Samsung's DMS2.5 BACnet gateway makes every unit its own BACnet device and builds the device ID from the network number and the unit address. Enter them to get the device ID, or decode one.
The device ID is three parts written one after the other: DNET | CPP | XX. DNET is the gateway's network number (1-40), CPP = 400 + 16 x a + b for unit address a.b.c, and XX is the indoor address c (00-63) or 64 for an outdoor unit. Samsung's example: network 9, indoor unit 01.01.32 gives 9 | 417 | 32 = 941732.
Samsung calculator
The calculator needs JavaScript. The formula and a worked example are below.
Which unit is this device?
How the numbers are built
device ID = DNET x 100000 + (400 + 16a + b) x 100 + XX
| Part | Meaning | Range |
|---|---|---|
| DNET | Network No. set on the gateway's BACnet page (default 9) | 1-40 |
| a | OnOff (centralized) controller address, first part of a.b.c | 0-15 |
| b | Interface module (outdoor unit) address, second part | 0-15 |
| XX | Indoor unit address c, or 64 for an outdoor unit or the gateway | 00-64 |
Samsung shows unit addresses as a.b.c, for example 01.01.32: OnOff controller, interface module (outdoor unit), indoor unit. Each gateway on the same network needs its own Network No. Inside every unit device the object instances are small fixed numbers, listed under each unit type below.
Worked example: network 9, unit 01.01.32
The first objects for network 9, unit 01.01.32 on the MIM-B17BN, worked out with the formula above:
| Unit type | Device instance | For |
|---|---|---|
| Indoor unit | 941732 | Network No. (DNET) 9, OnOff controller address (a) 1, Interface module / outdoor address (b) 1, Indoor unit address (c) 32 |
| AHU kit | 941732 | Network No. (DNET) 9, OnOff controller address (a) 1, Interface module / outdoor address (b) 1, Indoor unit address (c) 32 |
| EHS (air-to-water) | 941732 | Network No. (DNET) 9, OnOff controller address (a) 1, Interface module / outdoor address (b) 1, Indoor unit address (c) 32 |
| ERV / ERV Plus | 941732 | Network No. (DNET) 9, OnOff controller address (a) 1, Interface module / outdoor address (b) 1, Indoor unit address (c) 32 |
| Outdoor unit (interface module) | 941764 | Network No. (DNET) 9, OnOff controller address (a) 1, Interface module / outdoor address (b) 1 |
| BACnet gateway | 990064 | Network No. (DNET) 9 |
| Centralized (OnOff) controller | 900064 | Network No. (DNET) 9, Controller / SIM / DI-DO address 0 |
| SIM / PIM | 910064 | Network No. (DNET) 9, Controller / SIM / DI-DO address 0 |
| DMS DI/DO | 930064 | Network No. (DNET) 9, Controller / SIM / DI-DO address 0 |
| DVM chiller | — |
Source
Formula and objects from DMS2.5 / BACnet Gateway MIM-B17BN / LonWorks Gateway MIM-B18BN User & installation manual · DB68-06095A-05 · rev. 2022-11 (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.
Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.
Questions
How do I work out a Samsung instance number?
The device ID is three parts written one after the other: DNET | CPP | XX. DNET is the gateway's network number (1-40), CPP = 400 + 16 x a + b for unit address a.b.c, and XX is the indoor address c (00-63) or 64 for an outdoor unit. Samsung's example: network 9, indoor unit 01.01.32 gives 9 | 417 | 32 = 941732.
Is the Samsung device ID a sum or the digits put together?
The digits put together: network number, then the 3-digit CPP code, then the 2-digit address. 9, 417 and 32 make 941732. As arithmetic that is DNET x 100000 + CPP x 100 + XX.
What device ID does an outdoor unit get?
The same DNET and CPP as the indoor units behind it, with 64 as the last two digits. Network 9, outdoor unit 01.01 works out to 941764 (our worked example from Samsung's table, not printed in the manual).
Are the address parts hex or decimal?
Samsung's manual does not say. Its only example (01.01.32) reads the same either way. If your DMS shows letters in an address, confirm the device ID with a scan.
Is this Samsung calculator official?
No. It applies the formula printed in Samsung's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.
More instance calculators
- Fujitsu UTY-VBGX VRF gatewayFujitsu's UTY-VBGX gateway puts the refrigerant system and unit address inside every instance number.
instance = point code x 10000 + refrigerant system x 100 + unit address - Mitsubishi Electric BAC-HD150 BM AdapterThe BAC-HD150 BM Adapter numbers every CITY MULTI group's objects as M-NET number, group number and point number.
instance = M-NET number x 10000 + group x 100 + point - Mitsubishi Electric AE-C400 / EW-C50With the BACnet license, the AE-C400 and EW-C50 number objects by class, address and point.
instance = class x 10000 + address x 100 + point - Mitsubishi Electric PAC-YG31CDA (G-50A)The legacy PAC-YG31CDA BACnet interface serves up to ten G-50A controllers and numbers each group's objects by G-50A number, group and point.
instance = G-50A number x 10000 + group x 100 + point - Mitsubishi Electric Procon BAC-IP/50The Procon BAC-IP/50 gives every unit on its G-50 a block of objects numbered 1, the 3-digit unit address and the point number.
instance = 100000 + unit address x 100 + point - Daikin DMS502B71 VRV BACnet interfaceThe Daikin DMS502B71 BACnet interface gives every VRV indoor unit group the same 35-member object template.
instance = unit number x 256 + member number - Toshiba BMS-IFBN1281U BN interfaceToshiba Carrier's BN interface gives every indoor unit the same block of objects, numbered from the unit's central control address and a fixed function code.
instance = central control address x 256 + function code - Gree GMS GW BACnet converterGree's GMS GW 1 and GMS GW 12 converters number every split unit's objects from its line and remote control address.
instance = class x 1048576 + (line - 1) x 131072 + address x 256 + object