Electronic mixing valve (via gateway) · BACnet points list

Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 BACnet points list

Updated 12 November 2026

Short answer

The LEGIOMIX 6000 is an electronic thermostatic mixing valve for domestic hot water with programmable thermal disinfection and thermal shock. The Caleffi 755052 gateway maps its Modbus RTU registers to Analog and Binary Values on BACnet MS/TP or BACnet IP: mixed and recirculation temperatures, valve state, setpoints, disinfection schedule and timers, clock settings and command/reset objects.

This page lists 50 BACnet objects for the Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Caleffi’s own free documentation, linked below.

Manufacturer
Caleffi
Model
LEGIOMIX 6000 series mixing valve via gateway 755052
Equipment
Electronic mixing valve (via gateway)
Equipment type
Valves & actuators
BACnet objects
50 (42 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
LEGIOMIX 6000, Legiomix_6000_Series, 6001, Caleffi 755052, Caleffi Modbus RTU / BACnet gateway, FPC-N54
Source document
Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 5 LEGIOMIX_6000_SERIES Modbus RTU mappings to BACnet · H0004703.03 · rev. 2024
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Caleffi’s current documentation and the live device before use. Not official Caleffi information. Terms of use.

BMS integration notes: Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052

Integration in brief

Add the Legiomix_6000_Series profile and the valve's Modbus Node-ID in the gateway, then read AV 3 mixed temperature, AV 4 recirculation temperature and AV 7 state. Write the mixing and disinfection setpoints (AV 23/24) as needed and use BV 42 to reset alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 23Set Reg Deg_C (Set Mix temp)Mixed water setpoint, °CWrite
AV 3Tmix Deg_C (Mixing temp.)Mixed water temperature, °CRead
AV 4Trec Deg_C (Recirculation temp.)Recirculation temperature, °CRead
AV 7StateState: regulation, disinfection, flushing, shock, alarmRead
BV 42Alarm ResetAlarm resetWrite

Network setup

Watch out for

Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

50 of 50 shown
Type
AnalogBinary
Access
Show
Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 BACnet Points List
DescriptionStates
AV1Product typeProduct code (6001)Read
AV2AddressModbus address, 1-247Read
AVmin3Tmix Deg_C (Mixing temp.)Mixed water temperature°CRead
AVmin4Trec Deg_C (Recirculation temp.)Recirculation temperature°CRead
AV5Tmix Deg_F (Mixing temp.)Mixed water temperature°FRead
AV6Trec Deg_F (Recirculation temp.)Recirculation temperature°FRead
AVmin7StateValve operating stateRead1=Regulation, 2=Disinfection, 3=Flushing, 4=Thermal shock, 5=Alarm
AV8Program IDActive programRead0=0, 1=1a, 2=1b, 3=2
AV9Current DayClock day, 1-31Write
AV10Current MonthClock month, 1-12Write
AV11Current YearClock yearWrite
AV12Current HourClock hour, 0-23Write
AV13Current MinuteClock minute, 0-59Write
AV14LanguageDisplay languageWrite0=IT, 1=EN, 2=FR, 3=DE, 4=ES, 5=PT, 6=NL, 7=SL, 8=HR, 9=SR, 10=RO
AV15Time ON (h) (Start dis.)Disinfection start hour, 0-23hWrite
AV16Time ON (m) (Start dis.)Disinfection start minute, 0-59minWrite
AV17Time OFF (h) (Stop dis.)Disinfection stop hour, 0-23hWrite
AV18Time OFF (m) (Stop dis.)Disinfection stop minute, 0-59minWrite
AV19Time Wait (before reading rec.)Wait before reading recirculation temp, 1-255minWrite
AV20Time min (to have correct dis.)Minimum time for a valid disinfection, 0-254minWrite
AV21Time Flux (Time of closing relay 4 after ending the dis.)Relay 4 closing time after disinfection, 0-2550sWrite
AV22Time Shock (Time of duration)Thermal shock duration, 1-4320minWrite
AVmin23Set Reg Deg_C (Set Mix temp)Mixing setpoint, 20-85°CWrite
AV24Set Dis Deg_C (Set Dis temp)Disinfection setpoint, 40-85°CWrite
AV25Set Ric Deg_C (Set Rec temp)Recirculation setpoint, 40-85°CWrite
AV26Set Shock Deg_C (Set Shock temp)Thermal shock setpoint, 30-85°CWrite
AV27Set Tmax Deg_C (Set max temp)Maximum temperature, 50-90°CWrite
AV28Set Reg Deg_F (Set Mix temp)Mixing setpoint, 68-185°FWrite
AV29Set Dis Deg_F (Set Dis temp)Disinfection setpoint, 104-185°FWrite
AV30Set Ric Deg_F (Set Rec temp)Recirculation setpoint, 104-185°FWrite
AV31Set Shock Deg_F (Set Shock temp)Thermal shock setpoint, 86-185°FWrite
AV32Set Tmax Deg_F (Set max temp)Maximum temperature, 122-194°FWrite
AV33Daily DisinfectionDisinfection days, bit-codedWritebit 0=Monday ... bit 5=Saturday, bit 6=Sunday
BV34Presence of Recirculation ProbeRecirculation probe fittedWrite1=Presence of Rec probe
BV35AnticlogAnti-clog functionWrite1=Anticlog
AV36Legal HourDaylight saving ruleWritebit 2:0 bit 3:1=Disabled, bit 2:1 bit 3:0=EUR, bit 2:0 bit 3:1=USA, bit 2:1 bit 3:1=Custom
BV37International System of UnitTemperature unitWrite0=°C, 1=°F
BV38LED Display EnableLED display onWrite1=LED display enable
BV39Shock ActivationStart thermal shockWrite1=Shock Activation
BV40Pin-code ResetReset PIN codeWrite1=Pin-code Reset
BV41Disinfection ResetReset disinfectionWrite2=Disinfection Reset
BVmin42Alarm ResetReset alarmWrite3=Alarm Reset
BV43Historical DataHistorical data commandWrite4=Historical Data
BV44Shock DeactivationStop thermal shockWrite1=Shock Deactivation
AV45Time Motor (Time to move actuator from close to open position)Actuator stroke time, 8-320sWrite
AV46Time Play (Delay of time in movement of actuator while changing direction)Actuator reversal play delay, 1-255sWrite
AV47Start Sunday Legal HourDST start Sunday (custom rule)Write-3, -2, -1, 1, 2, 3
AV48Start Month Legal HourDST start month, 1-12Write
AV49End Sunday Legal HourDST end Sunday (custom rule)Write-3, -2, -1, 1, 2, 3
AV50End Month Legal HourDST end month, 1-12Write
Object ID lookup: Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LEGIOMIX 6000 series mixing valve via gateway 755052 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052

How many BACnet points does the Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 have?

This list has 50 BACnet objects: 40 analog values, 10 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 BACnet points are writable?

42 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052 BACnet documentation?

The source is Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 5 LEGIOMIX_6000_SERIES Modbus RTU mappings to BACnet (H0004703.03), revision 2024, published free by Caleffi at https://www.caleffi.com/sites/default/files/media/external-file/h0004703_EN.pdf.

What are the minimum BACnet points to integrate the Caleffi LEGIOMIX 6000 series mixing valve via gateway 755052?

Start with AV 23 Set Reg Deg_C (Set Mix temp) (Mixed water setpoint, °C); AV 3 Tmix Deg_C (Mixing temp.) (Mixed water temperature, °C); AV 4 Trec Deg_C (Recirculation temp.) (Recirculation temperature, °C); AV 7 State (State: regulation, disinfection, flushing, shock, alarm); BV 42 Alarm Reset (Alarm reset).

How do I check these points on the real LEGIOMIX 6000 series mixing valve via gateway 755052?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Caleffi BACnet points lists

Source: Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 5 LEGIOMIX_6000_SERIES Modbus RTU mappings to BACnet · H0004703.03 · rev. 2024. Object names, instances and units are reproduced as published; descriptions are our own.