Electronic mixing valve (via gateway) · BACnet points list

Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 BACnet points list

Updated 12 November 2026

Short answer

LEGIOMIX 2.0 is an electronic mixing valve for domestic hot water with programmable thermal disinfection and thermal shock. Through the Caleffi 755052 gateway it appears on BACnet MS/TP or BACnet IP with probe temperatures T1/T2, operating, motor and control status, ten alarm flags, I/O states, the clock, the mixing setpoint, disinfection settings and weekly schedule, recirculation time bands and start/stop/reset commands. All objects share one running ID sequence.

This page lists 85 BACnet objects for the Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 — 53 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Caleffi’s own free documentation, linked below.

Manufacturer
Caleffi
Model
LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052
Equipment
Electronic mixing valve (via gateway)
Equipment type
Valves & actuators
BACnet objects
85 (53 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
LEGIOMIX 2.0, Legiomix_2_0_6000_Series, 6002, LEGIOMIX 2.0 6000, Caleffi 755052, FPC-N54
Source document
Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 6 LEGIOMIX_2.0_6000_SERIES Modbus RTU mappings to BACnet · H0004703.03 · rev. 2024
Download CSV 85 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Caleffi’s current documentation and the live device before use. Not official Caleffi information. Terms of use.

BMS integration notes: Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052

Integration in brief

Add the Legiomix_2_0_6000_Series profile and the valve's Modbus Node-ID in the gateway, then read T1/T2, AI 7 status and the alarm BIs. Write AV 46 for the mixing setpoint and use BV 87 to reset active alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 46Set Point TemperatureMixed water setpointWrite
AI 3T1Probe T1 temperatureRead
AI 4T2Probe T2 temperatureRead
AI 7StatusStatus: mixing, shock or disinfectionRead
AI 24Motor StatusMotor stopped, opening or closingRead
BI 8Alarms AL01Alarm AL01Read
BV 87Reset active allarmsReset active alarmsWrite

Network setup

Watch out for

Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

85 of 85 shown
Type
Access
Show
Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 BACnet Points List
DescriptionStates
AI1ModelModel code (6002)Read
AI2ID ModbusModbus ID, 1-250Read
AImin3T1Temperature probe T1°C (°F)Read
AImin4T2Temperature probe T2°C (°F)Read
AI5ID NumberID number, 1701-9952Read
AI6Serial NumberSerial number, 0001-9999Read
AImin7StatusOperating statusRead0=Motor test, 1=Zero acquisition, 2=Full scale acquisition, 3=Water mixing status, 4=Thermal shock status, 5=Thermal disinfection status
BImin8Alarms AL01Alarm AL01Read1=AL01
BI9Alarms AL03Alarm AL03Read1=AL03
BI10Alarms AL04Alarm AL04Read1=AL04
BI11Alarms AL05Alarm AL05Read1=AL05
BI12Alarms AL06Alarm AL06Read1=AL06
BI13Alarms AL07Alarm AL07Read1=AL07
BI14Alarms AL08Alarm AL08Read1=AL08
BI15Alarms AL09Alarm AL09Read1=AL09
BI16Alarms AL10Alarm AL10Read1=AL10
BI17Alarms AL11Alarm AL11Read1=AL11
BI18IN1 StatusIN1 stateRead1=disabled, 0=enabled
BI19IN2 StatusIN2 stateRead1=disabled, 0=enabled
BI20OUT1 StatusOUT1 stateRead1=disabled, 0=enabled
BI21OUT2 StatusOUT2 stateRead1=disabled, 0=enabled
BI22OUT3 StatusOUT3 stateRead1=disabled, 0=enabled
AI23Adjustment StatusControl statusRead0=Not in progress, 1=On max temperature limit, 2=T1 enabled control, 3=T2 enabled control with d2 type, 4=T2 enabled control with d1 type, 5=ΔT measurement in progress
AImin24Motor StatusMotor statusRead0=Motor stopped, 1=Motor opening, 2=Motor closing
AI25Device Adjustment StatusRegulation band statusRead0=Without adjustment, 1=Adjustment on band 1, 2=Adjustment on band 2, 3=Adjustment on band 3, 4=Adjustment in position
AI26DNValve sizeRead0=DN15, 1=DN20, 2=DN25, 3=DN32, 4=DN40, 5=DN50
AI27SecondsClock seconds, 0-59Read
AI28Current DayDay of week, 1-7Read
AI29FirmwareFirmware versionRead
AI30SoftwareSoftware versionRead
AI31ChecksumChecksumRead
AI32Encoder PositionActuator encoder positionRead
AV33DayClock day, 1-31Write
AV34MonthClock month, 1-12Write
AV35YearClock year, 0-99Write
AV36HourClock hour, 0-23Write
AV37MinuteClock minute, 0-59Write
BV38Check BatteryBattery checkWrite1=confirmed, 0=not confirmed
BV39Day-hourDay/hour confirmationWrite1=confirmed, 0=not confirmed
BV40Daylight Saving TimeDaylight saving timeWrite1=enabled, 0=not disabled
BV41Time FormatClock formatWrite1=12H, 0=24H
BV42Temperature UnitTemperature unitWrite1=°F, 0=°C
BV43U.S. daylight Saving TimeUS daylight saving ruleWrite1=enabled, 0=disabled
BV44Disinfection ControlProbe used for disinfection controlWrite1=on T2, 0=on T1
BV45Encoder Steps AcquisitionStart encoder steps acquisitionWrite1=encoder steps acquisition
AVmin46Set Point TemperatureMixing setpoint, 35-65 °C°C (°F)Write
AV47Disinfection TypeDisinfection settings, bit-codedWritebit 1-0: 00=In1, 01=In2, 10=In3; bit 4: propagation time 1=fixed, 0=calculated; bit 5: ECO 1=enabled; bit 7: control on temp 1=d1, 0=d2
AV51Minimum Disinfection TemperatureMinimum disinfection temperature, 50-85 °C°C (°F)Write
AV52Minimum Disinfection TimeMinimum disinfection time, 1-600Write
AV53Maximum Disinfection TimeMaximum disinfection time, 3-900Write
BV54Disinfection Start Day MondayDisinfection on MondayWrite1=enabled, 0=disabled
BV55Disinfection Start Day TuesdayDisinfection on TuesdayWrite1=enabled, 0=disabled
BV56Disinfection Start Day WednesdayDisinfection on WednesdayWrite1=enabled, 0=disabled
BV57Disinfection Start Day ThursdayDisinfection on ThursdayWrite1=enabled, 0=disabled
BV58Disinfection Start Day FridayDisinfection on FridayWrite1=enabled, 0=disabled
BV59Disinfection Start Day SaturdayDisinfection on SaturdayWrite1=enabled, 0=disabled
BV60Disinfection Start Day SundayDisinfection on SundayWrite1=enabled, 0=disabled
AV61Monday Disinfection Starting MinuteDisinfection start minute, MondayWrite
AV62Monday Disinfection Starting HourDisinfection start hour, MondayWrite
AV63Tuesday Disinfection Starting MinuteDisinfection start minute, TuesdayWrite
AV64Tuesday Disinfection Starting HourDisinfection start hour, TuesdayWrite
AV65Wednesday Disinfection Starting MinuteDisinfection start minute, WednesdayWrite
AV66Wednesday Disinfection Starting HourDisinfection start hour, WednesdayWrite
AV67Thursday Disinfection Starting MinuteDisinfection start minute, ThursdayWrite
AV68Thursday Disinfection Starting HourDisinfection start hour, ThursdayWrite
AV69Friday Disinfection Starting MinuteDisinfection start minute, FridayWrite
AV70Friday Disinfection Starting HourDisinfection start hour, FridayWrite
AV71Saturday Disinfection Starting MinuteDisinfection start minute, SaturdayWrite
AV72Saturday Disinfection Starting HourDisinfection start hour, SaturdayWrite
AV73Sunday Disinfection Starting MinuteDisinfection start minute, SundayWrite
AV74Sunday Disinfection Starting HourDisinfection start hour, SundayWrite
BV75Time Bands 1 Ric StartRecirculation time band 1Write1=enabled, 0=disabled
BV76Time Bands 2 Ric StartRecirculation time band 2Write1=enabled, 0=disabled
BV77Time Bands 3 Ric StartRecirculation time band 3Write1=enabled, 0=disabled
BV78Time Bands 4 Ric StartRecirculation time band 4Write1=enabled, 0=disabled
BV79Time Bands 5 Ric StartRecirculation time band 5Write1=enabled, 0=disabled
BV80Time Bands 6 Ric StartRecirculation time band 6Write1=enabled, 0=disabled
AV81Minimum Thermal Shock TemperatureMinimum thermal shock temperature, 65-85 °C°C (°F)Write
AV82Minimum Thermal Shock TimeMinimum thermal shock time, 0-4320Write
AV83Maximum Thermal Shock TimeMaximum thermal shock time, 0-4320Write
AV84Maximum Temperature LimitMaximum temperature limit, 65-85 °C°C (°F)Write
BV85Thermal SchockThermal shock start/stopWrite1=Start, 0=Stop
AV86DisinfectionDisinfection start/stopWrite1=Start, 0=Stop
BVmin87Reset active allarmsReset active alarmsWrite0=no allarm, 1=allarm
BV88Reset istorical allarmsReset alarm historyWrite0=no allarm, 1=allarm
Object ID lookup: Caleffi LEGIOMIX 2.0 6000 series mixing valve via gateway 755052 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052

How many BACnet points does the Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 have?

This list has 85 BACnet objects: 17 analog inputs, 29 analog values, 15 binary inputs, 24 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 BACnet points are writable?

53 of the 85 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052 BACnet documentation?

The source is Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 6 LEGIOMIX_2.0_6000_SERIES Modbus RTU mappings to BACnet (H0004703.03), revision 2024, published free by Caleffi at https://www.caleffi.com/sites/default/files/media/external-file/h0004703_EN.pdf.

What are the minimum BACnet points to integrate the Caleffi LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052?

Start with AV 46 Set Point Temperature (Mixed water setpoint); AI 3 T1 (Probe T1 temperature); AI 4 T2 (Probe T2 temperature); AI 7 Status (Status: mixing, shock or disinfection); AI 24 Motor Status (Motor stopped, opening or closing); BI 8 Alarms AL01 (Alarm AL01); BV 87 Reset active allarms (Reset active alarms).

How do I check these points on the real LEGIOMIX 2.0 6000 series (6002) mixing valve via gateway 755052?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Caleffi BACnet points lists

Source: Start-up Guide for the gateway MODBUS RTU / BACnet, Code 755052, Appendix 6 LEGIOMIX_2.0_6000_SERIES Modbus RTU mappings to BACnet · H0004703.03 · rev. 2024. Object names, instances and units are reproduced as published; descriptions are our own.