Easy BACnet
  1. Home
  2. BACnet points lists
  3. Caleffi
  4. CONTECA EASY 750 series heat meter via gateway 755052

Heat / energy meter (via gateway) · BACnet points list

Caleffi CONTECA EASY 750 series heat meter via gateway 755052 BACnet points list

Updated 12 November 2026

Short answer

CONTECA EASY 750 is a heating and cooling energy meter. Through the Caleffi 755052 gateway it appears on BACnet MS/TP or BACnet IP as read-only Analog Inputs for heating and cooling energy, four pulse inputs (e.g. hot and cold water meters), power, flow, flow and return temperatures and an alarm/status word. Every value is mapped twice: AI 1-14 in SI units and AI 15-28 in imperial units.

This page lists 28 BACnet objects for the Caleffi CONTECA EASY 750 series heat meter via gateway 755052 — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Caleffi’s own free documentation, linked below.

Manufacturer
Caleffi
Model
CONTECA EASY 750 series heat meter via gateway 755052
Equipment
Heat / energy meter (via gateway)
Equipment type
Thermostats, sensors & meters
BACnet objects
28 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
CONTECA EASY, Conteca_Easy_750_Series, 750 series, 7500, Caleffi heat meter BACnet, Caleffi 755052
Source document
Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 7 CONTECA_EASY_750_SERIES Modbus RTU mappings to BACnet · H0004703.03 · rev. 2024
Download CSV 28 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Caleffi’s current documentation and the live device before use. Not official Caleffi information. Terms of use.

BMS integration notes: Caleffi CONTECA EASY 750 series heat meter via gateway 755052

Integration in brief

Add the Conteca_Easy_750_Series profile and the meter's Modbus Node-ID in the gateway, then read heating and cooling energy, power, flow and temperatures. Decode AI 14 for meter errors.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3Heating EnergyHeating energy, kWhRead
AI 4Cooling EnergyCooling energy, kWhRead
AI 9PowerThermal power, kWRead
AI 10Flow RateFlow rate, m³/hRead
AI 11Flow TemperatureFlow temperature, °CRead
AI 12Return TemperatureReturn temperature, °CRead
AI 14Alarm/StatusAlarm/status bits (sensor, flow, battery)Read

Network setup

Watch out for

Caleffi CONTECA EASY 750 series heat meter via gateway 755052 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

28 of 28 shown
Type
Analog
Show
Caleffi CONTECA EASY 750 series heat meter via gateway 755052 BACnet Points List
DescriptionStates
AI1ProductProduct code (7500)Read
AI2IDModbus ID, 1-250Read
AImin3Heating EnergyHeating energykWhRead
AImin4Cooling EnergyCooling energykWhRead
AI5Pulse Input 1Pulse input 1 (DHW)m³Read
AI6Pulse Input 2Pulse input 2 (DCW)m³Read
AI7Pulse Input 3Pulse input 3m³ / kWhRead
AI8Pulse Input 4Pulse input 4m³ / kWhRead
AImin9PowerThermal powerkWRead
AImin10Flow RateFlow ratem³/hRead
AImin11Flow TemperatureFlow temperature°CRead
AImin12Return TemperatureReturn temperature°CRead
AI13Delta TemperatureFlow minus return temperatureRead
AImin14Alarm/StatusAlarm and status bitsReadbit 0=T Flow error, bit 1=T Return error, bit 2=No flow rate, bit 3=Valve internal leakage, bit 6=Battery error, bit 7=No credit, bits 8-12=Measurement unit error C0-C4
AI15Product (Imperial Units)Product code (7500), imperialRead
AI16ID (Imperial Units)Modbus ID, 1-250, imperialRead
AI17Heating Energy (Imperial Units)Heating energy, imperialkBTURead
AI18Cooling Energy (Imperial Units)Cooling energy, imperialkBTURead
AI19Pulse Input 1 (Imperial Units)Pulse input 1 (DHW), imperialkgalRead
AI20Pulse Input 2 (Imperial Units)Pulse input 2 (DCW), imperialkgalRead
AI21Pulse Input 3 (Imperial Units)Pulse input 3, imperialkgal / kBTURead
AI22Pulse Input 4 (Imperial Units)Pulse input 4, imperialkgal / kBTURead
AI23Power (Imperial Units)Thermal power, imperialkBTU/hRead
AI24Flow Rate (Imperial Units)Flow rate, imperialGPMRead
AI25Flow Temperature (Imperial Units)Flow temperature, imperial°FRead
AI26Return Temperature (Imperial Units)Return temperature, imperial°FRead
AI27Delta Temperature (Imperial Units)Flow minus return temperature, imperialRead
AI28Alarm/Status (Imperial Units)Alarm and status bits, imperialReadbit 0=T Flow error, bit 1=T Return error, bit 2=No flow rate, bit 3=Valve internal leakage, bit 6=Battery error, bit 7=No credit, bits 8-12=Measurement unit error C0-C4
Object ID lookup: Caleffi CONTECA EASY 750 series heat meter via gateway 755052 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CONTECA EASY 750 series heat meter via gateway 755052 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Caleffi CONTECA EASY 750 series heat meter via gateway 755052

How many BACnet points does the Caleffi CONTECA EASY 750 series heat meter via gateway 755052 have?

This list has 28 BACnet objects: 28 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Caleffi CONTECA EASY 750 series heat meter via gateway 755052 BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Caleffi CONTECA EASY 750 series heat meter via gateway 755052 BACnet documentation?

The source is Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 7 CONTECA_EASY_750_SERIES Modbus RTU mappings to BACnet (H0004703.03), revision 2024, published free by Caleffi at https://www.caleffi.com/sites/default/files/media/external-file/h0004703_EN.pdf.

What are the minimum BACnet points to integrate the Caleffi CONTECA EASY 750 series heat meter via gateway 755052?

Start with AI 3 Heating Energy (Heating energy, kWh); AI 4 Cooling Energy (Cooling energy, kWh); AI 9 Power (Thermal power, kW); AI 10 Flow Rate (Flow rate, m³/h); AI 11 Flow Temperature (Flow temperature, °C); AI 12 Return Temperature (Return temperature, °C); AI 14 Alarm/Status (Alarm/status bits (sensor, flow, battery)).

How do I check these points on the real CONTECA EASY 750 series heat meter via gateway 755052?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Caleffi BACnet points lists

Source: Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 7 CONTECA_EASY_750_SERIES Modbus RTU mappings to BACnet · H0004703.03 · rev. 2024. Object names, instances and units are reproduced as published; descriptions are our own.