  4. Series AVPT pencil-style air velocity transmitter, BACnet MS/TP

Duct airflow velocity sensor · BACnet points list

Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP BACnet points list

Updated 12 November 2026

Short answer

The AVPT is a pencil-style thermal anemometer probe for duct air velocity, sold with either analog outputs or a BACnet MS/TP output. On BACnet it exposes velocity and air temperature as four Analog Inputs (each in imperial and metric), plus objects to set the MS/TP address, the baud rate and a factory reset.

This page lists 7 BACnet objects for the Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Dwyer’s own free documentation, linked below.

Manufacturer
Dwyer
Model
Series AVPT pencil-style air velocity transmitter, BACnet MS/TP
Equipment
Duct airflow velocity sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
7 (3 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
607000 + MS/TP address (607xxx)
Also known as
AVPT, Series AVPT, AVPT BACnet, DwyerOmega AVPT, AVPT pencil style air velocity transmitter
Source document
Series AVPT Pencil Style Air Velocity Transmitter - Specifications, Installation and Operating Instructions · Bulletin AQ-AVPT-C (FR# 444544-00) · rev. 11/19
Download CSV 7 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Dwyer’s current documentation and the live device before use. Not official Dwyer information. Terms of use.

BMS integration notes: Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP

Integration in brief

Set a unique MS/TP address (PIV 1, then power cycle), let auto-baud lock onto the bus, and read velocity and temperature in the units you need (AI 1-4).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Velocity FPMDuct air velocity, FPMRead
AI 3Temperature FDuct air temperature, °FRead

Network setup

Watch out for

Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

7 of 7 shown
Type
AnalogBinaryMulti-stateOther
Access
Show
Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP BACnet Points List
DescriptionStates
AImin1Velocity FPMAir velocityft/minRead
AI2Velocity MPSAir velocitym/sRead
AImin3Temperature FAir temperature°FRead
AI4Temperature CAir temperature°CRead
PIV1Device AddressMS/TP MAC address, 0-127; reset neededWrite
MV1Serial Baud RateMS/TP baud rate; Auto Baud is defaultWrite1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto Baud
BV1Restore Factory DefaultsWrite active then reset to restore defaultsWrite0=Inactive, 1=Active
Object ID lookup: Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Series AVPT pencil-style air velocity transmitter, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP

How many BACnet points does the Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP have?

This list has 7 BACnet objects: 4 analog inputs, 1 binary value, 1 multi-state value, 1 positive integer value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP BACnet points are writable?

3 of the 7 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP BACnet documentation?

The source is Series AVPT Pencil Style Air Velocity Transmitter - Specifications, Installation and Operating Instructions (Bulletin AQ-AVPT-C (FR# 444544-00)), revision 11/19, published free by Dwyer at https://assets.dwyeromega.com/manuals-do/AVPT_AVPT_BACnet.pdf.

What are the minimum BACnet points to integrate the Dwyer Series AVPT pencil-style air velocity transmitter, BACnet MS/TP?

Start with AI 1 Velocity FPM (Duct air velocity, FPM); AI 3 Temperature F (Duct air temperature, °F).

How do I check these points on the real Series AVPT pencil-style air velocity transmitter, BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.