Room pressure monitor · BACnet points list

Dwyer Series RSME / RSMC Room Status Monitor BACnet points list

Updated 4 November 2026

Short answer

The RSME/RSMC shows room differential pressure from a built-in sensor and can add two universal inputs (temperature, humidity, pressure or flow), a door/switch input and up to three external BACnet sensors read from other devices. It runs on BACnet MS/TP (or Modbus RTU) and exposes the readings, alarm states, alarm limits, room modes and almost all setup as objects. Up to three rooms can be shown on the display.

This page lists 192 BACnet objects for the Dwyer Series RSME / RSMC Room Status Monitor — 161 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Dwyer’s own free documentation, linked below.

Manufacturer
Dwyer
Model
Series RSME / RSMC Room Status Monitor
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
192 (161 writable)
Transport
BACnet MS/TP
Firmware
1.2 (application software 1.0.10R)
Default device instance
607127
Also known as
RSME, RSMC, Series RSME, Series RSMC, DwyerOmega RSME, Dwyer room pressure monitor
Source document
Series RSME/RSMC BACnet/Modbus Operating Instructions
Download CSV 192 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Dwyer’s current documentation and the live device before use. Not official Dwyer information. Terms of use.

BMS integration notes: Dwyer Series RSME / RSMC Room Status Monitor

Integration in brief

Read the room pressure (AI 1) and its alarm status (MSV 3), plus any universal or external inputs that are in use and their alarm statuses. The BMS can set each room to occupied, unoccupied or cleaning with MSV 36-38, and reset latched alarms with BV 22.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 36Room 1 ModeRoom 1 mode: 1 Occupied, 2 Unoccupied, 3 CleaningWrite
BV 22Reset AlarmsWrite 1 to reset latched alarmsWrite
AI 1PressureRoom differential pressure, inWC by defaultRead
MV 16Binary Input StatusDoor/switch input status (Door Open/Closed)Read
BV 16Relay StatusAlarm relay stateRead
MV 3Pressure Alarm StatusPressure alarm: 1 OK, 2 Warning, 3 AlarmRead

Enable & remote start

BV 1 Pressure Enable turns monitoring of the built-in sensor on; each universal input and external sensor has its own enable BV.

Sensors & values from the BMS

Up to three external BACnet analog sensors (ES1-ES3) and three digital points (ED1-ED3) are read by the monitor itself: set the remote device instance and object instance (PIV 12/13 for ES1 and so on), the object type, then enable the sensor. The remote device must answer a directed Who-Is. Values appear in AV 26/32/38 and MSV 58/62/66.

Network setup

Watch out for

Dwyer Series RSME / RSMC Room Status Monitor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

192 of 192 shown
Type
BinaryMulti-state
Access
Show
Dwyer Series RSME / RSMC Room Status Monitor BACnet Points List
DescriptionStates
AImin1PressureBuilt-in differential pressure sensor readinginWCRead
AI2UI1 ValueUniversal input 1 scaled value°FRead
AI3UI2 ValueUniversal input 2 scaled value°FRead
AV1Pressure High Alarm LimitinWCWrite
AV2Pressure High Alarm WarninginWCWrite
AV3Pressure Low Alarm LimitinWCWrite
AV4Pressure Low Alarm WarninginWCWrite
AV5Pressure Alarm DeadbandinWCWrite
AV6UI1 Max SignalVWrite
AV7UI1 Min SignalVWrite
AV8UI1 Max Scale ValueWrite
AV9UI1 Min Scale ValueWrite
AV10UI1 High Alarm Limit°FWrite
AV11UI1 High Alarm Warning°FWrite
AV12UI1 Low Alarm Limit°FWrite
AV13UI1 Low Alarm Warning°FWrite
AV14UI1 Alarm Deadband°FWrite
AV15UI2 Max SignalmAWrite
AV16UI2 Min SignalmAWrite
AV17UI2 Max Scale ValueWrite
AV18U12 Min Scale ValuePrinted "U12"; UI2 minimum scale valueWrite
AV19UI2 High Alarm Limit°FWrite
AV20UI2 High Alarm Warning°FWrite
AV21UI2 Low Alarm Limit°FWrite
AV22UI2 Low Alarm Warning°FWrite
AV23UI2 Alarm Deadband°FWrite
AV24Duct AreaDuct area for flow from a velocity inputft²Write
AV25Room VolumeRoom volume for air changes per hourft³Write
AV26ES1 ValueExternal BACnet sensor ES1°FRead
AV27ES1 High Alarm LimitExternal BACnet sensor ES1°FWrite
AV28ES1 High Alarm WarningExternal BACnet sensor ES1°FWrite
AV29ES1 Low Alarm LimitExternal BACnet sensor ES1°FWrite
AV30ES1 Low Alarm WarningExternal BACnet sensor ES1°FWrite
AV31ES1 Alarm DeadbandExternal BACnet sensor ES1°FWrite
AV32ES2 ValueExternal BACnet sensor ES2°FRead
AV33ES2 High Alarm LimitExternal BACnet sensor ES2°FWrite
AV34ES2 High Alarm WarningExternal BACnet sensor ES2°FWrite
AV35ES2 Low Alarm LimitExternal BACnet sensor ES2°FWrite
AV36ES2 Low Alarm WarningExternal BACnet sensor ES2°FWrite
AV37ES2 Alarm DeadbandExternal BACnet sensor ES2°FWrite
AV38ES3 ValueExternal BACnet sensor ES3°FRead
AV39ES3 High Alarm LimitExternal BACnet sensor ES3°FWrite
AV40ES3 High Alarm WarningExternal BACnet sensor ES3°FWrite
AV41ES3 Low LimitES3 low alarm limit°FWrite
AV42ES3 Low Alarm WarningExternal BACnet sensor ES3°FWrite
AV43ES3 Alarm DeadbandExternal BACnet sensor ES3°FWrite
BV1Pressure EnableWrite
BV2Pressure High Alarm EnableWrite
BV3Pressure Low Alarm EnableWrite
BV4UI1 EnableWrite
BV5UI1 High Alarm EnableWrite
BV6UI1 Low Alarm EnableWrite
BV7UI2 EnableWrite
BV8UI2 High Alarm EnableWrite
BV9UI2 Low Alarm EnableWrite
BV10Binary Input EnableWrite
BV11Binary Input Alarm EnableDetail page names it Binary Alarm EnableWrite
BV12Digital UI1 EnableWrite
BV13Digital UI1 Alarm EnableWrite
BV14Digital UI2 EnableWrite
BV15Digital UI2 Alarm EnableWrite
BVmin16Relay StatusAlarm relay active per Relay OperationRead
BV17Password Security EnableWrite
BV18Alarm Latch EnableWrite
BV19Alarm Buzzer EnableWrite
BV20Alarm Mute Button EnableWrite
BV21Mute AlarmsWrite 1 to mute the buzzer for the mute timeoutWrite1=Active
BVmin22Reset AlarmsWrite 1 to reset latched alarmsWrite1=Active
BV23ES1 EnableExternal BACnet sensor ES1Write
BV24ES1 High Alarm EnableExternal BACnet sensor ES1Write
BV25ES1 Low Alarm EnableExternal BACnet sensor ES1Write
BV26ES2 EnableExternal BACnet sensor ES2Write
BV27ES2 High Alarm EnableExternal BACnet sensor ES2Write
BV28ES2 Low Alarm EnableExternal BACnet sensor ES2Write
BV29ES3 EnableExternal BACnet sensor ES3Write
BV30ES3 High Alarm EnableExternal BACnet sensor ES3Write
BV31ES3 Low Alarm EnableExternal BACnet sensor ES3Write
BV32ED1 EnableExternal BACnet digital input ED1Write
BV33ED1 Alarm EnableExternal BACnet digital input ED1Write
BV34ED2 EnableExternal BACnet digital input ED2Write
BV35ED2 Alarm EnableExternal BACnet digital input ED2Write
BV36ED3 EnableExternal BACnet digital input ED3Write
BV37ED3 Alarm EnableExternal BACnet digital input ED3Write
MV1Pressure UnitWrite1=Pa, 2=kPa, 3=cmWC, 4=mmWC, 5=inWC
MV2Pressure Display FormatWrite1=0, 2=0.0, 3=0.00, 4=0.000
MVmin3Pressure Alarm StatusAlarm status of the built-in pressure readingRead1=OK, 2=Warning, 3=Alarm
MV4UI1 Signal TypeRead1=Digital, 2=4-20mA, 3=0-5V, 4=0-10V
MV5UI1 Media TypeRead1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow
MV6UI1 UnitRead1=degrees C, 2=degrees F
MV7UI1 Display FormatWrite1=0, 2=0.0, 3=0.00, 4=0.000
MV8UI1 Alarm StatusRead1=OK, 2=Warning, 3=Alarm
MV9UI2 Signal TypeRead1=Digital, 2=4-20mA, 3=0-5V, 4=0-10V
MV10UI2 Media TypeRead1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow
MV11UI2 UnitRead1=degrees C, 2=degrees F
MV12UI2 Display FormatWrite1=0, 2=0.0, 3=0.00, 4=0.000
MV13UI2 Alarm StatusRead1=OK, 2=Warning, 3=Alarm
MV14Binary Input UsageWrite1=Remote Switch, 2=Door Contact
MV15Binary Input PolarityWrite1=Reverse, 2=Direct
MVmin16Binary Input StatusDoor/switch input statusRead1=Door Open, 2=Door Closed
MV17Digital UI1 UsageWrite1=Remote Switch, 2=Door Contact
MV18Digital UI1 PolarityWrite1=Reverse, 2=Direct
MV19Digital UI1 StatusRead1=Door Open, 2=Door Closed
MV20Digital UI2 UsageWrite1=Remote Switch, 2=Door Contact
MV21Digital UI2 PolarityWrite1=Reverse, 2=Direct
MV22Digital UI2 StatusRead1=Door Open, 2=Door Closed
MV23Relay OperationWrite1=Normally Closed, 2=Normally Open
MV24Relay SourceWrite1=Disabled, 2=Master Alarm, 3=Door Alarm, 4=Pressure Alarm, 5=Analog Alarm, 6=Room 1 Alarm, 7=Room 2 Alarm, 8=Room 3 Alarm, 9=Room 1 Door Alarm, 10=Room 2 Door Alarm, 11=Room 3 Door Alarm
MV25Analog Output TypeWrite1=0-10V, 2=4-20mA
MV26Analog Output SourceWrite1=Built-in DP, 2=User I1, 3=User I2
MV27Display ModeWrite1=1 Room 1 Sensor, 2=1 Room 2 Sensors, 3=1 Room 3 Sensors, 4=2 Rooms 2 Sensors, 5=3 Rooms 3 Sensors
MV28Room 1 Sensor 1 Select AnalogWrite1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None
MV29Room 1 Sensor 2 Select AnalogWrite1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None
MV30Room 1 Sensor 3 Select AnalogWrite1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None
MV31Room 2 Sensor 1 Select AnalogWrite1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None
MV32Room 3 Sensor 1 Select AnalogWrite1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None
MV33Room 1 Select DigitalWrite1=None, 2=User I1, 3=User I2, 4=Digital I1, 5=ED1, 6=ED2, 7=ED3
MV34Room 2 Select DigitalWrite1=None, 2=User I1, 3=User I2, 4=Digital I1, 5=ED1, 6=ED2, 7=ED3
MV35Room 3 Select DigitalWrite1=None, 2=User I1, 3=User I2, 4=Digital I1, 5=ED1, 6=ED2, 7=ED3
MVmin36Room 1 ModeRoom 1 operating modeWrite1=Occupied, 2=Unoccupied, 3=Cleaning
MV37Room 2 ModeRoom 2 operating modeWrite1=Occupied, 2=Unoccupied, 3=Cleaning
MV38Room 3 ModeRoom 3 operating modeWrite1=Occupied, 2=Unoccupied, 3=Cleaning
MV39LanguageWrite1=English, 2=Espanol
MV40ES1 Object TypeExternal BACnet sensor ES1Write1=Analog Input, 2=Analog Value
MV41ES1 Media TypeExternal BACnet sensor ES1Read1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow
MV42ES1 UnitExternal BACnet sensor ES1Read1=degrees C, 2=degrees F
MV43ES1 Display FormatExternal BACnet sensor ES1Write1=0, 2=0.0, 3=0.00, 4=0.000
MV44ES1 Alarm StatusExternal BACnet sensor ES1Read1=OK, 2=Warning, 3=Alarm
MV45ES2 Object TypeExternal BACnet sensor ES2Write1=Analog Input, 2=Analog Value
MV46ES2 Media TypeExternal BACnet sensor ES2Read1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow
MV47ES2 UnitExternal BACnet sensor ES2Read1=degrees C, 2=degrees F
MV48ES2 Display FormatExternal BACnet sensor ES2Write1=0, 2=0.0, 3=0.00, 4=0.000
MV49ES2 Alarm StatusExternal BACnet sensor ES2Read1=OK, 2=Warning, 3=Alarm
MV50ES3 Object TypeExternal BACnet sensor ES3Write1=Analog Input, 2=Analog Value
MV51ES3 Media TypeExternal BACnet sensor ES3Read1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow
MV52ES3 UnitExternal BACnet sensor ES3Read1=degrees C, 2=degrees F
MV53ES3 Display FormatExternal BACnet sensor ES3Write1=0, 2=0.0, 3=0.00, 4=0.000
MV54ES3 Alarm StatusExternal BACnet sensor ES3Read1=OK, 2=Warning, 3=Alarm
MV55ED1 Object TypeExternal BACnet digital input ED1Write1=Binary Input, 2=Binary Value
MV56ED1 UsageExternal BACnet digital input ED1Write1=Remote Switch, 2=Door Contact
MV57ED1 PolarityExternal BACnet digital input ED1Write1=Reverse, 2=Direct
MV58ED1 StatusExternal BACnet digital input ED1Read1=Door Open, 2=Door Closed
MV59ED2 Object TypeExternal BACnet digital input ED2Write1=Binary Input, 2=Binary Value
MV60ED2 UsageExternal BACnet digital input ED2Write1=Remote Switch, 2=Door Contact
MV61ED2 PolarityExternal BACnet digital input ED2Write1=Reverse, 2=Direct
MV62ED2 StatusExternal BACnet digital input ED2Read1=Door Open, 2=Door Closed
MV63ED3 Object TypeExternal BACnet digital input ED3Write1=Binary Input, 2=Binary Value
MV64ED3 UsageExternal BACnet digital input ED3Write1=Remote Switch, 2=Door Contact
MV65ED3 PolarityExternal BACnet digital input ED3Write1=Reverse, 2=Direct
MV66ED3 StatusExternal BACnet digital input ED3Read1=Door Open, 2=Door Closed
PIV1Pressure Alarm DelaysWrite
PIV2Pressure Alarm To Normal DelaysWrite
PIV3UI1 Alarm DelaysWrite
PIV4UI1 Alarm To Normal DelaysWrite
PIV5UI2 Alarm DelaysWrite
PIV6UI2 Alarm To Normal DelaysWrite
PIV7Binary Input Alarm DelaysWrite
PIV8Digital UI1 Alarm DelaysWrite
PIV9Digital UI2 Alarm DelaysWrite
PIV10Alarm Buzzer VolumeWrite
PIV11Alarm Mute TimeoutsWrite
PIV12ES1 Device InstanceDevice instance of external BACnet sensorWrite
PIV13ES1 Object InstanceObject instance read on that deviceWrite
PIV14ES1 Alarm DelayExternal BACnet sensor ES1sWrite
PIV15ES1 Alarm To Normal DelayExternal BACnet sensor ES1sWrite
PIV16ES2 Device InstanceExternal BACnet sensor ES2Write
PIV17ES2 Object InstanceExternal BACnet sensor ES2Write
PIV18ES2 Alarm DelayExternal BACnet sensor ES2sWrite
PIV19ES2 Alarm To Normal DelayExternal BACnet sensor ES2sWrite
PIV20ES3 Device InstanceExternal BACnet sensor ES3Write
PIV21ES3 Object InstanceExternal BACnet sensor ES3Write
PIV22ES3 Alarm DelayExternal BACnet sensor ES3sWrite
PIV23ES3 Alarm To Normal DelayExternal BACnet sensor ES3sWrite
PIV24ED1 Device InstanceExternal BACnet digital input ED1Write
PIV25ED1 Object InstanceExternal BACnet digital input ED1Write
PIV26ED1 Alarm DelayExternal BACnet digital input ED1sWrite
PIV27ED2 Device InstanceExternal BACnet digital input ED2Write
PIV28ED2 Object InstanceExternal BACnet digital input ED2Write
PIV29ED2 Alarm DelayExternal BACnet digital input ED2sWrite
PIV30ED3 Device InstanceExternal BACnet digital input ED3Write
PIV31ED3 Object InstanceExternal BACnet digital input ED3Write
PIV32ED3 Alarm DelayExternal BACnet digital input ED3sWrite
CSV1Pressure Display NameWrite
CSV2UI1 Display NameWrite
CSV3UI2 Display NameWrite
CSV4Room 1 NameWrite
CSV5Room 2 NameWrite
CSV6Room 3 NameWrite
CSV7Operator PasswordOperator PINWrite
CSV8Administrator PasswordAdministrator PIN, numericWrite
CSV9ES1 Display NameExternal BACnet sensor ES1Write
CSV10ES2 Display NameExternal BACnet sensor ES2Write
CSV11ED2 Display NameThird external sensor (ES3) display nameWrite
Object ID lookup: Dwyer RSME / RSMC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Series RSME / RSMC Room Status Monitor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Dwyer Series RSME / RSMC Room Status Monitor

How many BACnet points does the Dwyer Series RSME / RSMC Room Status Monitor have?

This list has 192 BACnet objects: 3 analog inputs, 43 analog values, 37 binary values, 66 multi-state values, 11 characterstring values, 32 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Dwyer Series RSME / RSMC Room Status Monitor BACnet points are writable?

161 of the 192 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Dwyer Series RSME / RSMC Room Status Monitor BACnet documentation?

The source is Series RSME/RSMC BACnet/Modbus Operating Instructions, published free by Dwyer at https://assets.dwyeromega.com/manuals-do/RSMC_BACnet_and_Modbus_Operation_Instructions.pdf.

What are the minimum BACnet points to integrate the Dwyer Series RSME / RSMC Room Status Monitor?

Start with MV 36 Room 1 Mode (Room 1 mode: 1 Occupied, 2 Unoccupied, 3 Cleaning); BV 22 Reset Alarms (Write 1 to reset latched alarms); AI 1 Pressure (Room differential pressure, inWC by default); MV 16 Binary Input Status (Door/switch input status (Door Open/Closed)); BV 16 Relay Status (Alarm relay state); MV 3 Pressure Alarm Status (Pressure alarm: 1 OK, 2 Warning, 3 Alarm).

How do I enable BMS control of the Dwyer Series RSME / RSMC Room Status Monitor?

BV 1 Pressure Enable turns monitoring of the built-in sensor on; each universal input and external sensor has its own enable BV.

Can the BMS supply sensor values to the Dwyer Series RSME / RSMC Room Status Monitor?

Up to three external BACnet analog sensors (ES1-ES3) and three digital points (ED1-ED3) are read by the monitor itself: set the remote device instance and object instance (PIV 12/13 for ES1 and so on), the object type, then enable the sensor. The remote device must answer a directed Who-Is. Values appear in AV 26/32/38 and MSV 58/62/66.

How do I check these points on the real Series RSME / RSMC Room Status Monitor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Dwyer BACnet points lists

Source: Series RSME/RSMC BACnet/Modbus Operating Instructions. Object names, instances and units are reproduced as published; descriptions are our own.