Dwyer Series RSME / RSMC Room Status Monitor BACnet points list
Updated 4 November 2026
The RSME/RSMC shows room differential pressure from a built-in sensor and can add two universal inputs (temperature, humidity, pressure or flow), a door/switch input and up to three external BACnet sensors read from other devices. It runs on BACnet MS/TP (or Modbus RTU) and exposes the readings, alarm states, alarm limits, room modes and almost all setup as objects. Up to three rooms can be shown on the display.
This page lists 192 BACnet objects for the Dwyer Series RSME / RSMC Room Status Monitor — 161 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Dwyer’s own free documentation, linked below.
- Manufacturer
- Dwyer
- Model
- Series RSME / RSMC Room Status Monitor
- Equipment
- Room pressure monitor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 192 (161 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.2 (application software 1.0.10R)
- Default device instance
- 607127
- Also known as
- RSME, RSMC, Series RSME, Series RSMC, DwyerOmega RSME, Dwyer room pressure monitor
- Source document
- Series RSME/RSMC BACnet/Modbus Operating Instructions
Reference only, provided as-is: verify against Dwyer’s current documentation and the live device before use. Not official Dwyer information. Terms of use.
BMS integration notes: Dwyer Series RSME / RSMC Room Status Monitor
Read the room pressure (AI 1) and its alarm status (MSV 3), plus any universal or external inputs that are in use and their alarm statuses. The BMS can set each room to occupied, unoccupied or cleaning with MSV 36-38, and reset latched alarms with BV 22.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 36 | Room 1 Mode | Room 1 mode: 1 Occupied, 2 Unoccupied, 3 Cleaning | Write |
| BV 22 | Reset Alarms | Write 1 to reset latched alarms | Write |
| AI 1 | Pressure | Room differential pressure, inWC by default | Read |
| MV 16 | Binary Input Status | Door/switch input status (Door Open/Closed) | Read |
| BV 16 | Relay Status | Alarm relay state | Read |
| MV 3 | Pressure Alarm Status | Pressure alarm: 1 OK, 2 Warning, 3 Alarm | Read |
Enable & remote start
BV 1 Pressure Enable turns monitoring of the built-in sensor on; each universal input and external sensor has its own enable BV.
Sensors & values from the BMS
Up to three external BACnet analog sensors (ES1-ES3) and three digital points (ED1-ED3) are read by the monitor itself: set the remote device instance and object instance (PIV 12/13 for ES1 and so on), the object type, then enable the sensor. The remote device must answer a directed Who-Is. Values appear in AV 26/32/38 and MSV 58/62/66.
Network setup
- BACnet MS/TP or Modbus RTU over 2-wire RS485, chosen in the Network menu (Configuration > Network).
- Optional 120 ohm termination: jumper terminals 9 and 10.
- Default device instance 607127 (vendor ID 607); Max Master default 127.
- DeviceCommunicationControl and ReinitializeDevice need the password given in the manual.
- Time sync from BACnet must be turned on in Maintenance > Date and time.
Watch out for
- No segmentation: the full Object_List cannot be read in one ReadProperty; read it by index.
- Changing MV 1 Pressure Unit changes the units of all pressure limits; COV increments are unit-less and may need adjusting.
- BV 21 Mute and BV 22 Reset act only on writing 1; writing 0 does nothing.
- Most objects are setup values; do not write them cyclically from the BMS.
Dwyer Series RSME / RSMC Room Status Monitor BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Pressure | Built-in differential pressure sensor reading | inWC | Read | |
| AI | 2 | UI1 Value | Universal input 1 scaled value | °F | Read | |
| AI | 3 | UI2 Value | Universal input 2 scaled value | °F | Read | |
| AV | 1 | Pressure High Alarm Limit | inWC | Write | ||
| AV | 2 | Pressure High Alarm Warning | inWC | Write | ||
| AV | 3 | Pressure Low Alarm Limit | inWC | Write | ||
| AV | 4 | Pressure Low Alarm Warning | inWC | Write | ||
| AV | 5 | Pressure Alarm Deadband | inWC | Write | ||
| AV | 6 | UI1 Max Signal | V | Write | ||
| AV | 7 | UI1 Min Signal | V | Write | ||
| AV | 8 | UI1 Max Scale Value | Write | |||
| AV | 9 | UI1 Min Scale Value | Write | |||
| AV | 10 | UI1 High Alarm Limit | °F | Write | ||
| AV | 11 | UI1 High Alarm Warning | °F | Write | ||
| AV | 12 | UI1 Low Alarm Limit | °F | Write | ||
| AV | 13 | UI1 Low Alarm Warning | °F | Write | ||
| AV | 14 | UI1 Alarm Deadband | °F | Write | ||
| AV | 15 | UI2 Max Signal | mA | Write | ||
| AV | 16 | UI2 Min Signal | mA | Write | ||
| AV | 17 | UI2 Max Scale Value | Write | |||
| AV | 18 | U12 Min Scale Value | Printed "U12"; UI2 minimum scale value | Write | ||
| AV | 19 | UI2 High Alarm Limit | °F | Write | ||
| AV | 20 | UI2 High Alarm Warning | °F | Write | ||
| AV | 21 | UI2 Low Alarm Limit | °F | Write | ||
| AV | 22 | UI2 Low Alarm Warning | °F | Write | ||
| AV | 23 | UI2 Alarm Deadband | °F | Write | ||
| AV | 24 | Duct Area | Duct area for flow from a velocity input | ft² | Write | |
| AV | 25 | Room Volume | Room volume for air changes per hour | ft³ | Write | |
| AV | 26 | ES1 Value | External BACnet sensor ES1 | °F | Read | |
| AV | 27 | ES1 High Alarm Limit | External BACnet sensor ES1 | °F | Write | |
| AV | 28 | ES1 High Alarm Warning | External BACnet sensor ES1 | °F | Write | |
| AV | 29 | ES1 Low Alarm Limit | External BACnet sensor ES1 | °F | Write | |
| AV | 30 | ES1 Low Alarm Warning | External BACnet sensor ES1 | °F | Write | |
| AV | 31 | ES1 Alarm Deadband | External BACnet sensor ES1 | °F | Write | |
| AV | 32 | ES2 Value | External BACnet sensor ES2 | °F | Read | |
| AV | 33 | ES2 High Alarm Limit | External BACnet sensor ES2 | °F | Write | |
| AV | 34 | ES2 High Alarm Warning | External BACnet sensor ES2 | °F | Write | |
| AV | 35 | ES2 Low Alarm Limit | External BACnet sensor ES2 | °F | Write | |
| AV | 36 | ES2 Low Alarm Warning | External BACnet sensor ES2 | °F | Write | |
| AV | 37 | ES2 Alarm Deadband | External BACnet sensor ES2 | °F | Write | |
| AV | 38 | ES3 Value | External BACnet sensor ES3 | °F | Read | |
| AV | 39 | ES3 High Alarm Limit | External BACnet sensor ES3 | °F | Write | |
| AV | 40 | ES3 High Alarm Warning | External BACnet sensor ES3 | °F | Write | |
| AV | 41 | ES3 Low Limit | ES3 low alarm limit | °F | Write | |
| AV | 42 | ES3 Low Alarm Warning | External BACnet sensor ES3 | °F | Write | |
| AV | 43 | ES3 Alarm Deadband | External BACnet sensor ES3 | °F | Write | |
| BV | 1 | Pressure Enable | Write | |||
| BV | 2 | Pressure High Alarm Enable | Write | |||
| BV | 3 | Pressure Low Alarm Enable | Write | |||
| BV | 4 | UI1 Enable | Write | |||
| BV | 5 | UI1 High Alarm Enable | Write | |||
| BV | 6 | UI1 Low Alarm Enable | Write | |||
| BV | 7 | UI2 Enable | Write | |||
| BV | 8 | UI2 High Alarm Enable | Write | |||
| BV | 9 | UI2 Low Alarm Enable | Write | |||
| BV | 10 | Binary Input Enable | Write | |||
| BV | 11 | Binary Input Alarm Enable | Detail page names it Binary Alarm Enable | Write | ||
| BV | 12 | Digital UI1 Enable | Write | |||
| BV | 13 | Digital UI1 Alarm Enable | Write | |||
| BV | 14 | Digital UI2 Enable | Write | |||
| BV | 15 | Digital UI2 Alarm Enable | Write | |||
| BVmin | 16 | Relay Status | Alarm relay active per Relay Operation | Read | ||
| BV | 17 | Password Security Enable | Write | |||
| BV | 18 | Alarm Latch Enable | Write | |||
| BV | 19 | Alarm Buzzer Enable | Write | |||
| BV | 20 | Alarm Mute Button Enable | Write | |||
| BV | 21 | Mute Alarms | Write 1 to mute the buzzer for the mute timeout | Write | 1=Active | |
| BVmin | 22 | Reset Alarms | Write 1 to reset latched alarms | Write | 1=Active | |
| BV | 23 | ES1 Enable | External BACnet sensor ES1 | Write | ||
| BV | 24 | ES1 High Alarm Enable | External BACnet sensor ES1 | Write | ||
| BV | 25 | ES1 Low Alarm Enable | External BACnet sensor ES1 | Write | ||
| BV | 26 | ES2 Enable | External BACnet sensor ES2 | Write | ||
| BV | 27 | ES2 High Alarm Enable | External BACnet sensor ES2 | Write | ||
| BV | 28 | ES2 Low Alarm Enable | External BACnet sensor ES2 | Write | ||
| BV | 29 | ES3 Enable | External BACnet sensor ES3 | Write | ||
| BV | 30 | ES3 High Alarm Enable | External BACnet sensor ES3 | Write | ||
| BV | 31 | ES3 Low Alarm Enable | External BACnet sensor ES3 | Write | ||
| BV | 32 | ED1 Enable | External BACnet digital input ED1 | Write | ||
| BV | 33 | ED1 Alarm Enable | External BACnet digital input ED1 | Write | ||
| BV | 34 | ED2 Enable | External BACnet digital input ED2 | Write | ||
| BV | 35 | ED2 Alarm Enable | External BACnet digital input ED2 | Write | ||
| BV | 36 | ED3 Enable | External BACnet digital input ED3 | Write | ||
| BV | 37 | ED3 Alarm Enable | External BACnet digital input ED3 | Write | ||
| MV | 1 | Pressure Unit | Write | 1=Pa, 2=kPa, 3=cmWC, 4=mmWC, 5=inWC | ||
| MV | 2 | Pressure Display Format | Write | 1=0, 2=0.0, 3=0.00, 4=0.000 | ||
| MVmin | 3 | Pressure Alarm Status | Alarm status of the built-in pressure reading | Read | 1=OK, 2=Warning, 3=Alarm | |
| MV | 4 | UI1 Signal Type | Read | 1=Digital, 2=4-20mA, 3=0-5V, 4=0-10V | ||
| MV | 5 | UI1 Media Type | Read | 1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow | ||
| MV | 6 | UI1 Unit | Read | 1=degrees C, 2=degrees F | ||
| MV | 7 | UI1 Display Format | Write | 1=0, 2=0.0, 3=0.00, 4=0.000 | ||
| MV | 8 | UI1 Alarm Status | Read | 1=OK, 2=Warning, 3=Alarm | ||
| MV | 9 | UI2 Signal Type | Read | 1=Digital, 2=4-20mA, 3=0-5V, 4=0-10V | ||
| MV | 10 | UI2 Media Type | Read | 1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow | ||
| MV | 11 | UI2 Unit | Read | 1=degrees C, 2=degrees F | ||
| MV | 12 | UI2 Display Format | Write | 1=0, 2=0.0, 3=0.00, 4=0.000 | ||
| MV | 13 | UI2 Alarm Status | Read | 1=OK, 2=Warning, 3=Alarm | ||
| MV | 14 | Binary Input Usage | Write | 1=Remote Switch, 2=Door Contact | ||
| MV | 15 | Binary Input Polarity | Write | 1=Reverse, 2=Direct | ||
| MVmin | 16 | Binary Input Status | Door/switch input status | Read | 1=Door Open, 2=Door Closed | |
| MV | 17 | Digital UI1 Usage | Write | 1=Remote Switch, 2=Door Contact | ||
| MV | 18 | Digital UI1 Polarity | Write | 1=Reverse, 2=Direct | ||
| MV | 19 | Digital UI1 Status | Read | 1=Door Open, 2=Door Closed | ||
| MV | 20 | Digital UI2 Usage | Write | 1=Remote Switch, 2=Door Contact | ||
| MV | 21 | Digital UI2 Polarity | Write | 1=Reverse, 2=Direct | ||
| MV | 22 | Digital UI2 Status | Read | 1=Door Open, 2=Door Closed | ||
| MV | 23 | Relay Operation | Write | 1=Normally Closed, 2=Normally Open | ||
| MV | 24 | Relay Source | Write | 1=Disabled, 2=Master Alarm, 3=Door Alarm, 4=Pressure Alarm, 5=Analog Alarm, 6=Room 1 Alarm, 7=Room 2 Alarm, 8=Room 3 Alarm, 9=Room 1 Door Alarm, 10=Room 2 Door Alarm, 11=Room 3 Door Alarm | ||
| MV | 25 | Analog Output Type | Write | 1=0-10V, 2=4-20mA | ||
| MV | 26 | Analog Output Source | Write | 1=Built-in DP, 2=User I1, 3=User I2 | ||
| MV | 27 | Display Mode | Write | 1=1 Room 1 Sensor, 2=1 Room 2 Sensors, 3=1 Room 3 Sensors, 4=2 Rooms 2 Sensors, 5=3 Rooms 3 Sensors | ||
| MV | 28 | Room 1 Sensor 1 Select Analog | Write | 1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None | ||
| MV | 29 | Room 1 Sensor 2 Select Analog | Write | 1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None | ||
| MV | 30 | Room 1 Sensor 3 Select Analog | Write | 1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None | ||
| MV | 31 | Room 2 Sensor 1 Select Analog | Write | 1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None | ||
| MV | 32 | Room 3 Sensor 1 Select Analog | Write | 1=Built-in DP, 2=User I1, 3=User I2, 4=ES1, 5=ES2, 6=ES3, 7=None | ||
| MV | 33 | Room 1 Select Digital | Write | 1=None, 2=User I1, 3=User I2, 4=Digital I1, 5=ED1, 6=ED2, 7=ED3 | ||
| MV | 34 | Room 2 Select Digital | Write | 1=None, 2=User I1, 3=User I2, 4=Digital I1, 5=ED1, 6=ED2, 7=ED3 | ||
| MV | 35 | Room 3 Select Digital | Write | 1=None, 2=User I1, 3=User I2, 4=Digital I1, 5=ED1, 6=ED2, 7=ED3 | ||
| MVmin | 36 | Room 1 Mode | Room 1 operating mode | Write | 1=Occupied, 2=Unoccupied, 3=Cleaning | |
| MV | 37 | Room 2 Mode | Room 2 operating mode | Write | 1=Occupied, 2=Unoccupied, 3=Cleaning | |
| MV | 38 | Room 3 Mode | Room 3 operating mode | Write | 1=Occupied, 2=Unoccupied, 3=Cleaning | |
| MV | 39 | Language | Write | 1=English, 2=Espanol | ||
| MV | 40 | ES1 Object Type | External BACnet sensor ES1 | Write | 1=Analog Input, 2=Analog Value | |
| MV | 41 | ES1 Media Type | External BACnet sensor ES1 | Read | 1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow | |
| MV | 42 | ES1 Unit | External BACnet sensor ES1 | Read | 1=degrees C, 2=degrees F | |
| MV | 43 | ES1 Display Format | External BACnet sensor ES1 | Write | 1=0, 2=0.0, 3=0.00, 4=0.000 | |
| MV | 44 | ES1 Alarm Status | External BACnet sensor ES1 | Read | 1=OK, 2=Warning, 3=Alarm | |
| MV | 45 | ES2 Object Type | External BACnet sensor ES2 | Write | 1=Analog Input, 2=Analog Value | |
| MV | 46 | ES2 Media Type | External BACnet sensor ES2 | Read | 1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow | |
| MV | 47 | ES2 Unit | External BACnet sensor ES2 | Read | 1=degrees C, 2=degrees F | |
| MV | 48 | ES2 Display Format | External BACnet sensor ES2 | Write | 1=0, 2=0.0, 3=0.00, 4=0.000 | |
| MV | 49 | ES2 Alarm Status | External BACnet sensor ES2 | Read | 1=OK, 2=Warning, 3=Alarm | |
| MV | 50 | ES3 Object Type | External BACnet sensor ES3 | Write | 1=Analog Input, 2=Analog Value | |
| MV | 51 | ES3 Media Type | External BACnet sensor ES3 | Read | 1=Temperature, 2=Relative Humidity, 3=Pressure, 4=Flow | |
| MV | 52 | ES3 Unit | External BACnet sensor ES3 | Read | 1=degrees C, 2=degrees F | |
| MV | 53 | ES3 Display Format | External BACnet sensor ES3 | Write | 1=0, 2=0.0, 3=0.00, 4=0.000 | |
| MV | 54 | ES3 Alarm Status | External BACnet sensor ES3 | Read | 1=OK, 2=Warning, 3=Alarm | |
| MV | 55 | ED1 Object Type | External BACnet digital input ED1 | Write | 1=Binary Input, 2=Binary Value | |
| MV | 56 | ED1 Usage | External BACnet digital input ED1 | Write | 1=Remote Switch, 2=Door Contact | |
| MV | 57 | ED1 Polarity | External BACnet digital input ED1 | Write | 1=Reverse, 2=Direct | |
| MV | 58 | ED1 Status | External BACnet digital input ED1 | Read | 1=Door Open, 2=Door Closed | |
| MV | 59 | ED2 Object Type | External BACnet digital input ED2 | Write | 1=Binary Input, 2=Binary Value | |
| MV | 60 | ED2 Usage | External BACnet digital input ED2 | Write | 1=Remote Switch, 2=Door Contact | |
| MV | 61 | ED2 Polarity | External BACnet digital input ED2 | Write | 1=Reverse, 2=Direct | |
| MV | 62 | ED2 Status | External BACnet digital input ED2 | Read | 1=Door Open, 2=Door Closed | |
| MV | 63 | ED3 Object Type | External BACnet digital input ED3 | Write | 1=Binary Input, 2=Binary Value | |
| MV | 64 | ED3 Usage | External BACnet digital input ED3 | Write | 1=Remote Switch, 2=Door Contact | |
| MV | 65 | ED3 Polarity | External BACnet digital input ED3 | Write | 1=Reverse, 2=Direct | |
| MV | 66 | ED3 Status | External BACnet digital input ED3 | Read | 1=Door Open, 2=Door Closed | |
| PIV | 1 | Pressure Alarm Delay | s | Write | ||
| PIV | 2 | Pressure Alarm To Normal Delay | s | Write | ||
| PIV | 3 | UI1 Alarm Delay | s | Write | ||
| PIV | 4 | UI1 Alarm To Normal Delay | s | Write | ||
| PIV | 5 | UI2 Alarm Delay | s | Write | ||
| PIV | 6 | UI2 Alarm To Normal Delay | s | Write | ||
| PIV | 7 | Binary Input Alarm Delay | s | Write | ||
| PIV | 8 | Digital UI1 Alarm Delay | s | Write | ||
| PIV | 9 | Digital UI2 Alarm Delay | s | Write | ||
| PIV | 10 | Alarm Buzzer Volume | Write | |||
| PIV | 11 | Alarm Mute Timeout | s | Write | ||
| PIV | 12 | ES1 Device Instance | Device instance of external BACnet sensor | Write | ||
| PIV | 13 | ES1 Object Instance | Object instance read on that device | Write | ||
| PIV | 14 | ES1 Alarm Delay | External BACnet sensor ES1 | s | Write | |
| PIV | 15 | ES1 Alarm To Normal Delay | External BACnet sensor ES1 | s | Write | |
| PIV | 16 | ES2 Device Instance | External BACnet sensor ES2 | Write | ||
| PIV | 17 | ES2 Object Instance | External BACnet sensor ES2 | Write | ||
| PIV | 18 | ES2 Alarm Delay | External BACnet sensor ES2 | s | Write | |
| PIV | 19 | ES2 Alarm To Normal Delay | External BACnet sensor ES2 | s | Write | |
| PIV | 20 | ES3 Device Instance | External BACnet sensor ES3 | Write | ||
| PIV | 21 | ES3 Object Instance | External BACnet sensor ES3 | Write | ||
| PIV | 22 | ES3 Alarm Delay | External BACnet sensor ES3 | s | Write | |
| PIV | 23 | ES3 Alarm To Normal Delay | External BACnet sensor ES3 | s | Write | |
| PIV | 24 | ED1 Device Instance | External BACnet digital input ED1 | Write | ||
| PIV | 25 | ED1 Object Instance | External BACnet digital input ED1 | Write | ||
| PIV | 26 | ED1 Alarm Delay | External BACnet digital input ED1 | s | Write | |
| PIV | 27 | ED2 Device Instance | External BACnet digital input ED2 | Write | ||
| PIV | 28 | ED2 Object Instance | External BACnet digital input ED2 | Write | ||
| PIV | 29 | ED2 Alarm Delay | External BACnet digital input ED2 | s | Write | |
| PIV | 30 | ED3 Device Instance | External BACnet digital input ED3 | Write | ||
| PIV | 31 | ED3 Object Instance | External BACnet digital input ED3 | Write | ||
| PIV | 32 | ED3 Alarm Delay | External BACnet digital input ED3 | s | Write | |
| CSV | 1 | Pressure Display Name | Write | |||
| CSV | 2 | UI1 Display Name | Write | |||
| CSV | 3 | UI2 Display Name | Write | |||
| CSV | 4 | Room 1 Name | Write | |||
| CSV | 5 | Room 2 Name | Write | |||
| CSV | 6 | Room 3 Name | Write | |||
| CSV | 7 | Operator Password | Operator PIN | Write | ||
| CSV | 8 | Administrator Password | Administrator PIN, numeric | Write | ||
| CSV | 9 | ES1 Display Name | External BACnet sensor ES1 | Write | ||
| CSV | 10 | ES2 Display Name | External BACnet sensor ES2 | Write | ||
| CSV | 11 | ED2 Display Name | Third external sensor (ES3) display name | Write |
No points match these filters.
Object ID lookup: Dwyer RSME / RSMC point IDs by name
AI1PressureAI2UI1 ValueAI3UI2 ValueAV1Pressure High Alarm LimitAV2Pressure High Alarm WarningAV3Pressure Low Alarm LimitAV4Pressure Low Alarm WarningAV5Pressure Alarm DeadbandAV6UI1 Max SignalAV7UI1 Min SignalAV8UI1 Max Scale ValueAV9UI1 Min Scale ValueAV10UI1 High Alarm LimitAV11UI1 High Alarm WarningAV12UI1 Low Alarm LimitAV13UI1 Low Alarm WarningAV14UI1 Alarm DeadbandAV15UI2 Max SignalAV16UI2 Min SignalAV17UI2 Max Scale ValueAV18U12 Min Scale ValueAV19UI2 High Alarm LimitAV20UI2 High Alarm WarningAV21UI2 Low Alarm LimitAV22UI2 Low Alarm WarningAV23UI2 Alarm DeadbandAV24Duct AreaAV25Room VolumeAV26ES1 ValueAV27ES1 High Alarm LimitAV28ES1 High Alarm WarningAV29ES1 Low Alarm LimitAV30ES1 Low Alarm WarningAV31ES1 Alarm DeadbandAV32ES2 ValueAV33ES2 High Alarm LimitAV34ES2 High Alarm WarningAV35ES2 Low Alarm LimitAV36ES2 Low Alarm WarningAV37ES2 Alarm DeadbandAV38ES3 ValueAV39ES3 High Alarm LimitAV40ES3 High Alarm WarningAV41ES3 Low LimitAV42ES3 Low Alarm WarningAV43ES3 Alarm DeadbandBV1Pressure EnableBV2Pressure High Alarm EnableBV3Pressure Low Alarm EnableBV4UI1 EnableBV5UI1 High Alarm EnableBV6UI1 Low Alarm EnableBV7UI2 EnableBV8UI2 High Alarm EnableBV9UI2 Low Alarm EnableBV10Binary Input EnableBV11Binary Input Alarm EnableBV12Digital UI1 EnableBV13Digital UI1 Alarm EnableBV14Digital UI2 EnableBV15Digital UI2 Alarm EnableBV16Relay StatusBV17Password Security EnableBV18Alarm Latch EnableBV19Alarm Buzzer EnableBV20Alarm Mute Button EnableBV21Mute AlarmsBV22Reset AlarmsBV23ES1 EnableBV24ES1 High Alarm EnableBV25ES1 Low Alarm EnableBV26ES2 EnableBV27ES2 High Alarm EnableBV28ES2 Low Alarm EnableBV29ES3 EnableBV30ES3 High Alarm EnableBV31ES3 Low Alarm EnableBV32ED1 EnableBV33ED1 Alarm EnableBV34ED2 EnableBV35ED2 Alarm EnableBV36ED3 EnableBV37ED3 Alarm EnableMV1Pressure UnitMV2Pressure Display FormatMV3Pressure Alarm StatusMV4UI1 Signal TypeMV5UI1 Media TypeMV6UI1 UnitMV7UI1 Display FormatMV8UI1 Alarm StatusMV9UI2 Signal TypeMV10UI2 Media TypeMV11UI2 UnitMV12UI2 Display FormatMV13UI2 Alarm StatusMV14Binary Input UsageMV15Binary Input PolarityMV16Binary Input StatusMV17Digital UI1 UsageMV18Digital UI1 PolarityMV19Digital UI1 StatusMV20Digital UI2 UsageMV21Digital UI2 PolarityMV22Digital UI2 StatusMV23Relay OperationMV24Relay SourceMV25Analog Output TypeMV26Analog Output SourceMV27Display ModeMV28Room 1 Sensor 1 Select AnalogMV29Room 1 Sensor 2 Select AnalogMV30Room 1 Sensor 3 Select AnalogMV31Room 2 Sensor 1 Select AnalogMV32Room 3 Sensor 1 Select AnalogMV33Room 1 Select DigitalMV34Room 2 Select DigitalMV35Room 3 Select DigitalMV36Room 1 ModeMV37Room 2 ModeMV38Room 3 ModeMV39LanguageMV40ES1 Object TypeMV41ES1 Media TypeMV42ES1 UnitMV43ES1 Display FormatMV44ES1 Alarm StatusMV45ES2 Object TypeMV46ES2 Media TypeMV47ES2 UnitMV48ES2 Display FormatMV49ES2 Alarm StatusMV50ES3 Object TypeMV51ES3 Media TypeMV52ES3 UnitMV53ES3 Display FormatMV54ES3 Alarm StatusMV55ED1 Object TypeMV56ED1 UsageMV57ED1 PolarityMV58ED1 StatusMV59ED2 Object TypeMV60ED2 UsageMV61ED2 PolarityMV62ED2 StatusMV63ED3 Object TypeMV64ED3 UsageMV65ED3 PolarityMV66ED3 StatusPIV1Pressure Alarm DelayPIV2Pressure Alarm To Normal DelayPIV3UI1 Alarm DelayPIV4UI1 Alarm To Normal DelayPIV5UI2 Alarm DelayPIV6UI2 Alarm To Normal DelayPIV7Binary Input Alarm DelayPIV8Digital UI1 Alarm DelayPIV9Digital UI2 Alarm DelayPIV10Alarm Buzzer VolumePIV11Alarm Mute TimeoutPIV12ES1 Device InstancePIV13ES1 Object InstancePIV14ES1 Alarm DelayPIV15ES1 Alarm To Normal DelayPIV16ES2 Device InstancePIV17ES2 Object InstancePIV18ES2 Alarm DelayPIV19ES2 Alarm To Normal DelayPIV20ES3 Device InstancePIV21ES3 Object InstancePIV22ES3 Alarm DelayPIV23ES3 Alarm To Normal DelayPIV24ED1 Device InstancePIV25ED1 Object InstancePIV26ED1 Alarm DelayPIV27ED2 Device InstancePIV28ED2 Object InstancePIV29ED2 Alarm DelayPIV30ED3 Device InstancePIV31ED3 Object InstancePIV32ED3 Alarm DelayCSV1Pressure Display NameCSV2UI1 Display NameCSV3UI2 Display NameCSV4Room 1 NameCSV5Room 2 NameCSV6Room 3 NameCSV7Operator PasswordCSV8Administrator PasswordCSV9ES1 Display NameCSV10ES2 Display NameCSV11ED2 Display Name
Integration notes
- Object names come from Table 1 of the manual; access, units and state texts come from the per-object pages (Present Value property access).
- Table 1 and the detail pages disagree on a few names. MSV 16 is printed "Binary Input Alarm Enable" in Table 1 but its detail page, states and siblings (MSV 19, MSV 58) make it the input status, so the detail name "Binary Input Status" is used. BV 11 (detail: "Binary Alarm Enable"), CSV 11 and the MSV 36-38 detail name keep Table 1. The BV 18 text calls Reset Alarms BV21; Table 1 and its own page put it at BV 22.
- AV 18 is printed "U12 Min Scale Value" and AV 41 "ES3 Low Limit"; names are kept as printed.
- Units are defaults: pressure objects follow MV 1 Pressure Unit (default inWC); universal and external sensor values follow their media type and unit setting (default °F); AV 6/7 default to volts for UI1 and AV 15/16 to mA for UI2.
- Multi-state values are typed MSV in the manual and shown here as MV.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Series RSME / RSMC Room Status Monitor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Dwyer Series RSME / RSMC Room Status Monitor
How many BACnet points does the Dwyer Series RSME / RSMC Room Status Monitor have?
This list has 192 BACnet objects: 3 analog inputs, 43 analog values, 37 binary values, 66 multi-state values, 11 characterstring values, 32 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Dwyer Series RSME / RSMC Room Status Monitor BACnet points are writable?
161 of the 192 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Dwyer Series RSME / RSMC Room Status Monitor BACnet documentation?
The source is Series RSME/RSMC BACnet/Modbus Operating Instructions, published free by Dwyer at https://assets.dwyeromega.com/manuals-do/RSMC_BACnet_and_Modbus_Operation_Instructions.pdf.
What are the minimum BACnet points to integrate the Dwyer Series RSME / RSMC Room Status Monitor?
Start with MV 36 Room 1 Mode (Room 1 mode: 1 Occupied, 2 Unoccupied, 3 Cleaning); BV 22 Reset Alarms (Write 1 to reset latched alarms); AI 1 Pressure (Room differential pressure, inWC by default); MV 16 Binary Input Status (Door/switch input status (Door Open/Closed)); BV 16 Relay Status (Alarm relay state); MV 3 Pressure Alarm Status (Pressure alarm: 1 OK, 2 Warning, 3 Alarm).
How do I enable BMS control of the Dwyer Series RSME / RSMC Room Status Monitor?
BV 1 Pressure Enable turns monitoring of the built-in sensor on; each universal input and external sensor has its own enable BV.
Can the BMS supply sensor values to the Dwyer Series RSME / RSMC Room Status Monitor?
Up to three external BACnet analog sensors (ES1-ES3) and three digital points (ED1-ED3) are read by the monitor itself: set the remote device instance and object instance (PIV 12/13 for ES1 and so on), the object type, then enable the sensor. The remote device must answer a directed Who-Is. Values appear in AV 26/32/38 and MSV 58/62/66.
How do I check these points on the real Series RSME / RSMC Room Status Monitor?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Dwyer BACnet points lists
- CO2, humidity and temperature room sensor
Dwyer Series CDTA / CDTC Communicating CO2 Detector
Dwyer Series CDTA (CO2, humidity, temperature) and CDTC (CO2, temperature) wall-mount detectors with setpoint and override, BACnet MS/TP or Modbus RTU.
Also known as: CDTA, CDTC, CDTA-2N000, CDTA-5N000, CDTC-2N000, CDTC-5N000, CDTA-2N000-LCD - Differential pressure and airflow sensor
Dwyer Series MS2 Magnesense II Differential Pressure Transmitter with BACnet (MS2-B)
Dwyer Series MS2 Magnesense II differential pressure transmitters with BACnet MS/TP (ranges up to 25 in. w.c.).
Also known as: MS2-B, MS2, Magnesense II, P-MS2-B - Differential pressure sensor / transmitter
Dwyer Series MSX-Comms Magnesense Pressure Transmitter
Dwyer Series MSX-Comms Magnesense differential pressure transmitters with BACnet MS/TP or Modbus RTU output.
Also known as: MSX, MSX-Comms, Magnesense MSX, DwyerOmega MSX, MSX BACnet - Ultrasonic BTU / energy meter
Dwyer Series TUF ultrasonic energy meter, BACnet MS/TP (TUF-B)
Dwyer Series TUF ultrasonic heating/cooling energy meters (TUF-150 to TUF-2000) ordered with BACnet MS/TP.
Also known as: TUF, TUF-B, TUF BACnet, Dwyer TUF BTU meter, DwyerOmega TUF
Source: Series RSME/RSMC BACnet/Modbus Operating Instructions. Object names, instances and units are reproduced as published; descriptions are our own.