmin100004Set Point 1 TemperaturePrimary process temperature setpoint used when all other alternate setpoints are not0.1°FWrite
AV100005Set Point 2 Ambient Temperature TriggerSet point that when the ambient temperature falls below, will switch0.1°FWrite
AV100006Temperature Regulation BandTemperature band between the minimum and maximum fan speed for P fan0.1°FWrite
AV100007Set Point 2 Ambient Temperature Trigger DifferentialTemperature differential added to the ambient temperature set point 2 trigger0.1°FWrite
AV100008Pre-cooling Minimum Allowable Temperature Set PointMinimum ambient temperature at which the precooling system may operate0.1°FWrite
AV100009Pre-cooling Minimum Allowable Temperature DifferenceAmbient temperature offset added to the minimum allowable temperature0.1°FWrite
AV100010Proportional GainProportional gain constant used for the PID controller0.1gWrite
AV100017Switch Point #1 TemperatureMinimum temperature above which pre-cooling stage 1 will activate0.1°FRead
AV100018Switch Point #2 TemperatureMinimum temperature above which pre-cooling stage 2 will activate0.1°FRead
AV100019Switch Point #3 TemperatureMinimum temperature above which pre-cooling stage 3 will activate0.1°FRead
AV100020Switch Point #4 TemperatureMinimum temperature above which pre-cooling stage 4 will activate0.1°FRead
AV100022Flushing Fan SpeedDesired fan speed while performing a flushing cycle%Write
AV100023Set Point 2 TemperatureAlternate process temperature set point0.1°FWrite
AVmin200001Actual Unit StateCurrent state of the EVAPCO ControllerRead1=Unit on and operational, 2=Unit is off by an alarm, 4=Unit is off via Modbus/BACnet, 5=Unit is off via the scheduler, 6=Unit is off via the digital input, 7=Unit is switched off locally
AV200002Minimum Allowed Fan SpeedMinimum allowable fan speed%Write
AV200003Maximum Allowed Fan SpeedMaximum allowable fan speed%Write
AV200004Energy Savings Fan SpeedFan speed above which the pre-cooling system will activate%Write
AV200005Quiet Operation Maximum Fan SpeedMaximum allowable fan speed in quiet operation%Write
AV200006PID Integral TermPID integral termSecondsWrite
AV200007PID Differential TermPID differential termSecondsWrite
AV200008Fan Operating Hours (Thousands)Count of hours the fan(s) have been operational1000 HoursRead
AV200010Number of wet stagesCount of stages that have been enabled for the adiabatic systemUnitsRead
AV200011Pre-cooling Stage 1 Increase Delay Set PointCount of seconds that must pass with the process temperature above setSecondsWrite
AV200012Pre-cooling Stage 1 Decrease Delay Set pointCount of seconds that must pass with the process temperature below setSecondsWrite
AV200013Pre-cooling Stage 2 Operating Hours (Thousands)Count of hours the pre-cooling stage has been operational1000 HoursRead
AV200014RefrigerantFor condenser applicationsWrite0=R22, 1=R134a, 2=R404A, 3=R407C, 4=R410A, 5=R507, 6=R290, 7=R600, 8=R600a, 9=R717, 10=R744, 11=R728, 12=R1270, 13=R417A, 14=R422d, 15=R413A, 16=R422A, 17=R423A, 18=R407A, 19=R427A, 20=R245Fa, 21=R407F
AV200015Pre-cooling Stage 3 Operating Hours (Thousands)Count of hours the pre-cooling stage has been operational1000 HoursRead
AV200016Pre-cooling Stage 1 Minimum On TimeMinimum amount of time the pre-cooling stage remains activeSecondsWrite
AV200017Pre-cooling Stage 2 Minimum On TimeMinimum amount of time the pre-cooling stage remains activeSecondsWrite
AV200018Pre-cooling Stage 3 Minimum On TimeMinimum amount of time the pre-cooling stage remains activeSecondsWrite
AV200019Pre-cooling Stage 4 Minimum On TimeMinimum amount of time the pre-cooling stage remains activeSecondsWrite
AV200021Failsafe Mode Fan SpeedSpeed at which the fans will operate in Failsafe mode%Write
AV200028Inlet PressureInlet pressure reading via pressure sensor input0.1 psiRead
AVmin200029Reference Fan SpeedDesired fan speed determined by the controller%Read
AV200030Flushing TimeCount of minutes to perform the flushing routine once initiatedMinutesWrite
AV200036Flushing Time AccumulatorCount of seconds the flushing routine has been activeSecondsRead
AV200037Drying TimeCount of minutes to dry the pre-cooling padsMinutesWrite
AV200038Drying Time AccumulatorCount of seconds the drying routine has been activeSecondsRead
AV200039Pre-cooling Stage 4 Operating Hours (Thousands)Count of hours the pre-cooling stage has been operational1000 HoursRead
AV200040Pre-cooling Stage 1 Operating Hours (Thousands)Count of hours the pre-cooling stage has been operational1000 HoursRead
AV200041Fan Operating HoursCount of hours the fan(s) have been operational x 1HoursRead
AV200042Pre-cooling Stage 1 Operating HoursCount of hours the pre-cooling stage has been operationalHoursRead
AV200043Pre-cooling Stage 2 Operating HoursCount of hours the pre-cooling stage has been operationalHoursRead
AV200044Pre-cooling Stage 3 Operating HoursCount of hours the pre-cooling stage has been operationalHoursRead
AV200045Pre-cooling Stage 4 Operating HoursCount of hours the pre-cooling stage has been operationalHoursRead
AV200049Pre-cooling Stage 2-4 Increase Delay Set PointCount of seconds that must pass with the process fluid temperature aboveSecondsWrite
AV200050Pre-cooling Stage 2-4 Decrease Delay Set PointCount of seconds that must pass with the process fluid temperature belowSecondsWrite
AV200051Pre-cooling Stage 2-4 Decrease Delay AccumulatorCount of seconds with the process fluid below set pointSecondsRead
AV200052Pre-cooling Stage 1 Decrease Delay AccumulatorCount of seconds with the process fluid below set pointSecondsRead
AV200053Pre-cooling Stage 2-4 Increase Delay AccumulatorCount of seconds with the process fluid above set pointSecondsRead
AV200054Pre-cooling Stage 1 Increase Delay AccumulatorCount of seconds with the process fluid above set pointSecondsRead
AV200403ebm Fan 1 Alarm Codeebm Fan 1 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200404ebm Fan 1 Warning Codeebm Fan 1 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200405ebm Fan 1 Warning Bitsebm Fan 1 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200406ebm Fan 1 Alarm Bitsebm Fan 1 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200413ebm Fan 2 Alarm Codeebm Fan 2 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200414ebm Fan 2 Warning Codeebm Fan 2 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200415ebm Fan 2 Warning Bitsebm Fan 2 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200416ebm Fan 2 Alarm Bitsebm Fan 2 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200423ebm Fan 3 Alarm Codeebm Fan 3 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200424ebm Fan 3 Warning Codeebm Fan 3 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200425ebm Fan 3 Warning Bitsebm Fan 3 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200426ebm Fan 3 Alarm Bitsebm Fan 3 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200433ebm Fan 4 Alarm Codeebm Fan 4 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200434ebm Fan 4 Warning Codeebm Fan 4 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200435ebm Fan 4 Warning Bitsebm Fan 4 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200436ebm Fan 4 Alarm Bitsebm Fan 4 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200443ebm Fan 5 Alarm Codeebm Fan 5 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200444ebm Fan 5 Warning Codeebm Fan 5 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200445ebm Fan 5 Warning Bitsebm Fan 5 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200446ebm Fan 5 Alarm Bitsebm Fan 5 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200453ebm Fan 6 Alarm Codeebm Fan 6 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200454ebm Fan 6 Warning Codeebm Fan 6 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200455ebm Fan 6 Warning Bitsebm Fan 6 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200456ebm Fan 6 Alarm Bitsebm Fan 6 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200463ebm Fan 7 Alarm Codeebm Fan 7 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200464ebm Fan 7 Warning Codeebm Fan 7 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200465ebm Fan 7 Warning Bitsebm Fan 7 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200466ebm Fan 7 Alarm Bitsebm Fan 7 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200473ebm Fan 8 Alarm Codeebm Fan 8 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200474ebm Fan 8 Warning Codeebm Fan 8 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200475ebm Fan 8 Warning Bitsebm Fan 8 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200476ebm Fan 8 Alarm Bitsebm Fan 8 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200483ebm Fan 9 Alarm Codeebm Fan 9 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200484ebm Fan 9 Warning Codeebm Fan 9 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200485ebm Fan 9 Warning Bitsebm Fan 9 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200486ebm Fan 9 Alarm Bitsebm Fan 9 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200493ebm Fan 10 Alarm Codeebm Fan 10 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200494ebm Fan 10 Warning Codeebm Fan 10 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200495ebm Fan 10 Warning Bitsebm Fan 10 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200496ebm Fan 10 Alarm Bitsebm Fan 10 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200503ebm Fan 11 Alarm Codeebm Fan 11 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200504ebm Fan 11 Warning Codeebm Fan 11 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200505ebm Fan 11 Warning Bitsebm Fan 11 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200506ebm Fan 11 Alarm Bitsebm Fan 11 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200513ebm Fan 12 Alarm Codeebm Fan 12 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200514ebm Fan 12 Warning Codeebm Fan 12 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200515ebm Fan 12 Warning Bitsebm Fan 12 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200516ebm Fan 12 Alarm Bitsebm Fan 12 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200523ebm Fan 13 Alarm Codeebm Fan 13 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200524ebm Fan 13 Warning Codeebm Fan 13 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200525ebm Fan 13 Warning Bitsebm Fan 13 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200526ebm Fan 13 Alarm Bitsebm Fan 13 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200533ebm Fan 14 Alarm Codeebm Fan 14 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200534ebm Fan 14 Warning Codeebm Fan 14 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200535ebm Fan 14 Warning Bitsebm Fan 14 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200536ebm Fan 14 Alarm Bitsebm Fan 14 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200543ebm Fan 15 Alarm Codeebm Fan 15 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200544ebm Fan 15 Warning Codeebm Fan 15 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200545ebm Fan 15 Warning Bitsebm Fan 15 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200546ebm Fan 15 Alarm Bitsebm Fan 15 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200553ebm Fan 16 Alarm Codeebm Fan 16 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200554ebm Fan 16 Warning Codeebm Fan 16 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200555ebm Fan 16 Warning Bitsebm Fan 16 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200556ebm Fan 16 Alarm Bitsebm Fan 16 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200563ebm Fan 17 Alarm Codeebm Fan 17 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200564ebm Fan 17 Warning Codeebm Fan 17 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200565ebm Fan 17 Warning Bitsebm Fan 17 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200566ebm Fan 17 Alarm Bitsebm Fan 17 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200573ebm Fan 18 Alarm Codeebm Fan 18 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200574ebm Fan 18 Warning Codeebm Fan 18 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200575ebm Fan 18 Warning Bitsebm Fan 18 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200576ebm Fan 18 Alarm Bitsebm Fan 18 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200583ebm Fan 19 Alarm Codeebm Fan 19 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200584ebm Fan 19 Warning Codeebm Fan 19 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200585ebm Fan 19 Warning Bitsebm Fan 19 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200586ebm Fan 19 Alarm Bitsebm Fan 19 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage
AV200593ebm Fan 20 Alarm Codeebm Fan 20 Alarm CodeRead0=No Alarm, 1=Fan Offline, 2=Phase Fault, 3=Motor Blocked, 4=Low Input Voltage, 5=High Input Voltage, 6=DC Link Overvoltage, 7=DC Link Undervoltage, 8=Motor Overheating, 9=Internal Circuit Overheating, 10=Output Stage Overheating, 11=Hall Sensor Error, 12=Communication Error, 13=Generic Error
AV200594ebm Fan 20 Warning Codeebm Fan 20 Warning CodeRead0=No Warning, 1=Output Stage High Temperature, 2=Internal Circuit High Temperature, 3=High Motor Temperature, 4=Low DC Link Voltage, 5=Power Is Limited, 6=Current Is Limited, 7=Brake Mode Active
AV200595ebm Fan 20 Warning Bitsebm Fan 20 Warning BitsReadbit 0=Current Is Limited, bit 1=Not Used, bit 2=Power Is Limited, bit 3=Output Stage High Temperature, bit 4=High Motor Temperature, bit 5=Internal Circuit High Temperature, bit 6=Low DC Link Voltage, bit 7=Brake Mode Active
AV200596ebm Fan 20 Alarm Bitsebm Fan 20 Alarm BitsReadbit 0=Phase Fault, bit 1=Not Used, bit 2=Output Stage Overheating, bit 3=Communication Error, bit 4=Generic Error, bit 5=Motor Overheating, bit 6=Hall Sensor Error, bit 7=Motor Blocked, bit 8=Not Used, bit 9=Internal Circuit Overheating, bit 10=Not Used, bit 11=DC Link Overvoltage, bit 12=DC Link Undervoltage, bit 13=Low Input Voltage, bit 14=High Input Voltage

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eco-Air Controller, pCO version (EC Fans, 2020) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EVAPCO eco-Air Controller, pCO version (EC Fans, 2020)

How many BACnet points does the EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) have?

This list has 187 BACnet objects: 134 analog values, 53 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) BACnet points are writable?

33 of the 187 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EVAPCO eco-Air Controller, pCO version (EC Fans, 2020) BACnet documentation?

The source is EVAPCO Controller User's Manual Addendum - Communications Guide EC Fan Edition (COMM20EC), revision 2020-04, published free by EVAPCO at https://www.evapco.com/sites/evapco.com/files/2020-04/Communications%20Guide%20EC%20Motors%20.pdf.

What are the minimum BACnet points to integrate the EVAPCO eco-Air Controller, pCO version (EC Fans, 2020)?

Start with BV 100009 Enable Unit (BMS enable/disable when configured for BMS enable); AV 100004 Set Point 1 Temperature (Primary process setpoint (writable)); AV 200001 Actual Unit State (Operating state and reason it is off); AV 100001 Outlet Temperature (Process fluid outlet temperature (0.1 °F)); AV 100003 Active Set Point (Setpoint currently in control); AV 200029 Reference Fan Speed (Commanded fan speed); BV 100026 Common Alarm Digital Output Status (Common alarm output status).

How do I enable BMS control of the EVAPCO eco-Air Controller, pCO version (EC Fans, 2020)?

Write BV 100009 Enable Unit = 1; it only applies when the unit is configured to be enabled via BMS. AV 200001 = 4 means off via Modbus/BACnet.

How do I check these points on the real eco-Air Controller, pCO version (EC Fans, 2020)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EVAPCO BACnet points lists

Source: EVAPCO Controller User's Manual Addendum - Communications Guide EC Fan Edition · COMM20EC · rev. 2020-04. Object names, instances and units are reproduced as published; descriptions are our own.