Electronic mixing valve with thermal disinfection · BACnet points list

Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve BACnet points list

Updated 6 November 2026

Short answer

LEGIOMIXevo is an electronic 3-way mixing valve controller for domestic hot water that holds the mixed outlet temperature and runs scheduled thermal disinfection (anti-legionella) cycles. Over BACnet IP it exposes the mixing, recirculation and storage temperatures, the mixing setpoint, the running function and alarm codes, relay states, feature flags and identification strings.

This page lists 25 BACnet objects for the Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Caleffi’s own free documentation, linked below.

Manufacturer
Caleffi
Model
LEGIOMIXevo 6003 Series Electronic Mixing Valve
Equipment
Electronic mixing valve with thermal disinfection
Equipment type
Valves & actuators
BACnet objects
25 (1 writable)
Transport
BACnet IP
Firmware
2.0.0 or higher
Also known as
LEGIOMIXevo, LEGIOMIX evo, Serie 6003, 6003 Series
Source document
LEGIOMIXevo Electronic Mixing Valve with thermal disinfection - BACnet Protocol Implementation Conformance Statement (PICS) · SPD25_010 · rev. Rev. 2, 18/03/2026
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Caleffi’s current documentation and the live device before use. Not official Caleffi information. Terms of use.

BMS integration notes: Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve

Integration in brief

Read the mixed water, recirculation and storage temperatures, the running function (AV 10) and alarm code (AV 11). The BMS can change the mixing setpoint (AV 17). Disinfection and other programs run from the valve controller itself.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 17Mixing Temperature SetMixed water setpointWrite
AI 14Mixing TemperatureMixed outlet water temperatureRead
AI 15Recirculation TemperatureRecirculation return temperatureRead
AV 10StateRunning function, e.g. 8 = mixingRead
BV 20Relay 1- REC PUMPRecirculation pump relay closedRead
AV 11Alarm CodeActive alarm code; 0 = no errorRead
BV 24Relay 5 - ALARMAlarm relay closed on alarm or power lossRead

Network setup

Watch out for

Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

25 of 25 shown
Type
BinaryOther
Access
Show
Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve BACnet Points List
DescriptionStates
AImin14Mixing TemperatureMixing NTC probe temperature°C/°FRead
AImin15Recirculation TemperatureRecirculation NTC probe temperature°C/°FRead
AI16Storage TemperatureStorage NTC probe temperature°C/°FRead
AV5Current DayRead
AV6Current MonthRead
AV7Current YearRead
AV8Current HourRead
AV9Current MinuteRead
AVmin10StateRunning function code (Annex A)Read0=UNDEFINED, 1=PROGRAM 1, 2=PROGRAM 2, 3=PROGRAM 3, 4=FLUSH, 5=SHOCK, 6=ANTICLOG, 7=STOP_PROGRAM, 8=MIXING, 9=SAFETY VALVE, 88=INIT_ALL, 99=NO_PROGRAM
AVmin11Alarm CodeActive alarm code (Annex B)Read0=No error, 1=Disinfection error, 4=Flush run error, 5=Shock run error, 10=Mixing probe fault, 11=Mixing probe protection, 20=Recirculation probe fault, 21=Recirculation probe protection, 30=Boiler probe fault, 31=Boiler probe protection, 55=Shock on, 66=Safety Valve, 77=Wrong Settings, 101=Initialization error, 102=OS error, 103=Memory Error, 104=Loading Error, 105=Zeroing error, 106=Anticlog error, 110=Download error, 201=Disinfection fault, 204=Flush error, 205=Shock error, 301=Date and time lost, 401=OTA fault
AVmin17Mixing Temperature SetMixed water setpoint, 40-85 °C (105-185 °F)°C/°FWrite
BV12Presence of Recirculation ProbeRecirculation NTC fitted or notRead
BV13Presence of Storage ProbeStorage NTC fitted or notRead
BV18Disinfection EnabledDisinfection function enabledRead
BV19Anticlog EnabledAnticlog function enabledRead
BVmin20Relay 1- REC PUMPRecirculation pump relayRead0=Open, 1=Closed
BV21Relay 2 - FLUSHFlush relayRead0=Open, 1=Closed
BV22Relay 3 - SAFETY VALVESafety valve relayRead0=Open, 1=Closed
BV23Relay 4 - AUXAuxiliary relayRead0=Open, 1=Closed
BVmin24Relay 5 - ALARMAlarm relay; closed on alarm or no powerRead0=Open, 1=Closed
CSV0SerieRead
CSV1Firmware VersionRead
CSV2Hardware VersionRead
CSV3Product CodeRead
CSV4Serial NumberRead
Object ID lookup: Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LEGIOMIXevo 6003 Series Electronic Mixing Valve and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve

How many BACnet points does the Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve have?

This list has 25 BACnet objects: 3 analog inputs, 8 analog values, 9 binary values, 5 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve BACnet points are writable?

1 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve BACnet documentation?

The source is LEGIOMIXevo Electronic Mixing Valve with thermal disinfection - BACnet Protocol Implementation Conformance Statement (PICS) (SPD25_010), revision Rev. 2, 18/03/2026, published free by Caleffi at https://www.caleffi.com/sites/default/files/media/external-file/PICS_sdp25_010_rev_02_LEGIOMIXevo.pdf.

What are the minimum BACnet points to integrate the Caleffi LEGIOMIXevo 6003 Series Electronic Mixing Valve?

Start with AV 17 Mixing Temperature Set (Mixed water setpoint); AI 14 Mixing Temperature (Mixed outlet water temperature); AI 15 Recirculation Temperature (Recirculation return temperature); AV 10 State (Running function, e.g. 8 = mixing); BV 20 Relay 1- REC PUMP (Recirculation pump relay closed); AV 11 Alarm Code (Active alarm code; 0 = no error); BV 24 Relay 5 - ALARM (Alarm relay closed on alarm or power loss).

How do I check these points on the real LEGIOMIXevo 6003 Series Electronic Mixing Valve?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.