Differential pressure sensor / controller · BACnet points list

Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP BACnet points list

Updated 12 November 2026

Short answer

The DHC Digihelic is a differential pressure gauge, transmitter and two-relay controller that can also show velocity or flow. Its RS-485 port runs Modbus RTU (factory setting) or BACnet MS/TP, picked in the Conn menu. Over BACnet it exposes pressure, derived velocity and flow, peak and valley, and all set point, alarm, relay and external input settings as writable objects.

This page lists 37 BACnet objects for the Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP — 29 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Dwyer’s own free documentation, linked below.

Manufacturer
Dwyer
Model
Series DHC Digihelic differential pressure controller, BACnet MS/TP
Equipment
Differential pressure sensor / controller
Equipment type
Thermostats, sensors & meters
BACnet objects
37 (29 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
607000 + MS/TP address (607xxx)
Also known as
DHC, Series DHC, Digihelic, Digihelic DHC, DwyerOmega DHC, DHC-xxx-xxx
Source document
Series DHC Digihelic Differential Pressure Controller - Specifications, Installation and Operating Instructions · Bulletin P-DHC (FR# 444618-00 Rev. 1) · rev. 3/23
Download CSV 37 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Dwyer’s current documentation and the live device before use. Not official Dwyer information. Terms of use.

BMS integration notes: Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP

Integration in brief

Pick BAC in the Prot sub menu, set an address, then read AI 1 pressure (or AV 1 / AV 2 velocity and flow). Set point, alarm and relay settings are all writable over the network if the BMS should own them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 9Set Point 1 Trigger ValueSet point 1 trigger value, process unitsWrite
AI 1PressureDifferential pressureRead
AV 2FlowAirflow (flow mode)Read
BV 2Set Point 1 StatusSet point 1 activeRead
BV 4Set Point 2 StatusSet point 2 activeRead
BV 6Alarm High Limit StatusHigh alarm activeWrite
BV 8Alarm Low Limit StatusLow alarm activeWrite

Network setup

Watch out for

Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

37 of 37 shown
Type
BinaryMulti-stateOther
Access
Show
Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP BACnet Points List
DescriptionStates
AImin1PressureDifferential pressure; units model specificRead
AV1VelocityVelocity from pressure; fpm or m/sRead
AVmin2FlowFlow from velocity and area; cfm or m3/hRead
AV3PeakHighest process value since power-up or resetRead
AV4ValleyLowest process value since power-up or resetRead
AV5Velocity K-FactorPitot tube K-factor, default 1.0Write
AV6Flow AreaDuct cross-section area, 0.13-25.0 ft2ft²Write
AV7Process Output LowProcess value at minimum analog outputWrite
AV8Process Output HighProcess value at maximum analog outputWrite
AVmin9Set Point 1 Trigger ValueValue at which set point 1 turns activeWrite
AV10Set Point 1 Reset ValueValue at which set point 1 turns inactiveWrite
AV11Set Point 2 Trigger ValueValue at which set point 2 turns activeWrite
AV12Set Point 2 Reset ValueValue at which set point 2 turns inactiveWrite
AV13Alarm High LimitHigh alarm limitWrite
AV14Alarm Low LimitLow alarm limitWrite
MV1Process ModeProcess variable for outputs and limitsWrite1=Pressure, 2=Velocity, 3=Flow
MV2Voltage Output RangeVoltage output rangeWrite1=0-10V, 2=0-5V, 3=2-10V, 4=1-5
MV3Relay 1 SourceWhat drives relay 1Write1=Off, 2=Set Point 1, 3=Set Point 2, 4=Any Alarm, 5=Alarm High Limit, 6=Alarm Low Limit, 7=External Input
MV4Relay 1 ActionRelay 1 action when activeWrite1=Direct, 2=Reverse
MV5Relay 2 SourceWhat drives relay 2Write1=Off, 2=Set Point 1, 3=Set Point 2, 4=Any Alarm, 5=Alarm High Limit, 6=Alarm Low Limit, 7=External Input
MV6Relay 2 ActionRelay 2 action when activeWrite1=Direct, 2=Reverse
MV7External Input TypeContact type on the external inputWrite1=Normally Open, 2=Normally Closed
BV1Enable Set Point 1Enable set point 1Write0=Inactive, 1=Active
BVmin2Set Point 1 StatusSet point 1 activeRead0=Inactive, 1=Active
BV3Enable Set Point 2Enable set point 2Write0=Inactive, 1=Active
BVmin4Set Point 2 StatusSet point 2 activeRead0=Inactive, 1=Active
BV5Enable Alarm High LimitEnable high alarmWrite0=Inactive, 1=Active
BVmin6Alarm High Limit StatusHigh alarm active; write inactive to reset (manual reset mode)Write0=Inactive, 1=Active
BV7Enable Alarm Low LimitEnable low alarmWrite0=Inactive, 1=Active
BVmin8Alarm Low Limit StatusLow alarm active; write inactive to reset (manual reset mode)Write0=Inactive, 1=Active
BV9Manual Alarm ResetAlarms latch until reset when activeWrite0=Inactive, 1=Active
BV10Power Up Alarm InhibitLow alarm held off until value first rises above limitWrite0=Inactive, 1=Active
BV11Enable External InputEnable the external inputWrite0=Inactive, 1=Active
BV12External Input StatusExternal input activeRead0=Inactive, 1=Active
PIV1Alarm DelayTime an alarm condition must last, max 3600Write
PIV2External Input Activation DelayTime the input must be on before active, max 3600Write
PIV3Damping TimeMeasurement damping, 0-30 s; 0 = offsWrite
Object ID lookup: Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Series DHC Digihelic differential pressure controller, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP

How many BACnet points does the Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP have?

This list has 37 BACnet objects: 1 analog input, 14 analog values, 12 binary values, 7 multi-state values, 3 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP BACnet points are writable?

29 of the 37 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP BACnet documentation?

The source is Series DHC Digihelic Differential Pressure Controller - Specifications, Installation and Operating Instructions (Bulletin P-DHC (FR# 444618-00 Rev. 1)), revision 3/23, published free by Dwyer at https://assets.dwyeromega.com/manuals-do/AT_DHC_Instruction_Manual.pdf.

What are the minimum BACnet points to integrate the Dwyer Series DHC Digihelic differential pressure controller, BACnet MS/TP?

Start with AV 9 Set Point 1 Trigger Value (Set point 1 trigger value, process units); AI 1 Pressure (Differential pressure); AV 2 Flow (Airflow (flow mode)); BV 2 Set Point 1 Status (Set point 1 active); BV 4 Set Point 2 Status (Set point 2 active); BV 6 Alarm High Limit Status (High alarm active); BV 8 Alarm Low Limit Status (Low alarm active).

How do I check these points on the real Series DHC Digihelic differential pressure controller, BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Dwyer BACnet points lists

Source: Series DHC Digihelic Differential Pressure Controller - Specifications, Installation and Operating Instructions · Bulletin P-DHC (FR# 444618-00 Rev. 1) · rev. 3/23. Object names, instances and units are reproduced as published; descriptions are our own.