Dry / adiabatic fluid cooler controller · BACnet points list

EVAPCO eco-Air Controller (EC Fan Motors) BACnet points list

Updated 28 October 2026

Short answer

The eco-Air PLC panel exposes BACnet IP on its Ethernet port and BACnet MS/TP on a shared RS-485 terminal that can run either MS/TP or Modbus RTU, chosen on the HMI. Objects are plain Binary and Analog Values numbered from 0, covering unit enable and state, process and ambient temperature, setpoints, fan-speed limits, adiabatic pre-cooling stages and per-fan EC motor alarms, speeds and communication status.

This page lists 185 BACnet objects for the EVAPCO eco-Air Controller (EC Fan Motors) — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EVAPCO’s own free documentation, linked below.

Manufacturer
EVAPCO
Model
eco-Air Controller (EC Fan Motors)
Equipment
Dry / adiabatic fluid cooler controller
Equipment type
Cooling towers & fluid coolers
BACnet objects
185 (39 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
eco-Air PLC, EVAPCO Controller, COMM24 EC, eco-Air EC, eco-Air adiabatic cooler controller
Source document
EVAPCO Controller User's Manual Addendum - Communications Guide EC Motor Edition · COMM24 EC-E · rev. 2025-10
Download CSV 185 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: EVAPCO eco-Air Controller (EC Fan Motors)

Integration in brief

Pick MS/TP or Modbus RTU for the serial port on the HMI (BACnet IP is always live on Ethernet), set the addresses under Service > BMS & Network, then enable the unit through BV 0 if it is configured for BMS enable. Monitor AV 16 unit state, AV 0 outlet temperature and the common alarm, and write AV 3 for the process setpoint. For BMS fan-speed control enable BV 77, set AV 101 to Communication and write AV 105.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0bnEnableUnitBMS enable/disable when configured for BMS enableWrite
AV 3bnSetpointTempPrimary process setpoint (writable)Write
AV 16bnUnitStateOperating state and reason it is offRead
AV 0bnOutletTempProcess fluid outlet temperatureRead
AV 2bnActiveSetpointSetpoint currently in controlRead
AV 33bnRefFanSpeedCommanded fan speedRead
BV 10bnCommonAlarmStatusCommon alarm output statusRead

Enable & remote start

Write BV 0 bnEnableUnit = 1; it only takes effect when the unit is configured to be enabled via BMS. AV 16 reports 4 when the unit is off via BMS.

Sensors & values from the BMS

Fan speed can be driven remotely: set BV 77 bnRemoteEnable = 1, AV 101 bnRemoteSource = 2 (Communication) and write AV 105 bnRemoteFanSpeed. AV 103/AV 104 are fallback high/low speeds used when the analog speed input is lost, chosen by ambient against AV 102.

Network setup

Watch out for

EVAPCO eco-Air Controller (EC Fan Motors) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

185 of 185 shown
Type
AnalogBinary
Access
Show
EVAPCO eco-Air Controller (EC Fan Motors) BACnet Points List
DescriptionStates
BVmin0bnEnableUnitEnables the unit if it is configured to be enabled via BMSWrite0=Unit not enabled, 1=Unit enabled
BV1bnRemoteDigitalState of remote digital inputRead0=No voltage present, 1=Voltage present
BV2bnProcessAlarmFault for either the outlet temperature sensor or the inlet pressureRead0=Normal, 1=Process sensor is not detected
BV3bnValveStatus1State of first adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV4bnValveStatus2State of second adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV5bnValveStatus3State of third adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV6bnValveStatus4State of fourth adiabatic precooling valveRead0=Valve off (water not flowing), 1=Valve on (water flowing)
BV7bnManualFlushManually starts the precooling flushing cycleWrite0=Not active, 1=Start manual flush
BV8bnReleasePrecoolRelease precoolWrite0=Precooling system will not function, 1=Precooling system will function when needed
BV9bnEnableCommonAlarmEnables the common alarm for the digital outputWrite0=Common alarm not enabled, 1=Common alarm enabled
BVmin10bnCommonAlarmStatusStatus of the alarm digital outputRead0=No alarm/not active, 1=Alarm/active
BV11bnForceFullSpeedForce full speedWrite0=Not enabled, 1=Forces fans to run at 100 percent fan speed
BV12bnEnableStageOntimeEnable stage ontimeWrite0=Not active, 1=Valve must remain on for the minimum run time
BV13bnAlarmPresent_EBM_01Alarm present ebm fan 01Read0=Normal, 1=Alarm present
BV14bnAlarmPresent_EBM_02Alarm present ebm fan 02Read0=Normal, 1=Alarm present
BV15bnAlarmPresent_EBM_03Alarm present ebm fan 03Read0=Normal, 1=Alarm present
BV16bnAlarmPresent_EBM_04Alarm present ebm fan 04Read0=Normal, 1=Alarm present
BV17bnAlarmPresent_EBM_05Alarm present ebm fan 05Read0=Normal, 1=Alarm present
BV18bnAlarmPresent_EBM_06Alarm present ebm fan 06Read0=Normal, 1=Alarm present
BV19bnAlarmPresent_EBM_07Alarm present ebm fan 07Read0=Normal, 1=Alarm present
BV20bnAlarmPresent_EBM_08Alarm present ebm fan 08Read0=Normal, 1=Alarm present
BV21bnAlarmPresent_EBM_09Alarm present ebm fan 09Read0=Normal, 1=Alarm present
BV22bnAlarmPresent_EBM_10Alarm present ebm fan 10Read0=Normal, 1=Alarm present
BV23bnAlarmPresent_EBM_11Alarm present ebm fan 11Read0=Normal, 1=Alarm present
BV24bnAlarmPresent_EBM_12Alarm present ebm fan 12Read0=Normal, 1=Alarm present
BV25bnAlarmPresent_EBM_13Alarm present ebm fan 13Read0=Normal, 1=Alarm present
BV26bnAlarmPresent_EBM_14Alarm present ebm fan 14Read0=Normal, 1=Alarm present
BV27bnAlarmPresent_EBM_15Alarm present ebm fan 15Read0=Normal, 1=Alarm present
BV28bnAlarmPresent_EBM_16Alarm present ebm fan 16Read0=Normal, 1=Alarm present
BV29bnAlarmPresent_EBM_17Alarm present ebm fan 17Read0=Normal, 1=Alarm present
BV30bnAlarmPresent_EBM_18Alarm present ebm fan 18Read0=Normal, 1=Alarm present
BV31bnAlarmPresent_EBM_19Alarm present ebm fan 19Read0=Normal, 1=Alarm present
BV32bnAlarmPresent_EBM_20Alarm present ebm fan 20Read0=Normal, 1=Alarm present
BV33bnOnline_EBM_01This is the communication link between the Evapco controller and the fanRead0=Fan not online, 1=Fan is online
BV34bnOnline_EBM_02Online ebm fan 02Read0=Fan not online, 1=Fan is online
BV35bnOnline_EBM_03Online ebm fan 03Read0=Fan not online, 1=Fan is online
BV36bnOnline_EBM_04Online ebm fan 04Read0=Fan not online, 1=Fan is online
BV37bnOnline_EBM_05Online ebm fan 05Read0=Fan not online, 1=Fan is online
BV38bnOnline_EBM_06Online ebm fan 06Read0=Fan not online, 1=Fan is online
BV39bnOnline_EBM_07Online ebm fan 07Read0=Fan not online, 1=Fan is online
BV40bnOnline_EBM_08Online ebm fan 08Read0=Fan not online, 1=Fan is online
BV41bnOnline_EBM_09Online ebm fan 09Read0=Fan not online, 1=Fan is online
BV42bnOnline_EBM_10Online ebm fan 10Read0=Fan not online, 1=Fan is online
BV43bnOnline_EBM_11Online ebm fan 11Read0=Fan not online, 1=Fan is online
BV44bnOnline_EBM_12Online ebm fan 12Read0=Fan not online, 1=Fan is online
BV45bnOnline_EBM_13Online ebm fan 13Read0=Fan not online, 1=Fan is online
BV46bnOnline_EBM_14Online ebm fan 14Read0=Fan not online, 1=Fan is online
BV47bnOnline_EBM_15Online ebm fan 15Read0=Fan not online, 1=Fan is online
BV48bnOnline_EBM_16Online ebm fan 16Read0=Fan not online, 1=Fan is online
BV49bnOnline_EBM_17Online ebm fan 17Read0=Fan not online, 1=Fan is online
BV50bnOnline_EBM_18Online ebm fan 18Read0=Fan not online, 1=Fan is online
BV51bnOnline_EBM_19Online ebm fan 19Read0=Fan not online, 1=Fan is online
BV52bnOnline_EBM_20Online ebm fan 20Read0=Fan not online, 1=Fan is online
BV53bnAlarmPresent_EF_01Alarm present eflow fan 01Read0=Normal, 1=Alarm present
BV54bnAlarmPresent_EF_02Alarm present eflow fan 02Read0=Normal, 1=Alarm present
BV55bnAlarmPresent_EF_03Alarm present eflow fan 03Read0=Normal, 1=Alarm present
BV56bnAlarmPresent_EF_04Alarm present eflow fan 04Read0=Normal, 1=Alarm present
BV57bnAlarmPresent_EF_05Alarm present eflow fan 05Read0=Normal, 1=Alarm present
BV58bnAlarmPresent_EF_06Alarm present eflow fan 06Read0=Normal, 1=Alarm present
BV59bnAlarmPresent_EF_07Alarm present eflow fan 07Read0=Normal, 1=Alarm present
BV60bnAlarmPresent_EF_08Alarm present eflow fan 08Read0=Normal, 1=Alarm present
BV61bnAlarmPresent_EF_09Alarm present eflow fan 09Read0=Normal, 1=Alarm present
BV62bnAlarmPresent_EF_10Alarm present eflow fan 10Read0=Normal, 1=Alarm present
BV63bnAlarmPresent_EF_11Alarm present eflow fan 11Read0=Normal, 1=Alarm present
BV64bnAlarmPresent_EF_12Alarm present eflow fan 12Read0=Normal, 1=Alarm present
BV65bnOnline_EF_01This is the communication link between the Evapco controller and the fanRead0=Fan not online, 1=Fan is online
BV66bnOnline_EF_02Online eflow fan 02Read0=Fan not online, 1=Fan is online
BV67bnOnline_EF_03Online eflow fan 03Read0=Fan not online, 1=Fan is online
BV68bnOnline_EF_04Online eflow fan 04Read0=Fan not online, 1=Fan is online
BV69bnOnline_EF_05Online eflow fan 05Read0=Fan not online, 1=Fan is online
BV70bnOnline_EF_06Online eflow fan 06Read0=Fan not online, 1=Fan is online
BV71bnOnline_EF_07Online eflow fan 07Read0=Fan not online, 1=Fan is online
BV72bnOnline_EF_08Online eflow fan 08Read0=Fan not online, 1=Fan is online
BV73bnOnline_EF_09Online eflow fan 09Read0=Fan not online, 1=Fan is online
BV74bnOnline_EF_10Online eflow fan 10Read0=Fan not online, 1=Fan is online
BV75bnOnline_EF_11Online eflow fan 11Read0=Fan not online, 1=Fan is online
BV76bnOnline_EF_12Online eflow fan 12Read0=Fan not online, 1=Fan is online
BV77bnRemoteEnableRemote enableWrite0=Not enabled, 1=Fan speed is controlled either by analog input or communication.
AVmin0bnOutletTempOutlet temperature of the process fluidDeg.Read
AV1bnAmbientTempTemperature detected by the ambient temperature sensorDeg.Read
AVmin2bnActiveSetpointActive set point that the eco-Air unit will maintainDeg.Read
AVmin3bnSetpointTempPrimary process temperature setpoint used when all other alternate setpoints are notDeg.Write
AV4bnSetpoint2TempTrigSetpoint that when the ambient temperature falls below, will switch the controlDeg.Write
AV5bnTempRegulationBandTemperature band between the minimum and maximum fan speed for P fanDeg.Write
AV6bnSetpoint2TempTrigDiffTemperature differential added to the ambient temperature setpoint 2 triggerDeg.Write
AV7bnPrecoolMinTempMinimum ambient temperature at which the precooling system may operateDeg.Write
AV8bnPrecoolMinTempDiffAmbient temperature offset added to the minimum allowable temperatureDeg.Write
AV9bnProportionalGainProportional gain constant used for the PID controllerUnitsWrite
AV10bnSwitchTemp1Minimum temperature, above which the precooling stage 1 has permission to operateDeg.Read
AV11bnSwitchTemp2Minimum temperature, above which the precooling stage 2 has permission to operateDeg.Read
AV12bnSwitchTemp3Minimum temperature, above which the precooling stage 3 has permission to operateDeg.Read
AV13bnSwitchTemp4Minimum temperature, above which the precooling stage 4 has permission to operateDeg.Read
AV14bnFlushFanSpeedDesired fan speed while performing a flushing cycle%Write
AV15bnSetpoint2TempAlternate process temperature set pointDeg.Write
AVmin16bnUnitStateCurrent state of the EVAPCO ControllerRead1=Unit on and operational, 2=Unit is off by an alarm, 4=Unit is off via BMS, Modbus/ BACnet, 6=Unit is off via the digital input, 7=Unit is switched off locally, 8=Manual mode enabled for fan speed control
AV17bnMinFanSpeedMinimum allowable fan speed%Write
AV18bnMaxFanSpeedMaximum allowable fan speed%Write
AV19bnEnergySaveFanSpeedFan speed, above which the precooling system will activate%Write
AV20bnQuietMaxFanSpeedMaximum allowable fan speed in quiet operation%Write
AV21bnPID_IntegralPID integral termSec.Write
AV22bnPID_DerivativePID derivative termSec.Write
AV23bnNumWetStagesCount of stages that have been enabled for the adiabatic systemUnitsRead
AV24bnPrecoolStage1_IncreaseCount of seconds that must pass with the process temperature above setSec.Write
AV25bnPrecoolStage1_DecreaseCount of seconds that must pass with the process temperature below setSec.Write
AV26bnRefrigerantFor condenser applicationsWrite1=R22, 2=R134a, 3=R404A, 4=R407C, 5=R410A, 6=R407A, 7=R407F, 8=R290, 9=R507A, 10=R717 (NH3), 11=R723, 12=R1234ze, 13=R744 (CO2), 14=R448A, 15=R427A, 16=R450A (N13), 17=R513A, 18=R449A, 19=R1234yf, 20=R454B, 21=R454C, 22=R455A, 23=434A, 24=R422A, 25=R32, 26=R452B, 27=R452A, 28=Custom
AV27bnPrecoolStage1_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV28bnPrecoolStage2_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV29bnPrecoolStage3_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV30bnPrecoolStage4_MinOnMinimum amount of time the precooling stage remains activeSec.Write
AV31bnFailFanSpeedPercentage of fan speed the fans will operate%Write
AV32bnInletPressureInlet pressure reading via pressure sensor inputPress.Read
AVmin33bnRefFanSpeedDesired fan speed determined by the controller%Read
AV34bnFlushingTimeCount of minutes to perform the flushing routine once initiatedMin.Write
AV35bnFlushTimeAccCount of seconds the flushing routine has been activeSec.Read
AV36bnDryingTimeCount of minutes to dry the pre-cooling padsMin.Write
AV37bnDryTimeAccCount of seconds the drying routine has been activeSec.Read
AV38bnFan_HoursCount of hours the fans have been operationalHoursRead
AV39bnPrecoolStage1_HoursCount of hours the first valve has been operationalHoursRead
AV40bnPrecoolStage2_HoursCount of hours the second valve has been operationalHoursRead
AV41bnPrecoolStage3_HoursCount of hours the third valve has been operationalHoursRead
AV42bnPrecoolStage4_HoursCount of hours the fourth valve has been operationalHoursRead
AV43bnPrecool24_IncreaseCount of seconds that must pass with the process temperature above setpointSec.Write
AV44bnPrecool24_DecreaseCount of seconds that must pass with the process temperature below setpointSec.Write
AV45bnPrecool24_DecreaseAccCount of seconds with the process temperature below setpointSec.Read
AV46bnPrecool1_DecreaseAccCount of seconds with the process temperature below setpointSec.Read
AV47bnPrecool24_IncreaseAccCount of seconds with the process temperature above the setpointSec.Read
AV48bnPrecool1_IncreaseAccCount of seconds with the process temperature above the setpointSec.Read
AV49bnWarnBits_EBM_01Warning bits, ebm fan 01 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV50bnWarnBits_EBM_01Warning bits, ebm fan 02 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV51bnWarnBits_EBM_01Warning bits, ebm fan 03 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV52bnWarnBits_EBM_01Warning bits, ebm fan 04 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV53bnWarnBits_EBM_01Warning bits, ebm fan 05 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV54bnWarnBits_EBM_01Warning bits, ebm fan 06 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV55bnWarnBits_EBM_01Warning bits, ebm fan 07 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV56bnWarnBits_EBM_01Warning bits, ebm fan 08 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV57bnWarnBits_EBM_01Warning bits, ebm fan 09 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV58bnWarnBits_EBM_01Warning bits, ebm fan 10 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV59bnWarnBits_EBM_01Warning bits, ebm fan 11 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV60bnWarnBits_EBM_01Warning bits, ebm fan 12 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV61bnWarnBits_EBM_01Warning bits, ebm fan 13 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV62bnWarnBits_EBM_01Warning bits, ebm fan 14 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV63bnWarnBits_EBM_01Warning bits, ebm fan 15 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV64bnWarnBits_EBM_01Warning bits, ebm fan 16 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV65bnWarnBits_EBM_01Warning bits, ebm fan 17 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV66bnWarnBits_EBM_01Warning bits, ebm fan 18 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV67bnWarnBits_EBM_01Warning bits, ebm fan 19 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV68bnWarnBits_EBM_01Warning bits, ebm fan 20 (name as printed)Read0=Current Limitation Engaged, 1=Line Impedance High Warning, 2=Power Limitation Engaged, 3=Output Stage Temperature High Warning, 4=Motor Temperature High Warning, 5=Electronics Temperature High Warning, 6=DC-Link Voltage Low Warning, 7=Brake Operation, 9=Speed Under Limit, 10=Cable Break Warning, 12=DC-Link Voltage High Warning, 14=Line Voltage High Warning, 15=Shedding Active
AV69bnAlarmBits_EBM_01Alarm bits ebm fan 01Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV70bnAlarmBits_EBM_02Alarm bits ebm fan 02Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV71bnAlarmBits_EBM_03Alarm bits ebm fan 03Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV72bnAlarmBits_EBM_04Alarm bits ebm fan 04Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV73bnAlarmBits_EBM_05Alarm bits ebm fan 05Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV74bnAlarmBits_EBM_06Alarm bits ebm fan 06Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV75bnAlarmBits_EBM_07Alarm bits ebm fan 07Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV76bnAlarmBits_EBM_08Alarm bits ebm fan 08Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV77bnAlarmBits_EBM_09Alarm bits ebm fan 09Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV78bnAlarmBits_EBM_10Alarm bits ebm fan 10Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV79bnAlarmBits_EBM_11Alarm bits ebm fan 11Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV80bnAlarmBits_EBM_12Alarm bits ebm fan 12Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV81bnAlarmBits_EBM_13Alarm bits ebm fan 13Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV82bnAlarmBits_EBM_14Alarm bits ebm fan 14Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV83bnAlarmBits_EBM_15Alarm bits ebm fan 15Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV84bnAlarmBits_EBM_16Alarm bits ebm fan 16Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV85bnAlarmBits_EBM_17Alarm bits ebm fan 17Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV86bnAlarmBits_EBM_18Alarm bits ebm fan 18Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV87bnAlarmBits_EBM_19Alarm bits ebm fan 19Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV88bnAlarmBits_EBM_20Alarm bits ebm fan 20Read0=Phase Failure Alarm, 2=Output Stage Overheating Alarm, 3=Internal Communication Alarm, 5=Motor Overheating Alarm, 6=Hall Sensor Error, 7=Motor Blocked, 8=Speed Limit Exceeded, 10=Rotor Position Sensor Calibration Error, 12=DC-Link Undervoltage Alarm
AV89bnStatusBits_EF_01Status bits eflow fan 01Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV90bnStatusBits_EF_02Status bits eflow fan 02Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV91bnStatusBits_EF_03Status bits eflow fan 03Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV92bnStatusBits_EF_04Status bits eflow fan 04Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV93bnStatusBits_EF_05Status bits eflow fan 05Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV94bnStatusBits_EF_06Status bits eflow fan 06Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV95bnStatusBits_EF_07Status bits eflow fan 07Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV96bnStatusBits_EF_08Status bits eflow fan 08Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV97bnStatusBits_EF_09Status bits eflow fan 09Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV98bnStatusBits_EF_10Status bits eflow fan 10Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV99bnStatusBits_EF_11Status bits eflow fan 11Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV100bnStatusBits_EF_12Status bits eflow fan 12Read1=Low Line Voltage Alarm, 2=High Line Voltage Alarm, 3=High Current Motor Short Alarm, 4=High Temperature Warning, 5=Input Phase Error, 6=Rotor Blocked Alarm, 7=Current Limit Warning, 8=Voltage Limit Warning, 9=Rotor Direction Alarm, 10=EEPROM Error, 11=Internal Stop Alarm, 12=Earth Fault Alarm, 13=Brake Chopper Fault, 14=Motor Phase Error, 15=Internal Communication Error, 16=Voltage Ripple Warning, 20=Motor Controller in Bootloader Alarm, 25=Windmilling Warning, 27=IO Configuration Mismatch
AV101bnRemoteSourceSource of the reference fan speed:Write1=Analog Input, 2=Communication see ANALOG_VAL- UE:105
AV102bnRemoteAmbTrigWhen the source is set to Analog InputDeg.Write
AV103bnRemoteHighFanSpeedFan(s) will operate at the high default fan speed with a loss%Write
AV104bnRemoteLowFanSpeedFan(s) will operate at the low default fan speed with a loss%Write
AV105bnRemoteFanSpeedWith remote fan speed enabled and the source set to Communications%Write
AV106bnFanSpeedAIFan speed ai%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eco-Air Controller (EC Fan Motors) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EVAPCO eco-Air Controller (EC Fan Motors)

How many BACnet points does the EVAPCO eco-Air Controller (EC Fan Motors) have?

This list has 185 BACnet objects: 107 analog values, 78 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EVAPCO eco-Air Controller (EC Fan Motors) BACnet points are writable?

39 of the 185 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EVAPCO eco-Air Controller (EC Fan Motors) BACnet documentation?

The source is EVAPCO Controller User's Manual Addendum - Communications Guide EC Motor Edition (COMM24 EC-E), revision 2025-10, published free by EVAPCO at https://www.evapco.eu/media/772759.

What are the minimum BACnet points to integrate the EVAPCO eco-Air Controller (EC Fan Motors)?

Start with BV 0 bnEnableUnit (BMS enable/disable when configured for BMS enable); AV 3 bnSetpointTemp (Primary process setpoint (writable)); AV 16 bnUnitState (Operating state and reason it is off); AV 0 bnOutletTemp (Process fluid outlet temperature); AV 2 bnActiveSetpoint (Setpoint currently in control); AV 33 bnRefFanSpeed (Commanded fan speed); BV 10 bnCommonAlarmStatus (Common alarm output status).

How do I enable BMS control of the EVAPCO eco-Air Controller (EC Fan Motors)?

Write BV 0 bnEnableUnit = 1; it only takes effect when the unit is configured to be enabled via BMS. AV 16 reports 4 when the unit is off via BMS.

Can the BMS supply sensor values to the EVAPCO eco-Air Controller (EC Fan Motors)?

Fan speed can be driven remotely: set BV 77 bnRemoteEnable = 1, AV 101 bnRemoteSource = 2 (Communication) and write AV 105 bnRemoteFanSpeed. AV 103/AV 104 are fallback high/low speeds used when the analog speed input is lost, chosen by ambient against AV 102.

How do I check these points on the real eco-Air Controller (EC Fan Motors)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EVAPCO BACnet points lists

Source: EVAPCO Controller User's Manual Addendum - Communications Guide EC Motor Edition · COMM24 EC-E · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.