 "manufacturer": "Dwyer",
 "manufacturer_slug": "dwyer",
 "model": "Series AVPT pencil-style air velocity transmitter, BACnet MS/TP",
 "model_slug": "avpt-air-velocity-transmitter",
 "aliases": [
  "AVPT",
  "Series AVPT",
  "AVPT BACnet",
  "DwyerOmega AVPT",
  "AVPT pencil style air velocity transmitter"
 ],
 "equipment_type": "Duct airflow velocity sensor",
 "applies_to": "Dwyer Series AVPT thermal-anemometer duct velocity transmitters ordered with the BACnet MS/TP output.",
 "summary": "The AVPT is a pencil-style thermal anemometer probe for duct air velocity, sold with either analog outputs or a BACnet MS/TP output. On BACnet it exposes velocity and air temperature as four Analog Inputs (each in imperial and metric), plus objects to set the MS/TP address, the baud rate and a factory reset.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "607000 + MS/TP address (607xxx)",
 "access_inferred": false,
 "notes": [
  "Velocity and temperature are each given twice, in imperial and metric units, as separate objects.",
  "The overview table prints BV 1 as \"Restore Factory Defauls\"; the property table spells it \"Restore Factory Defaults\".",
  "Factory address is 127; the device instance follows the address until a specific instance is written."
 ],
 "source": {
  "title": "Series AVPT Pencil Style Air Velocity Transmitter - Specifications, Installation and Operating Instructions",
  "doc_number": "Bulletin AQ-AVPT-C (FR# 444544-00)",
  "revision_date": "11/19",
  "url": "https://assets.dwyeromega.com/manuals-do/AVPT_AVPT_BACnet.pdf"
 },
 "integration": {
  "summary": "Set a unique MS/TP address (PIV 1, then power cycle), let auto-baud lock onto the bus, and read velocity and temperature in the units you need (AI 1-4).",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "Velocity FPM",
    "why": "Duct air velocity, FPM"
   },
   {
    "ref": "AI 3",
    "name": "Temperature F",
    "why": "Duct air temperature, °F"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Ships at MS/TP address 127; write the new address to PIV 1 and reset or power cycle the device.",
   "Auto-baud is on by default (9600 to 115200, 8N1); it locks in after the first Who-Is or ReadProperty it answers.",
   "Device instance defaults to 607xxx (xxx = address) until a specific instance is written.",
   "DeviceCommunicationControl and ReinitializeDevice need the password \"Dwyer\".",
   "Max Master changes need a power cycle."
  ],
  "gotchas": [
   "The device may not answer while auto-baud is still detecting the bus speed.",
   "Default comms settings can also be restored by wiring: briefly connect the white CFG wire to ground as the manual describes."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Velocity FPM",
   "description": "Air velocity",
   "units": "ft/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Velocity MPS",
   "description": "Air velocity",
   "units": "m/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Temperature F",
   "description": "Air temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Temperature C",
   "description": "Air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 1,
   "name": "Device Address",
   "description": "MS/TP MAC address, 0-127; reset needed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Serial Baud Rate",
   "description": "MS/TP baud rate; Auto Baud is default",
   "units": "",
   "access": "W",
   "states": "1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto Baud"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Restore Factory Defaults",
   "description": "Write active then reset to restore defaults",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=Active"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/dwyer/avpt-air-velocity-transmitter",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}