Dry / adiabatic fluid cooler controller · BACnet points list
EVAPCO eco-Air Controller (EC Fan Motors) BACnet points list
Updated 28 October 2026
The eco-Air PLC panel exposes BACnet IP on its Ethernet port and BACnet MS/TP on a shared RS-485 terminal that can run either MS/TP or Modbus RTU, chosen on the HMI. Objects are plain Binary and Analog Values numbered from 0, covering unit enable and state, process and ambient temperature, setpoints, fan-speed limits, adiabatic pre-cooling stages and per-fan EC motor alarms, speeds and communication status.
This page lists 185 BACnet objects for the EVAPCO eco-Air Controller (EC Fan Motors) — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EVAPCO’s own free documentation, linked below.
- Manufacturer
- EVAPCO
- Model
- eco-Air Controller (EC Fan Motors)
- Equipment
- Dry / adiabatic fluid cooler controller
- Equipment type
- Cooling towers & fluid coolers
- BACnet objects
- 185 (39 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- eco-Air PLC, EVAPCO Controller, COMM24 EC, eco-Air EC, eco-Air adiabatic cooler controller
BMS integration notes: EVAPCO eco-Air Controller (EC Fan Motors)
Pick MS/TP or Modbus RTU for the serial port on the HMI (BACnet IP is always live on Ethernet), set the addresses under Service > BMS & Network, then enable the unit through BV 0 if it is configured for BMS enable. Monitor AV 16 unit state, AV 0 outlet temperature and the common alarm, and write AV 3 for the process setpoint. For BMS fan-speed control enable BV 77, set AV 101 to Communication and write AV 105.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | bnEnableUnit | BMS enable/disable when configured for BMS enable | Write |
| AV 3 | bnSetpointTemp | Primary process setpoint (writable) | Write |
| AV 16 | bnUnitState | Operating state and reason it is off | Read |
| AV 0 | bnOutletTemp | Process fluid outlet temperature | Read |
| AV 2 | bnActiveSetpoint | Setpoint currently in control | Read |
| AV 33 | bnRefFanSpeed | Commanded fan speed | Read |
| BV 10 | bnCommonAlarmStatus | Common alarm output status | Read |
Enable & remote start
Write BV 0 bnEnableUnit = 1; it only takes effect when the unit is configured to be enabled via BMS. AV 16 reports 4 when the unit is off via BMS.
Sensors & values from the BMS
Fan speed can be driven remotely: set BV 77 bnRemoteEnable = 1, AV 101 bnRemoteSource = 2 (Communication) and write AV 105 bnRemoteFanSpeed. AV 103/AV 104 are fallback high/low speeds used when the analog speed input is lost, chosen by ambient against AV 102.
Network setup
- Default communication parameters are printed on page 1 of the panel wiring diagram, not in this guide.
- Change BACnet/Modbus settings with the unit switched off: log in at Service level, Service > BMS & Network, then hold Update for 3 s (HMI and PLC restart).
- The RS-485 port runs either BACnet MS/TP or Modbus RTU, never both; BACnet IP and Modbus TCP share the Ethernet port and both stay active.
Watch out for
- Writable parameters are stored in the PLC's non-volatile memory, rated for about 100,000 writes; never write them cyclically.
- Points marked for adiabatic units (pre-cooling valves, flush, wet-stage timers) can be ignored on dry-only units.
- Per-fan point blocks repeat for each EC fan; unused fan numbers will read normal/offline.
EVAPCO eco-Air Controller (EC Fan Motors) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | bnEnableUnit | Enables the unit if it is configured to be enabled via BMS | Write | 0=Unit not enabled, 1=Unit enabled | |
| BV | 1 | bnRemoteDigital | State of remote digital input | Read | 0=No voltage present, 1=Voltage present | |
| BV | 2 | bnProcessAlarm | Fault for either the outlet temperature sensor or the inlet pressure | Read | 0=Normal, 1=Process sensor is not detected | |
| BV | 3 | bnValveStatus1 | State of first adiabatic precooling valve | Read | 0=Valve off (water not flowing), 1=Valve on (water flowing) | |
| BV | 4 | bnValveStatus2 | State of second adiabatic precooling valve | Read | 0=Valve off (water not flowing), 1=Valve on (water flowing) | |
| BV | 5 | bnValveStatus3 | State of third adiabatic precooling valve | Read | 0=Valve off (water not flowing), 1=Valve on (water flowing) | |
| BV | 6 | bnValveStatus4 | State of fourth adiabatic precooling valve | Read | 0=Valve off (water not flowing), 1=Valve on (water flowing) | |
| BV | 7 | bnManualFlush | Manually starts the precooling flushing cycle | Write | 0=Not active, 1=Start manual flush | |
| BV | 8 | bnReleasePrecool | Release precool | Write | 0=Precooling system will not function, 1=Precooling system will function when needed | |
| BV | 9 | bnEnableCommonAlarm | Enables the common alarm for the digital output | Write | 0=Common alarm not enabled, 1=Common alarm enabled | |
| BVmin | 10 | bnCommonAlarmStatus | Status of the alarm digital output | Read | 0=No alarm/not active, 1=Alarm/active | |
| BV | 11 | bnForceFullSpeed | Force full speed | Write | 0=Not enabled, 1=Forces fans to run at 100 percent fan speed | |
| BV | 12 | bnEnableStageOntime | Enable stage ontime | Write | 0=Not active, 1=Valve must remain on for the minimum run time | |
| BV | 13 | bnAlarmPresent_EBM_01 | Alarm present ebm fan 01 | Read | 0=Normal, 1=Alarm present | |
| BV | 14 | bnAlarmPresent_EBM_02 | Alarm present ebm fan 02 | Read | 0=Normal, 1=Alarm present | |
| BV | 15 | bnAlarmPresent_EBM_03 | Alarm present ebm fan 03 | Read | 0=Normal, 1=Alarm present | |
| BV | 16 | bnAlarmPresent_EBM_04 | Alarm present ebm fan 04 | Read | 0=Normal, 1=Alarm present | |
| BV | 17 | bnAlarmPresent_EBM_05 | Alarm present ebm fan 05 | Read | 0=Normal, 1=Alarm present | |
| BV | 18 | bnAlarmPresent_EBM_06 | Alarm present ebm fan 06 | Read | 0=Normal, 1=Alarm present | |
| BV | 19 | bnAlarmPresent_EBM_07 | Alarm present ebm fan 07 | Read | 0=Normal, 1=Alarm present | |
| BV | 20 | bnAlarmPresent_EBM_08 | Alarm present ebm fan 08 | Read | 0=Normal, 1=Alarm present | |
| BV | 21 | bnAlarmPresent_EBM_09 | Alarm present ebm fan 09 | Read | 0=Normal, 1=Alarm present | |
| BV | 22 | bnAlarmPresent_EBM_10 | Alarm present ebm fan 10 | Read | 0=Normal, 1=Alarm present | |
| BV | 23 | bnAlarmPresent_EBM_11 | Alarm present ebm fan 11 | Read | 0=Normal, 1=Alarm present | |
| BV | 24 | bnAlarmPresent_EBM_12 | Alarm present ebm fan 12 | Read | 0=Normal, 1=Alarm present | |
| BV | 25 | bnAlarmPresent_EBM_13 | Alarm present ebm fan 13 | Read | 0=Normal, 1=Alarm present | |
| BV | 26 | bnAlarmPresent_EBM_14 | Alarm present ebm fan 14 | Read | 0=Normal, 1=Alarm present | |
| BV | 27 | bnAlarmPresent_EBM_15 | Alarm present ebm fan 15 | Read | 0=Normal, 1=Alarm present | |
| BV | 28 | bnAlarmPresent_EBM_16 | Alarm present ebm fan 16 | Read | 0=Normal, 1=Alarm present | |
| BV | 29 | bnAlarmPresent_EBM_17 | Alarm present ebm fan 17 | Read | 0=Normal, 1=Alarm present | |
| BV | 30 | bnAlarmPresent_EBM_18 | Alarm present ebm fan 18 | Read | 0=Normal, 1=Alarm present | |
| BV | 31 | bnAlarmPresent_EBM_19 | Alarm present ebm fan 19 | Read | 0=Normal, 1=Alarm present | |
| BV | 32 | bnAlarmPresent_EBM_20 | Alarm present ebm fan 20 | Read | 0=Normal, 1=Alarm present | |
| BV | 33 | bnOnline_EBM_01 | This is the communication link between the Evapco controller and the fan | Read | 0=Fan not online, 1=Fan is online | |
| BV | 34 | bnOnline_EBM_02 | Online ebm fan 02 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 35 | bnOnline_EBM_03 | Online ebm fan 03 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 36 | bnOnline_EBM_04 | Online ebm fan 04 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 37 | bnOnline_EBM_05 | Online ebm fan 05 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 38 | bnOnline_EBM_06 | Online ebm fan 06 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 39 | bnOnline_EBM_07 | Online ebm fan 07 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 40 | bnOnline_EBM_08 | Online ebm fan 08 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 41 | bnOnline_EBM_09 | Online ebm fan 09 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 42 | bnOnline_EBM_10 | Online ebm fan 10 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 43 | bnOnline_EBM_11 | Online ebm fan 11 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 44 | bnOnline_EBM_12 | Online ebm fan 12 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 45 | bnOnline_EBM_13 | Online ebm fan 13 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 46 | bnOnline_EBM_14 | Online ebm fan 14 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 47 | bnOnline_EBM_15 | Online ebm fan 15 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 48 | bnOnline_EBM_16 | Online ebm fan 16 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 49 | bnOnline_EBM_17 | Online ebm fan 17 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 50 | bnOnline_EBM_18 | Online ebm fan 18 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 51 | bnOnline_EBM_19 | Online ebm fan 19 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 52 | bnOnline_EBM_20 | Online ebm fan 20 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 53 | bnAlarmPresent_EF_01 | Alarm present eflow fan 01 | Read | 0=Normal, 1=Alarm present | |
| BV | 54 | bnAlarmPresent_EF_02 | Alarm present eflow fan 02 | Read | 0=Normal, 1=Alarm present | |
| BV | 55 | bnAlarmPresent_EF_03 | Alarm present eflow fan 03 | Read | 0=Normal, 1=Alarm present | |
| BV | 56 | bnAlarmPresent_EF_04 | Alarm present eflow fan 04 | Read | 0=Normal, 1=Alarm present | |
| BV | 57 | bnAlarmPresent_EF_05 | Alarm present eflow fan 05 | Read | 0=Normal, 1=Alarm present | |
| BV | 58 | bnAlarmPresent_EF_06 | Alarm present eflow fan 06 | Read | 0=Normal, 1=Alarm present | |
| BV | 59 | bnAlarmPresent_EF_07 | Alarm present eflow fan 07 | Read | 0=Normal, 1=Alarm present | |
| BV | 60 | bnAlarmPresent_EF_08 | Alarm present eflow fan 08 | Read | 0=Normal, 1=Alarm present | |
| BV | 61 | bnAlarmPresent_EF_09 | Alarm present eflow fan 09 | Read | 0=Normal, 1=Alarm present | |
| BV | 62 | bnAlarmPresent_EF_10 | Alarm present eflow fan 10 | Read | 0=Normal, 1=Alarm present | |
| BV | 63 | bnAlarmPresent_EF_11 | Alarm present eflow fan 11 | Read | 0=Normal, 1=Alarm present | |
| BV | 64 | bnAlarmPresent_EF_12 | Alarm present eflow fan 12 | Read | 0=Normal, 1=Alarm present | |
| BV | 65 | bnOnline_EF_01 | This is the communication link between the Evapco controller and the fan | Read | 0=Fan not online, 1=Fan is online | |
| BV | 66 | bnOnline_EF_02 | Online eflow fan 02 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 67 | bnOnline_EF_03 | Online eflow fan 03 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 68 | bnOnline_EF_04 | Online eflow fan 04 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 69 | bnOnline_EF_05 | Online eflow fan 05 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 70 | bnOnline_EF_06 | Online eflow fan 06 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 71 | bnOnline_EF_07 | Online eflow fan 07 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 72 | bnOnline_EF_08 | Online eflow fan 08 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 73 | bnOnline_EF_09 | Online eflow fan 09 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 74 | bnOnline_EF_10 | Online eflow fan 10 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 75 | bnOnline_EF_11 | Online eflow fan 11 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 76 | bnOnline_EF_12 | Online eflow fan 12 | Read | 0=Fan not online, 1=Fan is online | |
| BV | 77 | bnRemoteEnable | Remote enable | Write | 0=Not enabled, 1=Fan speed is controlled either by analog input or communication. | |
| AVmin | 0 | bnOutletTemp | Outlet temperature of the process fluid | Deg. | Read | |
| AV | 1 | bnAmbientTemp | Temperature detected by the ambient temperature sensor | Deg. | Read | |
| AVmin | 2 | bnActiveSetpoint | Active set point that the eco-Air unit will maintain | Deg. | Read | |
| AVmin | 3 | bnSetpointTemp | Primary process temperature setpoint used when all other alternate setpoints are not | Deg. | Write | |
| AV | 4 | bnSetpoint2TempTrig | Setpoint that when the ambient temperature falls below, will switch the control | Deg. | Write | |
| AV | 5 | bnTempRegulationBand | Temperature band between the minimum and maximum fan speed for P fan | Deg. | Write | |
| AV | 6 | bnSetpoint2TempTrigDiff | Temperature differential added to the ambient temperature setpoint 2 trigger | Deg. | Write | |
| AV | 7 | bnPrecoolMinTemp | Minimum ambient temperature at which the precooling system may operate | Deg. | Write | |
| AV | 8 | bnPrecoolMinTempDiff | Ambient temperature offset added to the minimum allowable temperature | Deg. | Write | |
| AV | 9 | bnProportionalGain | Proportional gain constant used for the PID controller | Units | Write | |
| AV | 10 | bnSwitchTemp1 | Minimum temperature, above which the precooling stage 1 has permission to operate | Deg. | Read | |
| AV | 11 | bnSwitchTemp2 | Minimum temperature, above which the precooling stage 2 has permission to operate | Deg. | Read | |
| AV | 12 | bnSwitchTemp3 | Minimum temperature, above which the precooling stage 3 has permission to operate | Deg. | Read | |
| AV | 13 | bnSwitchTemp4 | Minimum temperature, above which the precooling stage 4 has permission to operate | Deg. | Read | |
| AV | 14 | bnFlushFanSpeed | Desired fan speed while performing a flushing cycle | % | Write | |
| AV | 15 | bnSetpoint2Temp | Alternate process temperature set point | Deg. | Write | |
| AVmin | 16 | bnUnitState | Current state of the EVAPCO Controller | Read | 1=Unit on and operational, 2=Unit is off by an alarm, 4=Unit is off via BMS, Modbus/ BACnet, 6=Unit is off via the digital input, 7=Unit is switched off locally, 8=Manual mode enabled for fan speed control | |
| AV | 17 | bnMinFanSpeed | Minimum allowable fan speed | % | Write | |
| AV | 18 | bnMaxFanSpeed | Maximum allowable fan speed | % | Write | |
| AV | 19 | bnEnergySaveFanSpeed | Fan speed, above which the precooling system will activate | % | Write | |
| AV | 20 | bnQuietMaxFanSpeed | Maximum allowable fan speed in quiet operation | % | Write | |
| AV | 21 | bnPID_Integral | PID integral term | Sec. | Write | |
| AV | 22 | bnPID_Derivative | PID derivative term | Sec. | Write | |
| AV | 23 | bnNumWetStages | Count of stages that have been enabled for the adiabatic system | Units | Read | |
| AV | 24 | bnPrecoolStage1_Increase | Count of seconds that must pass with the process temperature above set | Sec. | Write | |
| AV | 25 | bnPrecoolStage1_Decrease | Count of seconds that must pass with the process temperature below set | Sec. | Write | |
| AV | 26 | bnRefrigerant | For condenser applications | Write | 1=R22, 2=R134a, 3=R404A, 4=R407C, 5=R410A, 6=R407A, 7=R407F, 8=R290, 9=R507A, 10=R717 (NH3), 11=R723, 12=R1234ze, 13=R744 (CO2), 14=R448A, 15=R427A, 16=R450A (N13), 17=R513A, 18=R449A, 19=R1234yf, 20=R454B, 21=R454C, 22=R455A, 23=434A, 24=R422A, 25=R32, 26=R452B, 27=R452A, 28=Custom | |
| AV | 27 | bnPrecoolStage1_MinOn | Minimum amount of time the precooling stage remains active | Sec. | Write | |
| AV | 28 | bnPrecoolStage2_MinOn | Minimum amount of time the precooling stage remains active | Sec. | Write | |
| AV | 29 | bnPrecoolStage3_MinOn | Minimum amount of time the precooling stage remains active | Sec. | Write | |
| AV | 30 | bnPrecoolStage4_MinOn | Minimum amount of time the precooling stage remains active | Sec. | Write | |
| AV | 31 | bnFailFanSpeed | Percentage of fan speed the fans will operate | % | Write | |
| AV | 32 | bnInletPressure | Inlet pressure reading via pressure sensor input | Press. | Read | |
| AVmin | 33 | bnRefFanSpeed | Desired fan speed determined by the controller | % | Read | |
| AV | 34 | bnFlushingTime | Count of minutes to perform the flushing routine once initiated | Min. | Write | |
| AV | 35 | bnFlushTimeAcc | Count of seconds the flushing routine has been active | Sec. | Read | |
| AV | 36 | bnDryingTime | Count of minutes to dry the pre-cooling pads | Min. | Write | |
| AV | 37 | bnDryTimeAcc | Count of seconds the drying routine has been active | Sec. | Read | |
| AV | 38 | bnFan_Hours | Count of hours the fans have been operational | Hours | Read | |
| AV | 39 | bnPrecoolStage1_Hours | Count of hours the first valve has been operational | Hours | Read | |
| AV | 40 | bnPrecoolStage2_Hours | Count of hours the second valve has been operational | Hours | Read | |
| AV | 41 | bnPrecoolStage3_Hours | Count of hours the third valve has been operational | Hours | Read | |
| AV | 42 | bnPrecoolStage4_Hours | Count of hours the fourth valve has been operational | Hours | Read | |
| AV | 43 | bnPrecool24_Increase | Count of seconds that must pass with the process temperature above setpoint | Sec. | Write | |
| AV | 44 | bnPrecool24_Decrease | Count of seconds that must pass with the process temperature below setpoint | Sec. | Write | |
| AV | 45 | bnPrecool24_DecreaseAcc | Count of seconds with the process temperature below setpoint | Sec. | Read | |
| AV | 46 | bnPrecool1_DecreaseAcc | Count of seconds with the process temperature below setpoint | Sec. | Read | |
| AV | 47 | bnPrecool24_IncreaseAcc | Count of seconds with the process temperature above the setpoint | Sec. | Read | |
| AV | 48 | bnPrecool1_IncreaseAcc | Count of seconds with the process temperature above the setpoint | Sec. | Read | |
| AV | 49 | bnWarnBits_EBM_01 | Warning bits, ebm fan 01 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 50 | bnWarnBits_EBM_01 | Warning bits, ebm fan 02 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 51 | bnWarnBits_EBM_01 | Warning bits, ebm fan 03 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 52 | bnWarnBits_EBM_01 | Warning bits, ebm fan 04 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 53 | bnWarnBits_EBM_01 | Warning bits, ebm fan 05 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 54 | bnWarnBits_EBM_01 | Warning bits, ebm fan 06 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 55 | bnWarnBits_EBM_01 | Warning bits, ebm fan 07 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 56 | bnWarnBits_EBM_01 | Warning bits, ebm fan 08 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 57 | bnWarnBits_EBM_01 | Warning bits, ebm fan 09 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 58 | bnWarnBits_EBM_01 | Warning bits, ebm fan 10 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 59 | bnWarnBits_EBM_01 | Warning bits, ebm fan 11 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 60 | bnWarnBits_EBM_01 | Warning bits, ebm fan 12 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 61 | bnWarnBits_EBM_01 | Warning bits, ebm fan 13 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 62 | bnWarnBits_EBM_01 | Warning bits, ebm fan 14 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 63 | bnWarnBits_EBM_01 | Warning bits, ebm fan 15 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 64 | bnWarnBits_EBM_01 | Warning bits, ebm fan 16 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 65 | bnWarnBits_EBM_01 | Warning bits, ebm fan 17 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 66 | bnWarnBits_EBM_01 | Warning bits, ebm fan 18 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 67 | bnWarnBits_EBM_01 | Warning bits, ebm fan 19 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 68 | bnWarnBits_EBM_01 | Warning bits, ebm fan 20 (name as printed) | Read | 0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active | |
| AV | 69 | bnAlarmBits_EBM_01 | Alarm bits ebm fan 01 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 70 | bnAlarmBits_EBM_02 | Alarm bits ebm fan 02 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 71 | bnAlarmBits_EBM_03 | Alarm bits ebm fan 03 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 72 | bnAlarmBits_EBM_04 | Alarm bits ebm fan 04 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 73 | bnAlarmBits_EBM_05 | Alarm bits ebm fan 05 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 74 | bnAlarmBits_EBM_06 | Alarm bits ebm fan 06 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 75 | bnAlarmBits_EBM_07 | Alarm bits ebm fan 07 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 76 | bnAlarmBits_EBM_08 | Alarm bits ebm fan 08 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 77 | bnAlarmBits_EBM_09 | Alarm bits ebm fan 09 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 78 | bnAlarmBits_EBM_10 | Alarm bits ebm fan 10 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 79 | bnAlarmBits_EBM_11 | Alarm bits ebm fan 11 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 80 | bnAlarmBits_EBM_12 | Alarm bits ebm fan 12 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 81 | bnAlarmBits_EBM_13 | Alarm bits ebm fan 13 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 82 | bnAlarmBits_EBM_14 | Alarm bits ebm fan 14 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 83 | bnAlarmBits_EBM_15 | Alarm bits ebm fan 15 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 84 | bnAlarmBits_EBM_16 | Alarm bits ebm fan 16 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 85 | bnAlarmBits_EBM_17 | Alarm bits ebm fan 17 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 86 | bnAlarmBits_EBM_18 | Alarm bits ebm fan 18 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 87 | bnAlarmBits_EBM_19 | Alarm bits ebm fan 19 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 88 | bnAlarmBits_EBM_20 | Alarm bits ebm fan 20 | Read | 0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm | |
| AV | 89 | bnStatusBits_EF_01 | Status bits eflow fan 01 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 90 | bnStatusBits_EF_02 | Status bits eflow fan 02 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 91 | bnStatusBits_EF_03 | Status bits eflow fan 03 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 92 | bnStatusBits_EF_04 | Status bits eflow fan 04 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 93 | bnStatusBits_EF_05 | Status bits eflow fan 05 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 94 | bnStatusBits_EF_06 | Status bits eflow fan 06 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 95 | bnStatusBits_EF_07 | Status bits eflow fan 07 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 96 | bnStatusBits_EF_08 | Status bits eflow fan 08 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 97 | bnStatusBits_EF_09 | Status bits eflow fan 09 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 98 | bnStatusBits_EF_10 | Status bits eflow fan 10 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 99 | bnStatusBits_EF_11 | Status bits eflow fan 11 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 100 | bnStatusBits_EF_12 | Status bits eflow fan 12 | Read | 1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch | |
| AV | 101 | bnRemoteSource | Source of the reference fan speed: | Write | 1=Analog Input, 2=Communication see ANALOG_VAL- UE:105 | |
| AV | 102 | bnRemoteAmbTrig | When the source is set to Analog Input | Deg. | Write | |
| AV | 103 | bnRemoteHighFanSpeed | Fan(s) will operate at the high default fan speed with a loss | % | Write | |
| AV | 104 | bnRemoteLowFanSpeed | Fan(s) will operate at the low default fan speed with a loss | % | Write | |
| AV | 105 | bnRemoteFanSpeed | With remote fan speed enabled and the source set to Communications | % | Write | |
| AV | 106 | bnFanSpeedAI | Fan speed ai | % | Read |
No points match these filters.
Integration notes
- Per-fan objects (EC fan alarm and communication status, speed feedback) only matter for the number of fans fitted.
- BV 13-76 and AV 49-100 are EC-fan objects; AC/NEMA-motor units use a separate edition of the guide.
- Units column 'Deg.' follows the unit's configured temperature scale.
- The guide prints the same object name (bnWarnBits_EBM_01) for all twenty AV 49-68 (fans 1-20); names are kept as printed, so check the live object names.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eco-Air Controller (EC Fan Motors) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the EVAPCO eco-Air Controller (EC Fan Motors)
How many BACnet points does the EVAPCO eco-Air Controller (EC Fan Motors) have?
This list has 185 BACnet objects: 107 analog values, 78 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which EVAPCO eco-Air Controller (EC Fan Motors) BACnet points are writable?
39 of the 185 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official EVAPCO eco-Air Controller (EC Fan Motors) BACnet documentation?
The source is EVAPCO Controller User's Manual Addendum - Communications Guide EC Motor Edition (COMM24 EC-E), revision 2025-10, published free by EVAPCO at https://www.evapco.eu/media/772759.
What are the minimum BACnet points to integrate the EVAPCO eco-Air Controller (EC Fan Motors)?
Start with BV 0 bnEnableUnit (BMS enable/disable when configured for BMS enable); AV 3 bnSetpointTemp (Primary process setpoint (writable)); AV 16 bnUnitState (Operating state and reason it is off); AV 0 bnOutletTemp (Process fluid outlet temperature); AV 2 bnActiveSetpoint (Setpoint currently in control); AV 33 bnRefFanSpeed (Commanded fan speed); BV 10 bnCommonAlarmStatus (Common alarm output status).
How do I enable BMS control of the EVAPCO eco-Air Controller (EC Fan Motors)?
Write BV 0 bnEnableUnit = 1; it only takes effect when the unit is configured to be enabled via BMS. AV 16 reports 4 when the unit is off via BMS.
Can the BMS supply sensor values to the EVAPCO eco-Air Controller (EC Fan Motors)?
Fan speed can be driven remotely: set BV 77 bnRemoteEnable = 1, AV 101 bnRemoteSource = 2 (Communication) and write AV 105 bnRemoteFanSpeed. AV 103/AV 104 are fallback high/low speeds used when the analog speed input is lost, chosen by ambient against AV 102.
How do I check these points on the real eco-Air Controller (EC Fan Motors)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More EVAPCO BACnet points lists
- Dry / adiabatic fluid cooler controller
EVAPCO eco-Air Controller (AC / NEMA Motors)
EVAPCO eco-Air air-cooled and adiabatic fluid coolers and condensers with AC (NEMA-style) fan motors on VFDs.
Also known as: eco-Air PLC, EVAPCO Controller, COMM24 AC, COMM22NEMA, eco-Air NEMA motor - Dry / adiabatic fluid cooler controller
EVAPCO eco-Air Controller, pCO version (EC Fans, 2020)
Earlier EVAPCO eco-Air air-cooled and adiabatic fluid coolers and condensers with EC fans and the pCO-type controller.
Also known as: COMM20EC, eco-Air pCO, pcoWeb, pCONet, EVAPCO EC Fan Communications Guide
Source: EVAPCO Controller User's Manual Addendum - Communications Guide EC Motor Edition · COMM24 EC-E · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.